vallox 99 MV CEILING MOUNTING PLATE Instructions

June 5, 2024
VALLOX

Model
Velox 99 MV| Document
D10933| Valid from
01.01.2022| Updated
07.03.2022
---|---|---|---

Installation instructions

CEILING MOUNTING PLATE VALLOX 99 MV

vallox 99 MV CEILING MOUNTING PLATE

Ceiling mounting plate

INSTALLATION

  1. Install the ceiling mounting plate (1) with M8 thread bars so that it is horizontally level. If the foremost thread bars are located at the ducts, use alternative thread bar locations (2).
    NOTE! The end of the thread bars must be 5 mm or less below the fastening nut. Do not fasten the ceiling mounting plate too tight to the ceiling. There must be nuts above the ceiling mounting plate to prevent the plate from lifting up when the unit is being mounted. Ensure that the sliding bars move and restore to their original position by pulling from the operating levers (A). The top edge of the white covering strip of the ceiling mounting plate can be installed against the ceiling. Alternatively, a concealed mounting method can be used, in which case the ceiling can be 30 mm below the top of the white covering strip.
    2. Ensure that the insulation washers are in place in the outlet collars below the ceiling mounting plate.
    3. The door of the unit must be removed when the Vallox 99 ventilation unit is installed onto the ceiling mounting plate.
    4. Lift the ventilation unit close to the ceiling mounting plate and feed the cables and the connection box through the hole in the ceiling mounting plate on top of the ceiling.
    NOTE! Remember to make a service door in the ceiling so that the cables and the connection box can be accessed. The distance between the service door and the ceiling mounting plate must be around 500 mm.
    Alternatively, the cables can be fed to the rear wall between the ceiling mounting plate and the ventilation unit. When the ventilation unit is lifted against the ceiling mounting plate, the unit locks in place. (Where needed, guide the mounting hooks on the ceiling mounting plate (B) to the grooves on the side panels of the ventilation unit.) There are operating levers (A) on the front bottom corners of the ceiling mounting plate. When the levers have been restored to the same level with the white covering strip of the ceiling mounting plate, the unit has been locked in place.

  2. Where required, the unit can be detached from the ceiling mounting plate. Remove the door of the unit. Lift the unit slightly upwards and pull simultaneously from both operating levers (A) of the ceiling mounting plate to detach the unit from the ceiling mounting plate.

vallox 99 MV CEILING MOUNTING PLATE - fig

Dimensions and duct outlets

vallox 99 MV CEILING MOUNTING PLATE - fig1

Duct outlets
1. Supply air from the unit to the apartment
2. Extract air from the apartment to the unit| 3. Outdoor air to the unit
4. Exhaust air flowing outdoors
from the unit| 3. Outdoor air to the unit
4. Exhaust air flowing outdoors
from the unit

vallox 99 MV CEILING MOUNTING PLATE - fig2vallox
99 MV CEILING MOUNTING PLATE - fig3

www.vallox.com
Vallox Oy | Myllykyläntie 9-11 | 32200 LOIMAA | FINLAND
© Vallox – All rights reserved
D10933 | 07.03.2022 | PDF

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

VALLOX User Manuals

Related Manuals