CERBERUS PYROTRONICS XLD-1 X Series Loop Driver Owner’s Manual

June 9, 2024
CERBERUS PYROTRONICS

CERBERUS Logo XLD-1
“X” Series Loop Driver

ENGINEER AND ARCHITECT SPECIFICATIONS

CERBERUS PYROTRONICS XLD 1 X Series Loop Driver

  • X” Devices To MXL Interface
  • Allows XL-3 to MXL System Conversion
  • (4) Style 4 (Class B) or Style 6 (Class A) Loops
  • 30 “X” Series Devices Per Loop
  • Full MOM Card Slot
  • Supports All “X” Devices (TRX, PEX, DI-X3, PAX, etc.)
  • Allows MXL Operation with “X” Devices
  • Listed, ULC Listed, CSFM, NYMEA Approved

Description

The XLD-1 is an optional MXL network module that connects XL-3 analog addressable devices to the MXL system. By using the XLD-1, existing XL-3 systems can be replaced by MXL systems, yet continue to use all “X” Series devices that are installed on the XL-3.
Each XLD-1 provides (4) analog loops for connection to “X”, “I” or “IL” Series devices. Each of the XLD-1 circuits supports up to 30 alarm causing, trouble causing and supervisory type devices, as well as intelligent output devices (such as TRX relays, relay and audible bases.) Each XLD-1 analog loop is capable of being wired for either Style 4 (Class B) or Style 6 (Class A.)
The MXL can support up to 8 XLD-1 modules (960 “X” devices.) The XLD-1 provides the same device and loop capacity as the XL-3 module INX.
An XL-3 system with (8) INX modules (fully loaded XL3 – 960 devices) being replaced by an MXL would require (8) XLD-1s to utilize all existing “X” field device.

Engineer and Architect Specification

The XLD-1 shall be an analog loop driver with the ability to supervise and communicate with all Cerberus Pyrotronics “X”, “I” or “IL” Series devices (excluding the CZM-1 and ICP). XLD-1 shall provide (4) MXL network analog loops each capable of supporting up to 30 “X”, “I” or “IL” Series devices. The XLD-1 shall occupy one full card slot in the MOM-2 or MOM-4 card cages. Each XLD-1 network analog loop shall be capable of being wired for either style 4 (Class B) or style 6 (Class A.) The XLD-1 module shall contain an on board microprocessor which provides it with the ability to function and to initiate alarm conditions even if the main MXL processor fails.

Electrical Ratings

MODULE RATINGS:

Supervisory: 24VDC, 200mA max.
Alarm: 24VDC, 200mA max.

INITIATING CIRCUITS ARE RATED:
Supervisory| 24VDC peak, 40mA max.
Alarm:| 24VDC peak, 40mA max.
(30 devices in alarm)
Total Circuit Resistance:| 100 Ohms max.
Total Circuit Capacitance:| .4 uF line to line
.8 uF line to ground

Ordering Information

Model Description Part Number
XLD-1 “X” Device Loop Driver 500-893383
Installation Instructions 315-093385
XEA-1 Small XL-3 Enclosure Adapter Plate 500-893604
XED-1 Small XL-3 Enclosure Door (Black) 500-893605
XEA-2 Large XL-3 Enclosure Adapter Plate 500-893606
XED-2 Large XL-3 Enclosure Door (Black) 500-893607

XLD-1 Module Diagram

CERBERUS PYROTRONICS XLD 1 X Series Loop Driver -
Diagram

XLD-1 Wiring Diagram
CERBERUS PYROTRONICS XLD 1 X Series Loop Driver - Diagram
1 Compatibility Table for XLD-1

Compatible
Devices| | Installation
Instructions| Compatible
Devices| |

Installation
Instructions

---|---|---|---|---|---
DI-AX3| P/N| 315-085388F| I LP-1| P/N| 315-092994-2
DI-AX3H| P/N| 315-086588B| ILPT-1| P/N| 315-092994-2
DI-6X3| P/N| 315-086590-7| I LT-1| P/N| 315-093336-1
| P/N| 315-086592-5| MS1-10/20| P/N| 315-090903-3
DI-BX3H| P/N| 315-086590-7| M SI-10B/20B| P/N| 315-093329-1
| P/N| 315-086592-5| MSX-1| P/N| 315-183043C
DI-X3| P/N| 315-083534D| MSX-2| P/N| 315-088528B
DI-X3H| P/N| 315-086587B| PAX-1| P/N| 315-084615C
DP-X3| P/N| 315-083406A| PAX-3| P/N| 315-087558-3
DT-X3-135| P/N| 315-0841250| P EX-3000| P/N| 315-0865520
ID-601/601H| P/N| 315-090287-2| P EX-3000T| P/N| 315-0865520
ID-601A/601AH| P/N| 315-090287-2| SAX-1| P/N| 315-0846140
ID-601 B/60I BH| P/N| 315-086590-7| SAX-3| P/N| 315-087791A
| P/N| 315-086529-5| TRI-2/2 R/2D| P/N| 315-090556-5
ID-60P/60PT| P/N| 315-090289-3| TR1-60/60R/60D| P/N| 315-092329-2
ID-60T-135| P/N| 315-090288A| TRI-B6/B6R/B6D| P/N| 315-093315-1
I LI-1/1H/1A/1AH| P/N| 315-092724-2| TRX-1| P/N| 315-183462E
ILI-1B/IBH| P/N| 315-093234-1| TRX-2/2 D/2 R| P/N| 315-086678-4
| P/N| 315-093235-1| TRX-3| P/N| 315-086288A

Cerberus Pyrotronics 8 Ridgedale Avenue
Cedar Knolls, NJ 07927
Tel: 201-267-1300
FAX: 201-397-7008
Website: www.cerbpyro.com
4/97 5M CPY-IG
Printed in U.S.A.
Cerberus Pyrotronics 50 East Pearce Street
Richmond Hill, Ontario L4B, 1B7 CN
Tel: 905-764-8384
FAX: 905-731-9182
April 1997 Supersedes sheet dated 4/96
firealarmresources.com

Documents / Resources

| CERBERUS PYROTRONICS XLD-1 X Series Loop Driver [pdf] Owner's Manual
XLD-1 X Series Loop Driver, XLD-1, X Series Loop Driver, Loop Driver, Driver
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

CERBERUS PYROTRONICS User Manuals

Related Manuals