CERBERUS PYROTRONICS ALD-2I Analog Loop Driver Owner’s Manual
- June 9, 2024
- CERBERUS PYROTRONICS
Table of Contents
ALD-2I Analog Loop Driver
ENGINEER AND ARCHITECT SPECIFICATIONS
- Dynamic Supervision
- 2 Intelligent Analog Device Circuits
- Remote Smoke Detector Sensitivity, Voltage Read-out/Printout
- Device Identification
- 32 Character Custom Alphanumeric Message Per Device
- Accepts Remote Conventional Zone Modules (CZM-1)
- Alarm, Trouble, Supervisory, Security and Status Reporting
- Supports Audible Bases
- Short Circuit Isolation with LIM-1
- On Board Microprocessor
- Isolated Power Supply
- Power Limited Per NEC 760
- Programmable Input/Output Module
- 60 Intelligent Devices Per Circuit
- Remote Smoke Detector Sensitivity Adjustment
- Independent Control of Detector Relays (Up to 60 per Circuit)
- Intelligent Contact Monitoring Devices
- Supports T-Tap Wiring
- Style 4 (Class B) or Style 6 (Class A) Wiring
- Degrade Mode
- On-Board Ground Fault Detection
- Listed, ULC Listed, FM, CSFM, NYMEA, and City of Chicago Approved
Description
The ALD-2I is an MXL Network option module that supplies two intelligent
analog circuits utilizing Cerberus Pyrotronics “I” series type intelligent
devices. It occupies two addresses on the Network and, through the use of a
unique communications protocol, devices connected to the ALD-2I circuits are
dynamically supervised by the MXL Control Panel. Smoke detectors are monitored
for sensitivity and notification is given when the sensitivity is outside
normal parameters. Each of the ALD-2I circuits supports
the use of up to 60 alarm, trouble, security, status and supervisory type
devices as well as remote conventional initiating device zone modules (CZM-1)
and intelligent output devices (TRI-60R, ICP). Sensitivity of any smoke
detector can be queried and adjusted from the control panel. Sensitivity as
well as other device information can be displayed and printed at the control
panel. The ALD-2I supports the use of relay bases and audible bases
(independently controllable).
To provide analog loop short circuit isolation, the LIM-1 module can be used
to prevent a single short from interrupting loop device communication.
Each ALD-2I circuit can be wired in either a Style 4 (Class B) or Style 6
(Class A) configuration. When using the Style 4 method, T-Tapping is permitted
with no loss of supervision.
The ALD-2I has an on board microprocessor that provides it with the ability to
function in a degrade mode and initiate alarm conditions even if the MXL main
microprocessor fails.
The ALD-2I plugs into one full option slot in the MOM-2 or MOM-4 card cage.
This equipment is approved for operation over the temperature range of 0°C and
49°C.
Engineer and Architect Specifications
Intelligent analog device circuits shall be provided by an ALD-2I Analog Loop
Driver Module. This module shall plug into one full slot of the MOM-2 or MOM-4
card cage
as a part of the Cerberus Pyrotronics MXL or MXLV systems. Each ALD-2I shall
provide two circuits. Each of these circuits shall support the use of up to 60
intelligent devices, as well as remote conventional initiating zone modules.
Sensitivity of any smoke detector can be queried and adjusted from, as well as
displayed at, the control panel. Sensitivity change shall be performed either
manually or automatically through the time based logic.
The ALD-2I shall support the use of relay bases, audible bases, and remote
lamps.
ALD-2I circuits shall be capable of being wired to meet the requirements of
either NFPA Style 4 or Style 6. When wired as a Style 4 circuit, it shall
support the use of parallel branch circuits (T-Tapping).
The ALD-2I shall utilize an on board CPU as well as network interface
circuitry and A/D converters. It shall be capable of operation in a degrade
mode in the event of MXL main processor failure or loss or network
communication link. In the degrade mode the ALD-2I circuits shall be capable
of sensing an alarm condition from its connected devices and activating local
notification appliance circuits through a degrade alarm bus.
ALD-2I circuits shall meet the requirements of NEC 760 for power limiting.
Electrical Specifications
ALD-2I Electrical Ratings
-
Electrical Ratings
Supervisory 28 VDC peak, 60mA max
Alarm 28 VDC peak, 60mA max (60 devices in alarm) -
All wiring must be in accordance with Article 760 of NEC and local building codes.
-
Only the devices in the following list may be used. A maximum of 60 devices (excluding CZM-1, LIM-1 and ICP) in any combination my be connected to a single loop. The UL identifiers for compatibility are the same as the model names specified below.
Detector| Installation Instructions
---|---
CZM-1
ILP-1
ILPT-1
ILI-1/ILI-1H
ILI-1A/ILI-1AH
ILI-1B/ILI-1BH
ID-60I/60IH
ID-60IA/60IAH
ID-60IB/60IBH
TRI-2/2R/2D
TRI-60/60R/60D
ICP
LIM-1
MSI-1
MSI-10
MS-MI
MSI-20
ID-60T-135| P/N 315-090725
P/N 315-092594
P/N 315-092594
P/N 315-092724
P/N 315-092724
P/N 315-092724
P/N 315-090287
P/N 315-090287
P/N 315-086590
P/N 315-090556
P/N 315-091857
P/N 315-092471
P/N 315-092135
P/N 315-090437
P/N 315-090903
P/N 315-092169
P/N 315-090903
P/N 315-090288 -
No end of line device is required.
-
Both circuits are power limited to NFPA 70, per NEC 760. Each detector, or group of detectors, requires a two-wire circuit of 18 AWG minimum thermoplastic fixture wire enclosed in a conduit of 18 AWG limitedenergy shielded cable without conduit, if permitted by local building codes.
-
Total circuit resistance must not exceed 100 ohms.
Maximum Capacitance:
0.4µF, between loop+ and loop
0.8µF, between loop+ and chassis
0.8µF, between loop- and chassis
-
T-Tapping is not allowed on Class A loops.
Wiring Diagram
NOTICE: The use of other than Cerberus Pyrotronics detectors and bases with Cerberus Pyrotronics control equipment will be considered a misapplication of Cerberus Pyrotronics equipment and as such void all warranties, either expressed or implied with regard to loss, damage, liabilities and/or service problems.
Cerberus Pyrotronics
8 Ridgedale Avenue
Cedar Knolls, NJ 07927
Tel: 201-267-1300
FAX: 201-397-7008
9/95 10M
CPY-IG
Printed in U.S.A.
Cerberus Pyrotronics
50 East Pearce Street
Richmond Hill, Ontario
L4B, 1B7 CN
Tel: 905-764-8384
FAX: 905-731-9182
September 1995
Supersedes sheet dated 3/95