CERBERUS PYROTRONICS CP-2HR Control Panel Owner’s Manual

June 9, 2024
CERBERUS PYROTRONICS

CERBERUS Logo Pyr-A-Lon ® 1301 Control Panel

ENGINEER AND ARCHITECT SPECIFICATIONS

CERBERUS PYROTRONICS CP 2HR Control Panel

Model CP-2HR

  • Class A or B Options
  • 3 Selective Abort Options
  • Failsafe Reset
  • Telltale Operation
  • Latch Action Until Reset
  • No Break Rods Necessary
  • Listed, FM Approved

Introduction

The Pyr-A-Lon6 Series MH Remote Manual Electric Control has been designed with extreme flexibility in mind to meet a wide variety of application requirements and operational sequences in connection with its basic function as a release control for Pyr-A-Lons 1301 Fire Extinguishing Systems. To comply with NFPA 12A, these controls are now available only with a dual action function involving a “push-in” tab, followed by the “pull-down” lever action. Each of the above actions may operate electrical contacts to achieve various electrical sequence func-tions as desired.
The Series MH Manual Controls are Underwriters Laboratories, Inc. listed and Factory Mutual approved.
Flexibility of Application
The basic standard model is the double action Model MH-501, which contains one normally open contact. It is intended for use with Cerberus Pyrotronics low voltage systems, but has a rating of 120 Vac for connec-tion to other systems. With the double action control, the optional switch on the first action may be used for supervisory indication of tampering with the control or for connection to a remote annunciator. It may also be used to alarm one zone of a cross-zoned fire extinguishing system where the second zone, releasing the HaIon 1301.

Technical Description

The Pyr-A-Lon Series MH Remote Manual Electric Control is constructed of durable molded poly carbonate material, matte-finished in red with raised letting in white. The housing incorporates a “push-in” tab which must be operated first, permitting access to the “pull-down” lever which, when operated, locks in position after releasing a spring-loaded contact switch. Restor-ing the system to normal can only be accomplished by opening the cover of the hinged housing with an uncommon tool”, and then closing and locking the cover.
All models are fitted with screw-type terminals for system interconnection. Provision is made for surface or semi-flush mounting to conduit boxes.
Engineer and Architect Specifications
The Remote Manual Electric Control shall be Pyr-A-Lon ® Model _____ (See chart for number) with Underwriters Laboratories, Inc. listing and Factory Mutual approval.
Double Action Model the double action control, which shall be on the non-code type, shall consist of a molded housing, fitted with a “pull-down” lever and a “push-in” tab. It shall be necessary to operate the “push-in” tab first to provide access to the “pull-down” lever, which, when operated, locks in position after releasing a spring-loaded contact switch to effect actuation of the release circuit.
The body of the control shall be hinged to a backplate assembly to which it is locked with a socket head screw.
Resetting the control after operation shall require opening the control momentarily, and then locking the body to the backplate. Provision shall be made for the surface or semi-flush mounting to conduit boxes.

Mounting Data

Accessories

Model No. Description Shipping Wt.
SB-5R Surface Mounting Box 2 1/2 lbs.
LTP Locking Tool Pacakge (Contains 2 tools) 1/2 lb.

Ordering and Electrical Information Double Action Type

Model No. Switch Contacts & Ratings
Main Action First Action

MH-501
MH-5170| N.O. SPST .75A @ 125VAC/DC
N.O. DPST 1A
@ 250 VAC/DC 3A @ 125 VAC/DC| N.O. SPST .75 @ 125 VAC/DC

Cerberus Pyrotronics 8 Ridgedale Avenue
Cedar Knolls, NJ 07927
Tel: 201-267-1300
FAX: 201-397-7008
Website:www.cerbpyro.com
4/97 5M CPY-IG
Printed in U.S.A.
Cerberus Pyrotronics 50 East Pearce Street
Richmond Hill, Ontario L4B, 1B7 CN
Tel: 905-764-8384
FAX: 905-731-9182
February 1995 Supersedes sheet dated 4/96
firealarmresources.com

Documents / Resources

| CERBERUS PYROTRONICS CP-2HR Control Panel [pdf] Owner's Manual
CP-2HR Control Panel, CP-2HR, Control Panel, Panel
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

CERBERUS PYROTRONICS User Manuals

Related Manuals