MyVallox Touch Control Panels User Manual

June 9, 2024
VALLOX

MyVallox Touch Control Panels

SAFETY

Safe and appropriate handling requires knowledge of the basic safety regulations, and of the intended use of the ventilation system. Read this manual before operating the ventilation unit. Please keep the manual for later reference. If you lose the manual, it can be downloaded from our website.

This user manual contains all the information necessary for safe operation of the system. All persons who operate and maintain the ventilation system must follow the instructions provided in this manual. Furthermore, all local accident prevention regulations must be observed.

Installation

Installation and setup should only be carried out by a qualified specialist. Electrical installations and connections must be carried out only by an electrician and in compliance with local regulations.

WARRANTY

The guarantee and liability exclude damage resulting from:

  • Inappropriate use of the ventilation system or the control unit
  • Incorrect or inappropriate installation, setup or use
  • Neglect of instructions concerning transportation, installation, use, or maintenance
  • Structural or electronic modifications or changes made to the software
INTENDED USE

All Val lox ventilation units have been designed to provide appropriate and continuous ventilation so as to present no threat to health and to maintain structures in good condition.

IMPORTANT

Symbol In order to ensure that the indoor air presents no harm to health and remains optimal also for the structures of the building, ventilation must be kept on without disruptions. It is recommended that ventilation be left turned on during long holidays also. This keeps the indoor air fresh and prevents humidity from condensing in the ventilation ducts and structures. It also reduces the risk of moisture damage.

SymbolNOTE
For further information, go to www.vallox.com

WARNING

The unit is not intended for use by children under 8 or by persons with reduced sensory, physical or mental capabilities, or whose lack of knowledge and experience do not ensure safe operation of the unit.

Such persons can use the unit under supervision, or by following the instructions of someone who is responsible for their safety.

Children must be supervised and not be allowed to play with the device.

DISPOSAL OF THE VENTILATION UNIT

Do not dispose of electronic devices with household waste. Follow local laws and regulations on safe and ecological disposal of the product.

SAFETY SIGNS USED IN THE

INSTRUCTIONS

DANGER Indicates a hazard that will result in death or serious injury if not avoided.

WARNING Indicates a hazard that can result in death or serious injury if not avoided.

CAUTION Indicates a hazard that can result in minor or moderate injury if not avoided.

SymbolIMPORTANT Indicates a hazard that can result in damage to property or loss of data if not avoided.

SymbolNOTE Indicates essential information about the product

TIP Provides additional information about the use of the product and its benefits.

COMPATIBILITY OF THE MYVALLOX TOUCH CONTROL PANEL

The control panel is compatible with all My Val lox ventilation units

SYSTEM DESCRIPTION

System Description

  1. Internet
  2. WLAN
  3. Router
  4. WLAN/LAN
  5. Additional switch
  6. Sensors

VENTILATION UNIT CONTROL

Ventilation unit control options.

Operation of the Val lox ventilation unit can be controlled by the following means:

  • with a My Val lox Control/My Val lox Touch control panel
  • through the My Val lox Home user interface
  • through the My Val lox Cloud service
  • through building automation by means of Modbus messages

The inbuilt carbon dioxide and humidity sensor ensures that ventilation remains optimal also when the apartment is unoccupied. External carbon dioxide, VOC, and humidity sensors are available as accessories.

Each user can use the week clock to adjust the ventilation to fit their individual lifestyle

SymbolNOTE
For the My Val lox Cloud/Home instructions, please go to techmanuals.info/ Val lox MV/ENG/help/ whelp

CONNECTING THE VENTILATION UNIT TO THE CLOUD SERVICE

The ventilation unit can be connected to the My Val lox Cloud service. The cloud service allows for controlling ventilation remotely also, using e.g. a smartphone or tablet. Also the unit software is updated automatically through the cloud service. To connect to the cloud service, the ventilation unit must be connected to the Internet via LAN and registered with the cloud service. At the same time you create a My Val lox Cloud account for yourself. Read more about the service at www.myvallox.com.

To register your Val lox ventilation unit with the My Val lox Cloud service:

  1. Connect one end of the network cable to the grey connector of the Val lox ventilation unit and the other end to the router.

  2. Open the network settings on the computer by selecting Start → My Computer → Network. A computer icon with the text Val lox and a series of numbers will be displayed. Open the MyVallox Home user interface by double clicking on the icon. The My Val lox Home user interface opens. OR From the MyVallox Touch Control panel, select Service menu → Diagnostics display → IP address. Type in the IP address and press Enter. The MyVallox Home user interface opens.

