CERBERUS PYROTRONICS PNC-2Z NAC Expansion Module Owner’s Manual
- June 9, 2024
- CERBERUS PYROTRONICS
Table of Contents
CERBERUS PYROTRONICS PNC-2Z NAC Expansion Module
ENGINEER AND ARCHITECT SPECIFICATIONS
- 2 Style Z (Class A) Notification Appliance Circuits (NAC)
- Compatible with Cerberus Pyrotronics F-Series Notification Appliances
- 2 Amp, Power Limited Circuits
- Programmable for Coded or NonSilenceable Operation
- Bypass Option Programmable
- Listed, ULC Listed
Introduction
The model PNC-2Z Notification Appliance Circuit module provides 2 programmable, power limited circuits. They have the same device compatibility as the circuits contained in the PPS-10M power supply module. The PNC-2Z is listed by Underwriters Laboratories, Inc. and Underwriters Laboratories of Canada.
Description
- The PXL basic system contains 4 Notification Appliance Circuits on the power supply module. The system can be expanded with one additional power supply module and 4 PNC-2Z modules for a total of 16 NAC’s.
- Each notification circuit is provided with terminals for either Style Z (Class A) or Style Y (Class B) wiring. Each circuit is rated for 2 amps and is power limited per UL 864 requirements. The circuits are compatible with a wide range of Cerberus Pyrotronics notification appliances. Please refer to compatibility chart.
- The notification circuits default to steady operation, but can be programmed for March Time, Temporal or California Uniform Fire Code operation. Any circuit can alternatively be programmed as non-silenceable (waterflow service for example). In that event, the circuit is steady. Temporal Code is required for building evacuation by NFPA Standard 72 as of July 1996.
Ordering Information
Model | Description | Part Number |
---|---|---|
PNC-2Z | 2 NAC Expansion Module for PXL | 500-894079 |
For more information on PXL please refer to catalog #8100.
The installation Instruction for the Model PNC-2Z is P/N 315-093975.
Wiring Diagram
Compatible Device List
Chime/ Strobes| Vibrating Bells| Electro-Mech.
Horn/Strobes| Electronic Horns 1-Tone with Strobe| Single Stroke
Bells
---|---|---|---|---
EC-S15-C/F/S EC-S17-C/F/S EC-S75-F/S EC-S110-F/S| BE-F/LC BF-F/LC BS-F/LC
BT-F/LC| HN-S15-C/F/S HN-S17-C/F/S HN-S75-F/S HN-S110-F/S| HNH-S15-C/F/S
HNH-S17-C/F/S HNH-S75-F/S HNH-S110-F/S| EH-S15-C/F/S EH-S17-C/F/S EH-S75-F/S
EH-S110-F/S| BE-SS BF-SS BS-SS BT-SS
Strobes| Electronic S.W./Strobes| Horns/ Horn Strobes
3-Tone
| Horns/ Horn Strobes
3-Tone
| Sync. Strobes| Bell/Strobe Plate
S15-F/FS/FT/S/ST S17-F/FS/FT/S/ST S75-F/FS/FT/S/ST S110-F/FS/FT/S/ST|
EW-S15-C/F/S EW-S17-C/F/S EW-S75-F/S EW-S110-F/S| MC-C/F/S
MC-S15-C/F/S MC-S17-C/F/S MC-S75-F/S MC-S110-F/S
| MTL-C/F/S MTL-S15-C/F/S MTL-S17-C/F/S MTL-S75-F/S MTL-S110-F/S| S15S-F/FS/FT/S/ST S17S-F/FS/FT/S/ST S75S-F/FS/FT/S/ST| S15-6060H/6090V S17-6060H/6090V S75-6090V
S110-6090V
Sync. Electro-Mech.
Horn/Strobes
| Sync. Horns/ Horn Strobes 3-Tone| Sync. Horns/ Horn Strobes
8-Tone| Synchronizing Control Module| Sync. Bell/Strobe Plate
HN-S15S-C/F/S HN-S17S-C/F/S HN-S75S-F/S| HNH-S15S-C/F/S HNH-S17S-C/F/S HNH-
S75S-F/S| MC-S15S-C/F/S MC-S17S-C/F/S MC-S75S-F/S| MTL-S15S-C/F/S MTL-
S17S-C/F/S MTL-S75S-F/S| SCM-F/FW| S15S-6060H/6090V S17S-6060H/6090V S75S-
6090V
Electronic Horns 1-Tone| Chimes| Electronic Slow Whoop|
Electro-Mech.
Horns
| Tri-Tone Horns| Suffixes
EH-C/F/S| EC-C/F/S CH-F/LC/SS| EW-C/F/S| HN-C/EP/F/S HNH-C/EP/F/S| SEA TTH| C
= Ceiling
EP = Explosion Proof F = Flush
FT = Flush w/Terminals G = Gang Mount
H = Horizontal LC = Low Current S = Surface
SS = Single Stroke
ST = Surface w/Terminals U = Universal Mount
V = Vertical W = White
Mini-Horns| Sync. Mini-Horns| Mini-Horns/Strobes 8-Tone|
Sync. Mini-Horns/ Strobes 8-Tone
MH-1G/1GW MH-U/UW
MH-S15-U/UW MH-S17-U/UW MH-S75-U/UW MH-S110-U/UW
| MHT-1G/1GW MHT-U/UW MHT-S15-U/UW MHT-S17-U/UW MHT-S75-U/UW
MHT-S110-U/UW
| MHST-1G/1GW MHST-U/UW MHST-S15S-U/UW MHST-S17S-U/UW MHST-S75S-U/UW| MMT- 1G/1GW MMT-U/UW MMT-S15-U/UW MMT-S17-U/UW MMT-S75-U/UW
MMT-S110-U/UW
| MMT-S15S-U/UW MMT-S17S-U/UW MMT-S75S-U/UW
The SCM-F/FW Synchronizing Control Module must be used with these modules to synchronize the strobes.