PPI ScanLog 96 Single Dual Channels Universal Process Data Logger with PC Software Instruction Manual

June 11, 2024
PPI

PPI ScanLog 96 Single Dual Channels Universal Process Data Logger with PC

Software

PPI ScanLog-96-Single-Dual-Channels-Universal-Process-Data-Logger-with-PC-
Software-PRODUCT

This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net

OPERATOR PARAMETERS

Parameters Settings
Batch Start No Yes
Batch Stop No Yes

ALARM SETTINGS

Parameters Settings (Default Value)
Select Channel ( Available only for Dual Channel Version ) 1 or 2
Select Alarm AL1, AL2, AL3, AL4

(The actual available options depends on the numbers of Alarms set per channel on

Alarm configuration page)

ALx Type

x = 1, 2, 3 or 4

| None Process Low Process High (Default : None)
ALx Setpoint

x = 1, 2, 3 or 4

| Min. to Max. of selected input type range

(Default : 0)

ALx Hysteresis

x = 1, 2, 3 or 4

| 1 to 30000

(Default : 20)

ALx Inhibit

x = 1, 2, 3 or 4

| No Yes

(Default : No)

DEVICE CONFIGURATION

Parameters Settings (Default Value)
Scan Rate 1 Sec. to 99 Sec. (Default : 3 Sec.)
Delete Records No Yes

(Default : No)

Recorder ID| 1 to 127

(Default : 1)

CHANNEL CONFIGURATION

Parameters Settings (Default Value)

Select Channel ( This parameter is available for Dual

Channel Version only )

| ****

1 or 2

Input Type| Refer Table 1

(Default : 0 to 10 V)

Resolution| Refer Table 1
Parameters| Settings (Default Value)
---|---
Units| Refer Table 2 (Default : °C)
Signal Low| | Input Type| Settings| Default
---|---|---
0 to 20mA| 0.00 to Signal High| 0.00
4 to 20mA| 4.00 to Signal High| 4.00
0 to 80mV| 0.00 to Signal High| 0.00
0 to 1.25V| 0.000 to Signal High| 0.000
0 to 5V| 0.000 to Signal High| 0.000
0 to 10V| 0.00 to Signal High| 0.00
1 to 5V| 1.000 to Signal High| 1.000
Signal High| | Input Type| Settings| Default
---|---|---
0 to 20mA| Signal Low to 20.00| 20.00
4 to 20mA| Signal Low to 20.00| 20.00
0 to 80mV| Signal Low to 80.00| 80.00
0 to 1.25V| Signal Low to 1.250| 1.250
0 to 5V| Signal Low to 5.000| 5.000
0 to 10V| Signal Low to 10.00| 10.00
1 to 5V| Signal Low to 5.000| 5.000
Range Low| -30000 to +30000

(Default : 0.0)

Range High| -30000 to +30000

(Default : 1000)

Low Clipping| Disable Enable

(Default : Disable)

Low Clip Val| -30000 to High Clip Val (Default : 0)
High Clipping| Disable Enable

(Default : Disable)

High Clip Val| Low Clip Val to 30000 (Default : 1000)
Zero Offset| -30000 to +30000

(Default : 0)

ALARM CONFIGURATION

Parameters Settings (Default Value)
Alarms/Chan 1 to 4

(Default : 4)

Relay-1 Logic Relay-2 Logic| Normal  Reverse  (Default : Normal)

RECORDER CONFIGURATION

Parameters Settings (Default Value)
Normal Interval 0:00:00 (H:MM:SS) to

2:30:00 (H:MM:SS)

(Default : 0:00:30)

Zoom Interval| 0:00:00 (H:MM:SS) to

2:30:00 (H:MM:SS)

(Default : 0:00:10)

Alrm Toggl Rec| Disable Enable

(Default : Enable)

Recording Mode| Continuous Batch

(Default : Continuous)

Batch Time| 0:01 (HH:MM) to

250:00 (HHH:MM)

(Default : 1:00)

Batch Start Batch Stop| No Yes

RTC SETTING

Parameters Settings
Time (HH:MM) 0.0 to 23:59
Date 1 to 31
Month 1 to 12
Year 2000 to 2099

UTILITIES

Parameters Settings (Default Value)
Lock Unlock No Yes

(Default : No)

Factory Default| No Yes

(Default : No)