  3. Select Special functions.

  4. The MyVallox Cloud area will open and you can see whether you are signed in to the cloud service.

  5. Select Connect.

  6. The registration page of the MyVallox Cloud service opens. A unique identification number of the ventilation unit will be automatically generated into the field.

  7. Enter the following information on the form:
    • Ventilation unit name — Enter the ventilation unit name of your choice in this field.
    • Language — Select the desired language from the drop down menu
    • Country — Select the desired country from the drop down menu
    • Select username — Enter the username of your choice in this field.
    • Email address — Enter the email address of your choice in this field.
    • Password — Enter the password of your choice in this field.
    • Retype password — Retype your password in this field.

  8. Select the I want to receive notifications related to my ventilation unit box if you want to receive notifications related to your ventilation unit in your inbox.

  9. Read the conditions of use and select I have read and accept the conditions of use of the MyVallox Cloud service . The use of the services requires that the user has accepted the conditions of use of the service.

  10. Select Create a MyVallox Cloud account. The ventilation unit will generate a unique identification code and send it to the service. The service will remember the unit next time you sign in into the cloud service.

  11. A confirmation message will be sent to your email address. Click on the link contained in the message to confirm your email address and to sign in into the cloud service for the first time.

  12. Once you have signed in, the MyVallox Cloud service will open and the main page of the MyVallox Cloud account will be displayed in your browser.

CONTROL PANEL BUTTONS

| The arrow buttons allow you to change the operating mode of the ventilation unit.
---|---
| The Ventilation information button allows you to view the currently active mode information and information on temperatures and sensors.
| The Settings button opens the settings menu.
| The Back button takes you backwards in the menu
| The Left arrow button takes you leftward in the menu.
| The Right arrow button takes you rightward in the menu.
| The OK button accepts the selected option.
| Press the Cancel button to cancel selection.
| Press the Select button to edit the week clock.
| The Edit button allows you to edit settings.
| The Plus button allows you to:

  • Increase the value of the selected setting.

| The Minus button allows you to:

  • Reduce the value of the selected setting.

| The Up arrow button takes you upward in the menu.
| The Down arrow button takes you downwards in the menu.
| The Statistics button opens the temperature, relative humidity of air or carbon dioxide level graph (1 day).

Symbol NOTE The MyVallox Touch Control panel contains the buttons described in the following table. The control panel has a touch screen.

UNIT SOFTWARE

We recommend that the latest software version be always used.

The software version of the ventilation unit is shown on the display of the control panel, when the device starts up. Alternatively, the current software version can be checked from the Unit information display of the Service menu.

The latest version can be found at: http://www.cloud.vallox.com.

Updating the unit software

  1. Unplug the ventilation unit from the mains or turn off the fuse.
  2. The latest software version can be found at: http://www.cloud.vallox.com.
  3. Transfer the update file HSWUPD.BIN (Note! The file name must not be altered!) that you have downloaded on a MicroSD card.
TURNING ON AND TURNING OFF THE UNIT

f you are starting the ventilation unit for the first time or after a maintenance procedure, first connect it to the mains. This will start the unit.
If the ventilation unit was turned off from the control panel (see Turning the Unit Off), you can start it by touching the touch screen of the device.

To turn the ventilation unit off:

  1. Use the arrow buttons to select Turn unit off.
  2. Select OK.
  3. Press OK to confirm the selection. The ventilation unit has now been turned off.

SymbolIMPORTANT
It is recommended that the ventilation be kept turned on without disruptions.

SETUP SETTINGS

The following settings will be configured during the setup of the ventilation unit:

  • user interface language
  • time and date
  • fan settings

The qualified ventilation installer must complete the fan settings in accordance with the ventilation plan. Do not change these settings.

Select the language
  1. Select your language.
  2. Select OK.
  3. The language has now been set, and the control panel will move on to the time settings.
Set the time
  1. Use the Plus and Minus buttons to set the hours.
  2. Select OK.
  3. Use the Plus and Minus buttons to set the minutes.
  4. The time is now set.
  5. Proceed to the next phase by selecting OK.
Set the 24- or 12-hour clock

The 24-hour clock is used by default. To use the 12-hour clock:

  1. Select Off as the value of the 24 h setting.
  2. Proceed to the next phase by selecting OK.
Set the automatic daylight saving time

By default, the automatic daylight saving time is on. To use the manual daylight saving time setting:

  1. Select Off as the value of the Summer time setting.
  2. The manual daylight-saving time setting is now on.
  3. Proceed to the next phase by selecting OK.

TIP The MyVallox Touch control panel automatically switches to the sleep mode when the Sleep time set in the Display settings has elapsed. You can wake up the control panel by touching the touch screen.

Set the date

Setup Settings

  1. Use the Plus and Minus buttons to set the date.
  2. Select OK.
  3. Use the Plus and Minus buttons to set the month.
  4. Select OK.
  5. Use the Plus and Minus buttons to set the year.
  6. Select OK.
  7. The date is now set.
Basic fan settings

SymbolIMPORTANT
Adjust the air flows according to the values specified in the ventilation plan. It is recommended that the air flows be adjusted without having to choke the air flows at the valves. This is the most energy-efficient set up.

First, set both values as close to the ideal value as possible by looking at the supply and extract air fan curves. If the ratio between the air flows is very high at first, the ventilation unit may have to carry out extra defrosting cycles in sub-zero temperatures, thus making adjustment of the air flows more complicated. Check the air flows by measuring them at the valves, and fine-tune the percentage values as required.

SymbolNOTE If the outside air is extremely cold (below -10°C on an aluminum cell or below -3°C on a plastic cell), the ventilation unit may have to defrost the heat recovery cell. The air flows cannot be adjusted during defrosting.

Adjusting the supply and extract air flows
  1. Use the Plus and Minus buttons to set the supply air fan ratio as a percentage of the maximum output ratio. The fan speed (rpm) will change accordingly.
  2. Measure and adjust the supply air flows from the valves.
  3. Press the OK button.
  4. Use the Plus and Minus buttons to set the extract air  fan ratio as a percentage of the maximum output ratio.The fan speed (rpm) will change accordingly. Measure and adjust the extract air flows from the valves.
  5. Select OK. Supply and extract air flow settings are now complete.
  6. Record the set percentages in the measurement log. Do not change the output ratio between the supply and extract air fans once the settings are complete. The same ratio is also used in the Away and Boost modes.

SymbolNOTE If the use of the ventilation unit was started before airflow adjustment, the airflow must be measured through the Setup menu (see “Save and restore settings”). This ensures that the unit settings are optimal for the adjustment of the airflows.

SymbolIMPORTANT
The supply and extract air settings have been completed by a specialist during setup of the ventilation unit.
These settings should be changed only when the ventilation unit is reconfigured, and not at any other time. Changing the ventilation settings so that overpressure is created can result in damage to the structures of the building.

VENTILATION MODES

Four ventilation unit modes

Ventilation Modes

At   home
Use this mode when the dwelling or the premises are occupied.

Away
Use this mode when the dwelling or premises are unoccupied, e.g. during a trip or other long absence.

Fireplace mode
Use this mode when, for example, you are making a fire in the fireplace. The mode is primarily used to create a momentary overpressure in the dwelling.

Boost
Use this mode to increase the ventilation rate, e.g. when there are more people than usual in the dwelling or elsewhere on the premises

TIP
Using the At home, Away, and Boost modes according to need saves energy

SymbolIMPORTANT
Prolonged overpressure can result in damage to the structures of the building.

CHANGING THE MODE

  1. Press the Arrow button until the desired ventilation mode icon appears on the display.
  2. The ventilation mode has now been changed.
Viewing the basic settings of the ventilation modes

Changing The Mode

To view the basic settings of the ventilation modes, select Ventilation information:
The temperature display shows the following information:
Indoor air — Indicates the temperature of the air flowing into the unit to be removed from the premises.
Outdoor air — Indicates the temperature of the air flowing into the unit from outside.
Supply air — Indicates the temperature of the air flowing into the premises from the unit.
Exhaust air — Indicates the temperature of the air flowing outdoors from the unit.

Changing The Mode

TIP You can view the day-specific temperature, relative humidity of air, and carbon dioxide graphs by selecting Statistics.
TIP You can view the basic ventilation settings by using the arrow buttons.

Changing The Mode

The sensors display shows the following information:

Changing The Mode

  • Humidity — Indicates the relative humidity of air measured by the sensors.
  • Carbon dioxide — Indicates the carbon dioxide level measured by the sensors. If a VOC sensor has been installed, it indicates the VOC level.

The Unit information display shows the following information:

Changing The Mode

  • Fan speed — Indicates the fan speed of the ventilation unit.

The statuses of the ventilation unit heat recovery cell are:

  • Heat recovery — The heat recovery cell heats the air streaming in from outdoors.
  • Cool recovery — The heat recovery cell cools the air flowing in from the outdoors.
  • Cell bypass — The inflowing air bypasses the heat recovery cell.
  • Defrosting — The heat recovery cell is being defrosted.
  • Replace filters — Indicates the next recommended filter replacement date.
  • Time in operation — Indicates how long the device has been running.
Editing the ventilation mode settings

Changing The Mode

  1. Select Settings.
  2.  Select Ventilation mode settings.
  3. Select OK.
  4. Select the desired ventilation mode.
  5. Select OK.
  6. Use the Arrow buttons to select the setting that you want to edit.
  7. Select Edit.

