Dextra Ineal 46 CELLULAR Installation Guide
- June 9, 2024
- Dextra
Table of Contents
Ineal 46 Installation
Installation Guide
Ineal 46 CELLULAR
WARNING: Luminaire must be earthed. Risk of electric shock from LED
boards if operated with cover removed. Installation / operation outside of
luminaires intended scope invalidates warranty. Suitable only for domestic /
light industrial / industrial applications within the scope of EN55015. Tested
to compliance with BSEN 60598: specification for general requirements and
tests. Must be installed by a suitably qualified person in accordance with all
relevant legislation. Ambient operating temperature of 0°C to 25°C. If maximum
operating temperature is exceeded luminaire will automatically dim / switch
off. Terminal blocks are rated to 16A unless stated otherwise. The light
source is non replaceable.
LUMINAIRES WITH EMERGENCY PACK: When supply is isolated battery output
terminals may be live if battery is connected. Isolate mains and battery
before servicing. Emergency luminaires require unswitched live connection
taken from same phase as switched supply. When unswitched supply is connected
status indicator illuminates green, when unswitched supply is disconnected
indicator extinguishes and luminaire operates in emergency mode. 24 hour
charge period required before undertaking full discharge test. Emergency test
sheets provided should be used to record all emergency tests. Batteries should
be replaced when 3 hour duration is not met. Excessive switching of permanent
live may result in premature battery failure. Battery electrolyte can be
harmful to eyes / open wounds, do not puncture, if electrolyte touches skin /
eyes flush with water. Do not incinerate batteries.
1. All variations:| 2. Installation for standard fittings ONLY:
Ensure the quarter turn is aligned correctly and located on the same side as
the locking pin for the track adaptor.
---|---
|
3. Offer the luminaire up to the track. Ensure both the track adaptor and
quarter turn are pushed inside the track.| 4. (1) Rotate the lever to lock
the track adaptor in place.
(2) Now that it’s locked, rotate the quarter turn by 90 degrees.
|
5. Rotate to select the desired circuit.| 6. Installation for DALI emergency
fittings ONLY:
When installing a DALI emergency fitting, please ensure the global track is
configured as shown above.
|
7. Rotate the two levers to lock the DALI adaptor to the track. You may
require a tool to rotate the lever.| 8. Once locked adjust lever to select
the desired circuit.
|
9. EMERGENCY FITTINGS ONLY: Rotate the lever then insert the locking
screw into the mechanical lock.| 10. Moving the luminaire
If the luminaire needs to be moved at any point, ensure the track adaptor is
unlocked and the corresponding quarter turn/mechanical lock(s) are
disengaged.
This will prevent any damage to the luminaire.
|
220-240V / 50-60Hz IP20
Terminal Labelling:
Power
L1| Switched Live
E **| Earth
N| Neutral
Emergency
L2| Unswitched Live
DA/AT3| DALI Autotest
A/AT3| DALI Autotest
Dimming**
-/D1/DA| Analogue/DSI/DALI
+/D2/DA| Analogue/DSI/DALI
L3| Switch Dim /Corridor Function
DIL-0458-0001
Revision – E