TABLE – 1

Option| Range (Min. to Max.)| Resolution & Unit
Type J (Fe-K)| 0.0 to +960.0°C / +32.0 to +1760.0°F| ****






1 °C /°F

or

0.1 °C /°F

Type K (Cr-Al)| -200.0 to +1376.0°C / -328.0 to +2508.0°F
Type T (Cu-Con)| -200.0 to +387.0°C / -328.0 to +728.0°F
Type R (Rh-13%)| 0.0 to +1771.0°C / +32.0 to +3219.0°F
Type S (Rh-10%)| 0.0 to +1768.0°C / +32.0 to +3214.0°F
Type B| 0.0 to +1826.0°C / +32.0 to +3218.0°F
Type N| 0.0 to +1314.0°C / +32.0 to +2397.0°F
Reserved for customer-specific Thermocouple types not listed above. The type shall be specified in accordance with the ordered (optional on request) Thermocouple type.


RTD Pt100

| -199 to +600 °C / -328 to +1112 °F

or

-199.9 to +600.0 °C / -328.0 to +1112.0 °F

| 1°C

or

0.1 °C

0 to 20 mA| ****

-30000 to 30000 units

| ****



1 Unit

0.1 Unit

0.01 Unit

0.001 Unit

4 to 20 mA
0 to 80 mV
Reserved
0 to 1.25 V| ****


-30000 to 30000 units

0 to 5 V
0 to 10 V
1 to 5 V
TABLE 2

Option| Description
°C| Degree Centigrade
°F| Degree Fahrenheit
(none)| No Unit (Blank)
°K| Degree Kelvin
EU| Engineering Units
%| Percentage
Pa| Pascals
Mpa| Mpascals
kPa| Kpascals
Option| Description
---|---
bar| Bar
mbar| Milli bar
psi| PSI
kg/sq.cm| kg/cm²
mmH2O| mm water gauge
inH2O| Inches water gauge
mmHg| mm mercury
Torr| Torr
litre/hr| Litres per hour
litre/min| Litres per minute
%RH| % Relative Humidity
%O2| % Oxygen
%CO2| % Carbon di-oxide
%CP| % Carbon Potential
V| Volts
A| Amps
mA| Milli Amps
mV| Milli Volts
ohm| Ohms
ppm| Parts per million
rpm| Revolutions per minute
mSec| Milli seconds
Sec| Seconds
min| Minutes
hrs| Hours
PH| PH
%PH| %PH
miles/hr| Miles per hour
mg| Milli grams
g| Grams
kg| Kilo grams

FRONT PANEL DISPLAY & KEYS

PPI ScanLog-96-Single-Dual-Channels-
Universal-Process-Data-Logger-with-PC-Software-FIG-
\(5\)

Symbol Key Function
SET-UP Press to enter / exit Set-up Mode.
DOWN Press to decrease the parameter value. Pressing once decreases the

value by one count; holding the key pressed speeds up the change.
| UP| Press to increase the parameter value. Pressing once increases the value by one count; holding the key pressed speeds up the change.

|

ENTER /

Alarm ACK

| Press to store the set parameter value and to scroll to the next parameter in Set-up Mode.

Press to acknowledge / mute alarm output (if active).

SCROLLING THROUGH VARIOUS SCREENS

PPI ScanLog-96-Single-Dual-Channels-
Universal-Process-Data-Logger-with-PC-Software-FIG-
\(6\) PPI
ScanLog-96-Single-Dual-Channels-Universal-Process-Data-Logger-with-PC-
Software-FIG- \(7\)

AUTO/MANUAL SCAN MODE SELECTION

Press ENTER key for approximately for 5 Seconds to toggle between Auto & Manual Scan Mode. In Manual Mode use UP / DOWN Keys to Select Channels.

ELECTRICAL CONNECTIONS

Notes:

  1. Analog Input 2 connections (terminals 23 to 28) are applicable only for Dual Channel version.
  2. Excitation Voltage output (terminals 15 & 22) is available optionally.
  3. Serial Commutation Port (terminals 11 & 12) is available for PC Interface Version only

101, Diamond Industrial Estate, Navghar, Vasai Road (E), Dist. Palghar – 401 210.
Sales : 8208199048 / 8208141446
Support : 07498799226 / 08767395333
E : sales@ppiindia.net, support@ppiindia.net

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals