Dextra Rubix Surface Flush Light Installation Guide
- June 9, 2024
- Dextra
Table of Contents
Rubix Surface Flush Light
Installation Guide
Rubix Surface Flush Light
220-240V / 50-60Hz IP20
Terminal Labelling:
Power
L1 | Switched Live |
---|---|
E **** | Earth |
N | Neutral |
Emergency
L2 | Unswitched Live |
---|---|
DA/AT3 | DALI Autotest |
DA/AT3 | DALI Autotest |
Dimming
-/D1/DA | Analogue/DSI/DALI |
---|---|
+/D2/DA | Analogue/DSI/DALI |
L3 | Switch Dim / Corridor Function |
WARNING: Luminaire must be earthed. Risk of electric shock from LED
boards if operated with cover removed. Installation/operation outside of
luminaires intended scope invalidates warranty. Suitable only for
domestic/light industrial/industrial applications within the scope of EN55015.
Tested to compliance with BSEN 60598:
specification for general requirements and tests. Must be installed by a
suitably qualified person in accordance with all relevant legislation. Ambient
operating temperature of 0°C to 25°C. If maximum operating temperature is
exceeded luminaire will automatically dim/switch off. Terminal blocks are
rated to 16A unless stated otherwise. The light source is non replaceable.
LUMINAIRES WITH EMERGENCY PACK:
When supply is isolated battery output terminals may be live if battery is
connected. Isolate mains and battery before servicing. Emergency luminaires
require Unswitched live connection taken from same phase as switched supply.
When Unswitched supply is connected status indicator illuminates green, when
Unswitched supply is disconnected indicator extinguishes and luminaire
operates in emergency mode. 24 hour charge period required before undertaking
full discharge test. Emergency test sheets provided should be used to record
all emergency tests. Batteries should be replaced when 3 hour duration is not
met. Excessive switching of permanent live may result in premature battery
failure. Battery electrolyte can be harmful to eyes/open wounds, do not
puncture, if electrolyte touches skin / eyes flush with water. Do not
incinerate batteries.
Secure the housing to ceiling using the
four screw holes in each corner. (Screw not supplied) Feed mains cable through
the cable grommet and wire into respective terminals. Ensure cable restraint
is used.
Attach both earth leads to earth tags. Connect the LED plug and sockets.
Attach the frame to the housing using the two carabiner clips as shown below.
Re-engage the frame ensuring no cables/ wires are trapped.
The same process applies to all sizes (600×600, 1200×600, 1200×230, and
1500×230).
Where a Sensor variant is used, the sensor lead must be reconnected to the
power supply before re-attaching the frame.
Where an Emergency version is used, the E3 indicator LED must be reattached to
its clip before re-attaching the frame
The caps in the ends of the 1500×230
and 1200×230 fittings can be removed to allow continuous conduit mounting.
DIL-0276-0001
Revision – F