PPI ScanLog 16 Channel Recorder and Pen-Drive Interface Instruction Manual

June 11, 2024
PPI

ScanLog (Pen Drive)
4 / 8 / 16 Channel Recorder + Pen-Drive Interface
Operation Manual

ScanLog 16 Channel Recorder and Pen-Drive Interface

This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net

OPERATOR PARAMETERS

Parameters Settings
Stop Copy No Yes
Select Option 1. None

2. Copy (New)
3. Re-copy (Old)
4. Read Chan Names
5. Recover
(Default : None)
Batch Start| No Yes
Balance Slot Time| Read Only
Batch Stop| No Yes

ALARM SETTINGS

Parameters Settings (Default Value)
Select Channel Pen Drive Version For 4C : Channel-1 to

Channel-4
For 8C : Channel-1 to
Channel-8
For 16C : Channel-1 to
Channel-16
Select Alarm| AL1, AL2, AL3, AL4
(The actual available options depends on the numbers of Alarms set per channel on
Alarm configuration page)
AL1 Type| None Process Low Process High (Default : None)
AL1 Setpoint| Min. to Max. of selected input type range
(Default : 0)
AL1 Hysteresis| 1 to 30000
(Default : 20)
AL1 Inhibit| No Yes
(Default : No)

DEVICE CONFIGURATION

Parameters Settings (Default Value)
Delete Records No Yes

(Default : No)

CHANNEL CONFIGURATION

Parameters Settings (Default Value)
All Chan Common No Yes

(Default : No)
Select Channel| Pen Drive Version For 4C : Channel-1 to Channel-4
For 8C : Channel-1 to
Channel-8
For 16C : Channel-1 to
Channel-16
Parameters| Settings (Default Value)
Input Type| Refer Table 1
(Default : 0 to 10 V)
Resolution| Refer Table 1
Signal Low| | Input Type| Settings| Default
---|---|---
0 to 20mA| 0.00 to Signal High| 0
4 to 20mA| 4.00 to Signal High| 4
0 to 80mV| 0.00 to Signal High| 0
0 to 1.25V| 0.000 to Signal High| 0
0 to 5V| 0.000 to Signal High| 0
0 to 10V| 0.00 to Signal High| 0
1 to 5V| 1.000 to Signal High| 1
Signal High| | Input Type| Settings| Default
---|---|---
0 to 20mA| Signal Low to 20.00| 20
4 to 20mA| Signal Low to 20.00| 20
0 to 80mV| Signal Low to 80.00| 80
0 to 1.25V| Signal Low to 1.250| 1.25
0 to 5V| Signal Low to 5.000| 5
0 to 10V| Signal Low to 10.00| 10
1 to 5V| Signal Low to 5.000| 5
Range Low| -30000 to +30000
(Default : 0)
Range High| -30000 to +30000
(Default : 1000)
Low Clipping| Disable Enable
(Default : Disable)
Low Clip Val| -30000 to High Clip Val (Default : 0)
High Clipping| Disable Enable
(Default : Disable)
High Clip Val| Low Clip Val to 30000 (Default : 1000)
Zero Offset| -30000 to +30000
(Default : 0)

ALARM CONFIGURATION

Parameters Settings (Default Value)
Alarms/chan 1 to 4

(Default : 4)

RECORDER CONFIGURATION

Parameters Settings (Default Value)
Normal Interval 0:00:00 (H:MM:SS) **to

2:30:00 (H:MM:SS)
(Default : 0:00:30)
Zoom Interval| 0:00:00 (H:MM:SS) to
2:30:00 (H:MM:SS)
(Default : 0:00:10)
Alrm Toggl Rec| Disable Enable
(Default : Enable)
Recording Mode| Continuous Batch
(Default : Continuous)
Batch Time| 0:01 (HH:MM) to
250:00 (HHH:MM)
(Default : 1:00)
Batch Start Batch Stop**| No Yes

RTC SETTING

Parameters Settings
Time (HH:MM) 0.0 to 23:59
Date 1 to 31
Month 1 to 12
Year 2000 to 2099
Unique ID Number Read Only

UTILITIES

Parameters Settings (Default Value)
Lock Unlock No Yes

(Default : No)
Factory Default| No Yes
(Default : No)
TABLE 1

Option| Range (Min. to Max.)| Resolution & Unit
Type J (Fe-K)| 0.0 to +960.0°C| 1 °C  or 0.1 °C
Type K (Cr-Al)| -200.0 to +1376.0°C
Type T (Cu-Con)| -200.0 to +387.0°C
Type R (Rh-13%)| 0.0 to +1771.0°C
Type S (Rh-10%)| 0.0 to +1768.0°C
Type B| 0.0 to +1826.0°C
Type N| 0.0 to +1314.0°C
Reserved for customer specific Thermocouple type not listed above. The type shall be specified in accordance with the ordered (optional on request) Thermocouple type.
RTD Pt100| -199.9 to +600.0°C| 1°C or 0.1 °C
0 to 20 mA| -30000 to 30000 units| 1
0.1
0.01
0.001
units
4 to 20 mA
0 to 80 mV
Reserved
0 to 1.25 V| -30000 to 30000 units
0 to 5 V
0 to 10 V
1 to 5 V

FRONT PANEL KEYS

FRONT PANEL KEYS

Symbol| Key| Function
****| Scroll| Press to scroll through various Process Information Screens in Normal Operation Mode.


| Alarm Acknowledge| Press to acknowledge / mute alarm output (if active) & to view Alarm Status screen.
| DOWN| Press to decrease the parameter value. Pressing once decreases the value by one count; keeping pressed speeds up the change.
| UP| Press to increase the parameter value. Pressing once increases the value by one count; keeping pressed speeds up the change.
| SET-UP|

Press to enter or exit set-up mode.

**| ENTER| In Run Mode, press to toggle between Auto & Manual Scan Mode. (Only for 16 Channel version)
** In Set-up Mode, press to store the set parameter value and to scroll to the next parameter.

SCROLLING THROUGH VARIOUS SCREENS

The screen shown below are for 4 Channel Version. The sequence is the same for 8 & 16 Channel Version.

PPI ScanLog 16 Channel Recorder and Pen Drive Interface - Channel
Version

VIEWING ALARM STATUS SCREEN

PPI ScanLog 16 Channel Recorder and Pen Drive Interface - STATUS
SCREEN

16 Channel With Alarm Relay Outputs

PPI ScanLog 16 Channel Recorder and Pen Drive Interface - Relay
Outputs

ELECTRICAL CONNECTIONS

PPI ScanLog 16 Channel Recorder and Pen Drive Interface - Relay
Outputs1

101, Diamond Industrial Estate, Navghar,
Vasai Road (E), Dist. Palghar – 401 210.
Sales : 8208199048 / 8208141446
Support : 07498799226 / 08767395333
E: sales@ppiindia.net,
support@ppiindia.net

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals