Dextra Rubix Recessed Installation Guide
- June 9, 2024
- Dextra
Table of Contents
Rubix Recessed Installation
Installation Guide
Rubix Recessed
WARNING: Luminaire must be earthed. Risk of electric shock from LED
boards if operated with cover removed. Installation / operation outside of
luminaires intended scope invalidates warranty. Suitable only for domestic /
light industrial / industrial applications within the scope of EN55015. Tested
to compliance with BSEN 60598: specification for general requirements and
tests. Must be installed by a suitably qualified person in accordance with all
relevant legislation. Ambient operating temperature of 0°C to 25°C. If maximum
operating temperature is exceeded luminaire will automatically dim / switch
off.
Terminal blocks are rated to 16A unless stated otherwise. The light source
contained in this luminaire shall only be replaced by the manufacturer or his
service agent or a similar qualified person.
LUMINAIRES WITH EMERGENCY PACK: When supply is isolated battery output
terminals may be live if battery is connected. Isolate mains and battery
before servicing. Emergency luminaires require unswitched live connection
taken from same phase as switched supply. When unswitched supply is connected
status indicator illuminates green, when unswitched supply is disconnected
indicator extinguishes and luminaire operates in emergency mode. 24 hour
charge period required before undertaking full discharge test. Emergency test
sheets provided should be used to record all emergency tests. Batteries should
be replaced when 3 hour duration is not met. Excessive switching of permanent
live may result in premature battery failure. Battery electrolyte can be
harmful to eyes / open wounds, do not puncture, if electrolyte touches skin /
eyes flush with water. Do not incinerate batteries.
1. Lift and tilt the lay-in frame into the ceiling grid as shown.| 2.
Carefully lift and tilt the luminaire into the frame.
---|---
|
3. Remove screwfrom terminal box and remove lid.| 4. Wire mains cable(s)
into relevant marked terminals and replace cover and screw. Ensure cable
clamps are engaged fully.
|
5. For a pull-up version, insert tile into ceiling grid and use the Lumafix
brackets to secure to the rear of ceiling grid.| 6. As previously
demonstrated in steps 2 – 4, install luminaire and wire mains cable(s) as
required.
|
Maintenance
- Disconnect luminaire before undertaking any maintenanceor cleaning.
- Cleaning should be undertaken on external partsof the luminaire only using a slightly damp lint free cloth.
- To access LED tray use a pan pozi screwdriver to remove screws.
- Use a pan pozi driver to remove components.
- Please contact Dextra for assistance with spare components supply.
220-240V / 50-60Hz IP20
Terminal Labelling:
Power
L1| Switched Live
E **| Earth
N| Neutral
Emergency
L2| Unswitched Live
DA/AT3| DALI Autotest
A/AT3| DALI Autotest
Dimming**
-/D1/DA| Analogue/DSI/DALI
+/D2/DA| Analogue/DSI/DALI
L3| Switch Dim /Corridor Function