CERBERUS PYROTRONICS SR-35 Supplementary Relay Owner’s Manual
- June 9, 2024
- CERBERUS PYROTRONICS
Table of Contents
CERBERUS PYROTRONICS SR-35 Supplementary Relay
Description
The SR-35 relay module is designed to activate or de-activate external circuit controls such as fan shutdown, door releases, and other fire related equipment. The SR-35 contains eight independent relays with 2 amp SPDT contacts. Each relay can be selected to operate either on a high going input signal from appropriate System 3 mod-ules or an open collector input signal such as those available on Cerberus Pyrotronics XL3, MXL and SXL systems. The position of actuation mode headers on each relay determines high going or low going signal activation. Power to operate the relays is provided from the 24 VDC system power supply. The SR-35 module occupies only one standard module position in the System 3 enclosure. All terminals are of the clamp type and will accommodate 2 wires of up to #14 gauge. The SR-35 is UL and ULC listed and NYMEA, FM, CSFM and City of Chicago approved.
Engineer and Architect Specifications
The Cerberus Pyrotronics Model SR-35 Supplementary Relay shall be provided for
control of external fire related circuits. The module shall contain eight (8)
independent 24 VDC relays fitted with SPDT contacts rated at 2 amp, 120 VAC or
30 VDC. Power to operate the relays shall be 24 VDC furnished by the system
power supply. Each relay shall be provided with a program plug that will
select either a high going input signal actuation or a low going signal.
A separate terminal shall be provided for individual actua-tion of each relay.
All terminals shall be of the clamp type and will accommodate 2 wires of up to
14 gauge.
The unit shall be UL and ULC listed and NYMEA, FM, CSFM and City of Chicago approved.
Electrical Information
Current Requirements
- Relays de-energized: None
- Relay Energized – High Going – 26 mA per relay
- Relay Energized – Low Going – 21 mA per relay
Ordering Information
Typical Wiring
NOTICE: The use of other than Cerberus Pyrotronics detectors and bases with Cerberus Pyrotronics control equipment will be considered a misapplication of Cerberus Pyrotronics equipment and as such void all warranties either expressed or implied with regards to loss, damage, liabilities and/or service problems.