SETTINGS

Filter settings

Settings

  1. Select Settings > Filters.
  2. Select OK.
  3. The summary display of filter replacement shows the following information:
    Filters replaced — Indicates the date when the filters were last replaced.
    Reminder interval — Indicates the filter replacement interval in months.
    Next reminder — Indicates the date when a reminder to replace the filters will next be shown.
Setting the Filter replacement reminder interval

Settings

  1. Select Settings > Filters.
  2. Select OK.
  3. Use the Arrow buttons to select the reminder interval.
  4. Select OK.
  5. Use the Plus and Minus buttons to set the desired reminder interval in months in the Reminder interval field. The interval value can be between 1 and 12 months. The factory setting is 6 months.
  6. Select OK.
Setting the date the filters were last replaced

Settings

Instructions for replacing the filters are provided in the Maintenance section.

After replacing the filters, enter the replacement date.

  1. Select Settings > Filters.
  2. Select OK.
  3. Use the Arrow buttons to select Replaced.
  4. Select OK, if you want to update the filters as having been replaced today.

SymbolNOTE. Based on the set reminder interval, the unit will automatically set the maintenance reminder to provide a reminder to replace the filters at the due time.

Filter maintenance reminder

The maintenance reminder reminds you of the filter replacement with a pop-up window.

The message can be acknowledged by selecting OK.

You can postpone the reminder for one week by pressing the Back button.

DISPLAY SETTINGS

Setting the sleep time

Display Settings
Display Settings

  1. Select Settings > Display settings.
  2. Select OK.
  3. Use the Arrow buttons to select Sleep time.
  4. Select Edit.

TIP The MyVallox Touch panel automatically switches to the sleep mode when the pre-set Sleep time has elapsed. When you want to wake up the control panel, touch the touch screen.

Adjusting the display brightness
  1. Select Settings > Display settings.
  2. Select OK.
  3. Use the Arrow buttons to select Brightness.
  4. Select Edit.
Selecting the user interface language

Display Settings

  1. Select Settings > Language.
  2. Select OK.
  3. Select your language.
  4. Select OK.

TIME AND DATE

Setting the time and date

The available time settings are:

  • Time
  • 24- or 12-hour clock
  • Date
  • Automatic daylight-saving time

SymbolNOTE The ventilation unit time will withstand a power cut of a few hours.

Setting the time

Time And Date

  1. Select Settings > Time and date.
  2. Select OK.
  3. Select the time
  4. Use the Plus and Minus buttons to set the time.
  5. Select OK.
Selecting the 24- or 12-hour clock

The 24-hour clock is used by default. To use the 12-hour clock:

Time And Date

  1. Select Settings > Time and date.
  2. Select OK.
  3. Select 24 h.
  4. Select Off as the value of the 24 h setting.
  5. Select OK.
Setting the date

Time And Date

  1. Select Settings > Time and date.
  2. Select OK.
  3. Select date.
  4. Use the Plus and Minus buttons to set the date.
  5. Select OK.
  6. Use the Plus and Minus buttons to set the month.
  7. Select OK.
  8. Use the Plus and Minus buttons to set the year.
  9. Select OK.
Automatic daylight-saving time

By default, automatic daylight-saving time is turned on. To use the manual daylight-saving time setting:

  1. Select Settings > Time and date.
  2. Select OK.
  3. Select Down arrow, until the 2/2 display opens.
  4. Select Summer time.
  5. Select OK.

WEEK CLOCK

The week clock allows you to pre-set a weekly ventilation programmed for the ventilation unit. For each hour of the week, one of the following modes can be configured:

  • At home — The At home mode is used.
  • Away — The Away mode is used.
  • Boost — The Boost mode is used.
  • Empty — The previous mode is used.

SymbolNOTE If you change the mode manually when the week clock is on, the selected mode will remain active until the week clock switches to the next mode in the program.

If ventilation is being controlled by the humidity, carbon dioxide or VOC sensors, they will adjust the fan speed regardless of whether a mode has been manually selected or selected by the week clock.

Setting and editing the weekly programmed

Week Clock

  1. Select Settings > Week clock on/off.

  2. Select OK.

  3. Select Edit the week clock.

  4. Select OK.

  5. Use the Right arrow button to select the desired day.

  6. Use the Down arrow button to select the desired time.

  7. Use the Select button to browse and select the ventilation mode that will be turned on at the chosen time. The icons are:
    At home mode.
    Away mode.
    Boost mode.

