Dextra Rubix Surface Flush Light Installation Guide

June 9, 2024
Dextra

Dextra logo Rubix Surface Flush Light
Installation Guide

Rubix Surface Flush Light

220-240V / 50-60Hz IP20

Terminal Labelling:
Power

L1 Switched Live
E **** Earth
N Neutral

Emergency

L2 Unswitched Live
DA/AT3 DALI Autotest
DA/AT3 DALI Autotest

Dimming

-/D1/DA Analogue/DSI/DALI
+/D2/DA Analogue/DSI/DALI
L3 Switch Dim / Corridor Function

WARNING: Luminaire must be earthed. Risk of electric shock from LED boards if operated with cover removed. Installation/operation outside of luminaires intended scope invalidates warranty. Suitable only for domestic/light industrial/industrial applications within the scope of EN55015.
Tested to compliance with BSEN 60598:
specification for general requirements and tests. Must be installed by a suitably qualified person in accordance with all relevant legislation. Ambient operating temperature of 0°C to 25°C. If maximum operating temperature is exceeded luminaire will automatically dim/switch off. Terminal blocks are rated to 16A unless stated otherwise. The light source is non replaceable.
LUMINAIRES WITH EMERGENCY PACK:
When supply is isolated battery output terminals may be live if battery is connected. Isolate mains and battery before servicing. Emergency luminaires require Unswitched live connection taken from same phase as switched supply. When Unswitched supply is connected status indicator illuminates green, when Unswitched supply is disconnected indicator extinguishes and luminaire operates in emergency mode. 24 hour charge period required before undertaking full discharge test. Emergency test sheets provided  should be used to record all emergency tests. Batteries should be replaced when 3 hour duration is not met. Excessive switching of permanent live may result in premature battery failure. Battery electrolyte can be harmful to eyes/open wounds, do not puncture, if electrolyte touches skin / eyes flush with water. Do not incinerate batteries.

Dextra Rubix Surface Flush Light - holes in each
cornerSecure the housing to ceiling using the four screw holes in each corner. (Screw not supplied) Dextra Rubix Surface
Flush Light - Ensure cableFeed mains cable through the cable grommet and wire into respective terminals. Ensure cable restraint is used.
Attach both earth leads to earth tags. Connect the LED plug and sockets.

Dextra Rubix Surface Flush Light - LED plugAttach the frame to the housing using the two carabiner clips as shown below.

Dextra Rubix Surface Flush Light - ensuring no cablesRe-engage the frame ensuring no cables/ wires are trapped.
The same process applies to all sizes (600×600, 1200×600, 1200×230, and 1500×230).
Where a Sensor variant is used, the sensor lead must be reconnected to the power supply before re-attaching the frame.
Where an Emergency version is used, the E3 indicator LED must be reattached to its clip before re-attaching the frame
Dextra Rubix Surface Flush Light - reattached to its
clipThe caps in the ends of the 1500×230 and 1200×230 fittings can be removed to allow continuous conduit mounting. Dextra Rubix Surface Flush Light - continuous conduit
mounting

DIL-0276-0001
Revision – F Dextra logo

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals