Dextra Tanek Luminaire Finder Installation Guide
- June 9, 2024
- Dextra
Table of Contents
Dextra Tanek Luminaire Finder
Terminal Labelling
Power
- L1 Switched Live
- E Earth
- N Neutral
Emergency
- L2 Unswitched Live
- DA/AT3 DALI Autotest
- DA/AT3 DALI Autotest
Dimming
- -/D1/DA Analogue/DSI/DALI
- +/D2/DA Analogue/DSI/DALI
- L3 Switch Dim / Corridor Function
WARNING
- Luminaire must be earthed. Risk of electric shock from LED boards if operated with cover removed.
- Installation/operation outside of luminaires intended scope invalidates warranty.
- Suitable only for domestic/light industrial/industrial applications within the scope of EN55015.
- Tested to compliance with BSEN 60598: specification for general requirements and tests.
- Must be installed by a suitably qualified person in accordance with all relevant legislation.
- Ambient operating temperature of 0°C to 25°C. If maximum operating temperature is exceeded luminaire will automatically dim/switch off.
- Terminal blocks are rated to 16A unless stated otherwise. The light source is nonreplaceable.
LUMINAIRES WITH EMERGENCY PACK
- When supply is isolated battery output terminals may be live if battery is connected.
- Isolate mains and battery before servicing.
- Emergency luminaires require unswitched live connection taken from same phase as switched supply.
- When unswitched supply is connected status indicator illuminates green, when unswitched supply is disconnected indicator extinguishes and luminaire operates in emergency mode.
- 24 hour charge period required before undertaking full discharge test.
- Emergency test sheets provided should be used to record all emergency tests.
- Batteries should be replaced when 3 hour duration is not met.
- Excessive switching of permanent live may result in premature battery failure.
- Battery electrolyte can be harmful to eyes / open wounds, do not puncture, if electrolyte touches skin/eyes flush with water.
- Do not incinerate batteries.
INSTALLATION
-
Carefully unpack the luminaire and undo the 10 x M5x20 socket screws in the frame and lift the entire frame from the housing.
-
Undo the 2 x M4x10 machine screws in the ends of the gear tray as show in the image and remove the gear tray from the housing.
-
Drill suitable fixings to suit required installation.
NOTE: IT IS THE CONTRACTORS RESPONSIBILITY TO ENSURE THE HOLES ARE SEALED. FAILURE TO SEAL THE HOLES WILL INVALIDATE THE LUMINAIRE’S IP RATING. -
Remove the female socket from the tray as shown and hard-wire to the mains supply.
-
Reconnect the plug to the tray leaving sufficient cable length to reach.
-
Carefully return the gear tray into the housing and secure into place with the 2 x M4x10 machine screws provided. Ensure the mains cable does not become trapped when doing so.
-
Feed the toggles on the tether wires through one of the 7mm rounds on the end brackets inside the housing. Hole location as shown to the right.
-
Reverse step 1 to secure the frame back onto the housing. Do not over tighten the socket head screws when replacing the frame. Tighten sufficiently so to provide a seal between the frame gasket and the housing.