  8. Once you have selected the modes for the week clock, select Back.

  9. Select OK, if you want to save the changes made to the week clock. Select Cancel, if you do not want to save the changes. Select Back, if you want to go back to editing the week clock.

Turning the week clock on

Week Clock

  1. Select Settings > Week clock off.
  2. Select OK.
  3. Select Turn on.
  4. Select Select.
  5. The control panel confirms that the week clock is turned on.
Turning the week clock off

Week Clock

  1. Select Settings > Week clock on.
  2. Select OK.
  3. Select Turn off.
  4. Select OK.
  5. The control panel will confirm that the week clock is turned off.
  6. The week clock is now turned off. If you have set a weekly program, it will be saved in the unit.
Removing the week clock settings

Week Clock

To delete the set weekly programmed:

  1. Select Settings > Week clock on or Week clock off.
  2. Select Remove all settings.
  3. Select OK to accept deletion of the weekly program. The weekly program has now been deleted.
Example of setting a weekly program

In this example, the following weekly program has been set:

  • Mon-Fri 8-17, Away .
  • Mon-Fri 17-7, At home.
  • Sat 8-17, At home.
  •  Sat 18-20, At home with a ventilation boost needed for cooking, for example.
  • Sat 21-Mon 8, At home

To set the week clock, proceed as follows:

Week Clock

The figures above show the aforementioned settings in the week clock.

  1. Open the week clock.
  2. Select Monday, and input the following settings:
  3. For 08:00, select the Away mode.
  4. For 17:00, select the At home mode.
  5. Then input the corresponding settings for the other weekdays.
  6. Then select Saturday, and input the following settings:
  7. For 18:00, select the Boost mode.
  8. For 21:00, select the At home mode.
  9. Ensure that the week clock is turned on.
  10. The weekly program has now been set.

SymbolNOTE Do not set a ventilation mode separately for every hour. Only include into the week program hours when you want the ventilation mode to change.

TURNING THE UNIT OFF

Turning The Unit Off

To turn the ventilation unit off:

  1. Select Settings > Turn unit off.
  2. Select OK.
  3. Accept the command by selecting OK.
  4. The ventilation unit has now been turned off.

SymbolMPORTANT In order to ensure that the indoor air presents no harm to health and remains optimal for the structures of the building, ventilation must be kept on without disruptions.
It is recommended that ventilation be left turned on during long holidays also. This keeps the indoor air fresh and prevents humidity from condensing in the ventilation ducts and structures. It also reduces the risk of moisture damage.

TIP To re-start the ventilation unit, touch the touch screen.

TROUBLESHOOTING

SymbolNOTE Error messages are displayed on the control panel and in the MyVallox Home and MyVallox Cloud services.

FAULT CAUSE MEASURES
Error message: Extract air fan **The extract air fan has
stopped.** **Make sure that the fan is not running. The fan cabling and

operation must be checked and, where required, the fan must be replaced. Contact the service center.
Error message: Supply air fan| The supply air fan has stopped.| Make sure that the fan is not running. The fan cabling and operation must be checked and, where required, the fan must be replaced. Contact the service center.
Error message:**

Temperature sensor 1/2/3/4/5

| The temperature sensor indicated on the user interface has become damaged.| The sensor installation must be checked and, where required, the sensor must be replaced. Contact the service center.
Error message:

High supply air temperature

| The supply air temperature is too high.| The operation of the post and additional heating resistor must be checked. Contact the service center.
Error message:

Low supply air temperature

| The supply air temperature is too low.| The operation of the post and additional heating resistor must be checked. Ensure that the resistors are turned on in the user interface. Contact the service center if necessary.
The ventilation unit is not working; the control panel is not working.| Power input to the unit is lost or the safety switch catch of the door is not touching the safety switch.| Check:

  • The fuse in the fuse box
  • The glass tube fuse in the unit. Contact the service centre.
  • Press the safety switch all the way down and test if the unit can be turned on. If the unit can be turned on, ensure that the safety switch catch is touching the safety switch.

The ventilation unit is working, but the control panel is not working.| Either the control panel 24 VDC power is lost, or the control panel is damaged.| Check the cables from the unit to the control panel. Contact the service center.

CUSTOMER SUPPORT

www.vallox.com
Val lox Oy | Myllykyläntie 9-11 | 32200 LOIMAA | FINLAND

Vallox Logo

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

VALLOX User Manuals

Related Manuals