1. Technical Specifications
2. Installation
⚠ Warnings:
- Installation of the sensor involves connecting it to the mains supply. This work must be carried out by a specialist in accordance with electrotechnical regulations.
- Disconnect supply before installing.
3. Rotary Switch Settings
4. Functions
4.1 Tri-level Control (Corridor Function)
Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas require a light change notice before switch-off. It offers 3 levels of light: 100%–>dimmed light–>off; and 2 periods of selectable waiting time: motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection area.
4.2 Synchronization Function
By connecting the “SYNC” terminals in parallel (see wiring diagram), no matter which sensor detects motion, all HMW25 in the group will turn on the lights when surrounding natural light is below the daylight threshold. The sensor module is shared and the detection area could be widely enlarged in this way.
4.3 Lux Off Function
The built-in daylight sensor can read ambient natural light and switch off the fixture automatically whenever artificial light is unneeded (natural light lux level exceeds daylight threshold). Note: if the stand-by time is preset at “+”, the fixture never switches off even when natural light is sufficient.
4.4 Semi-auto Function (Absence Detection)
The motion sensor is employed, but only activated on the manual press of the push switch, light keeps on in the presence, and dims down in the absence, and eventually switches off automatically in the long absence.
4.5 Manual Override
With the help of push-switch, this sensor maybe over-ridden by the end-users to switch on/off the lights manually, or adjust the light brightness during motion hold-time. This makes the product more user-friendly and offers more options to fit for extra-ordinary demands.
- Short push (<1s): on/off function; ON ¹ OFF: the light turns off immediately and cannot be lighten for a certain time (equals to hold time preset) even there is movement is detected. After this period, the sensor goes back to auto sensor mode. OFF ¹ ON: the light turns on 100% and goes to auto sensor mode, even when ambient Lux level exceeds the daylight threshold.
- Long push (>1s): adjust the maximum brightness (between 10% and 100%) during hold-time. Both the settings on DIP switch and manual override can overwrite each other, the last adjustment remains in memory.
5. Wiring Diagram
6. Detection Pattern
7. Description of the Button Functions (remote control HRC-11)
Permanent ON/OFF [ button 1 ]
Press button 1 ,to select permanent ON or permanent OFF mode.
- Press button 2 / 4 to resume automatic operation. The mode will change to AUTO Mode after power failure.
RESET [ button 2 ]
Press button 2 , all settings go back to the rotary switch settings.
Shift [ button 3 ]
Press button 3 , the LED on the top left corner is on for indication. All
values / settings in RED are in valid for 20 seconds.
Auto Mode [ button 4 ]
Press button 4 to initiate automatic mode. The sensor starts working and all
settings remain as before the light was switched ON/OFF.
Semi-auto Mode [ button 3 & 4 ] 1. Press button 3 Shift (the red LED is on for
indication). 2. Press button 4 to initiate semi-auto mode. The fixture is
manually
on by push-switch and automatically off in semi-auto mode.
Power output [ button 5 ]
Press button 5 , the light output shifts between 80% and 100%. Note: the
function of “Sensor off” and “Twilight” are disabled.
Brightness +/- [ button 6 ]
Press button 6 to adjust the light brightness between 10%~100% .
Scene prog. [ zone 7 ] (One-key-commissioning)
- Press button “start” to program.
- Select the buttons in 8 “Detection range”, 9 / 10 “Daylight threshold”, 11 “Hold time”, 12 “Stand-by time”, 13 “Stand-by dimming level” to set all parameters.
- Press button “Memory” to save all the settings programmed in the remote control.
- Press button “Apply” to set the settings to each sensor unit(s). For example, to pre-set detection range 100%, daylight threshold Disable, hold time 5min, stand-by time +, stand-by dimming level 30%, steps should be: Press button 7 Start, button 8 100%, 10 Disable, 3 Shift, 11 5min, 3 Shift, 12 +, 13 30%, 7 Memory. By pointing to the sensor unit(s) and pressing 7 Apply, all settings are passed on the sensor(s).
Detection range [ zone 8 ]
Press buttons in zone 8 to set detection range at 100% / 75% / 50% / 10%.
Daylight threshold [ zone 9 ]
Press buttons in zone 9 to set the daylight sensor at 2Lux / 10Lux / 50Lux /
100Lux / 300Lux / 500Lux or Disable. Note: To set daylight sensor at 100Lux /
300 Lux / 500Lux, press button 3 Shift at first.
Ambient daylight threshold [ button 10 ]
- Press button 3 Shift, the red LED is on for indication.
- Press button 10, the ambient lux level is sampled and set as the new daylight threshold.
Hold time [ zone 11 ]
Press buttons in zone 11 to set the hold time at 2s / 30s / 1min / 5min /
10min / 15min / 20min / 30min. Note: 1.To set hold-time at 30s / 5min / 15min
/ 30min, press button 3 Shift at first. 2. 2s is for test purpose only, stand-
by period and daylight sensor settings are disabled in this mode. *To exit
from Test mode, press button 2 or any button in zone 11 .
Stand-by time [ zone 12 ]
Press buttons in zone 12 to set the stand-by period at 0s / 10s / 1min / 5min
/ 10min / 30min / 1h / +. Note: “0s” means on/off control; “+” means bi-level
control, 100% on when motion detected, and remains at the stand-by dimming
level when no presence after hold-time.
Stand-by dimming level [ zone 13 ]
Press buttons in zone 13 to set the stand-by dimming level at 10% / 20% / 30%
/ 50%. Note: the function of 24h/12h/4h/30s are disabled.
Dual tech & RF mode [ zone 14 ]
All buttons in zone 14 are disabled.
8. Trouble Shooting
Hytronik Industrial Ltd. | www.hytronik.com 3rd Floor, block C, complex building, 155#, Bai’gang road south, Bai’gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023 Tel: 86-752-2772020 Fax: 86-752-2777877