Terminal Labelling

Power
L1 Switched Live
E Earth
N Neutral
Emergency
L2 Unswitched Live
DA/AT3 DALI Auto test
DA/AT3 DALI Autotest
Dimming
-/D1/DA Analogue/DSI/DALI
+/D2/DA Analogue/DSI/DALI
L3 Switch Dim / Corridor Function

WARNING: Luminaire must be earthed. Risk of electric shock from LED boards if operated with cover removed. Installation / operation outside of luminaires intended scope invalidates warranty. Suitable only for domestic / light industrial / industrial applications within the scope of EN55015. Tested to compliance with BSEN 60598: specification for general requirements and tests. Must be installed by a suitably qualified person in accordance with all relevant legislation. Ambient operating temperature of 0°C to 25°C. If maximum operating temperature is exceeded luminaire will automatically dim / switch off.
Terminal blocks are rated to 16A unless stated otherwise. The light source contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.
LUMINAIRES WITH EMERGENCY PACK : When supply is isolated battery output terminals may be live if battery is connected. Isolate mains and battery before servicing. Emergency luminaires require unswitched live connection taken from same phase as switched supply. When unswitched supply is connected status indicator illuminates green, when unswitched supply is disconnected indicator extinguishes and luminaire operates in emergency mode. 24 hour charge period required before undertaking full discharge test. Emergency test sheets provided should be used to record all emergency tests. Batteries should be replaced when 3 hour duration is not met. Excessive switching of permanent live may result in premature battery failure. Battery electrolyte can be harmful to eyes / open wounds, do not puncture, if electrolyte touches skin / eyes flush with water. Do not incinerate batteries.

Installation

  1. Ceiling cut out: 368mm x 153mm
    Tile Thickness: 4-25mm

  2. Wire into allocated terminals.

  3. Once electrical connection is made, offer fixture in to aperture. Retract 2No adjacent springs – fit in ceiling – retract remaining 2No springs to complete installation.

  4. Note:
    Ceiling patress required if being installed on fibre board ceilings.

Maintenance

  1. Disconnect luminaire before undertaking any maintenance or cleaning.
  2. Cleaning should be undertaken on external parts of the luminaire only using a slightly damp lint free cloth.
  3. To remove rear housing use a pan pozi screwdriver to remove screws.
  4. Use a pan pozi screwdriver to open remote box and remove components.
  5. Please contact Dextra for assistance with spare component supply.