VALLOX 101 MC R Ventilation Unit User Manual
- June 5, 2024
- VALLOX
Table of Contents
101 MC R Ventilation Unit
MANUAL
Manual
Model Vallox 101 MC R Vallox 101 MC L
Type A3740
Document D4686
Valid from 31.08.2020
Updated 20.01.2021
Ventilation unit
MAIN PARTS
Extract air fan Supply air fan Heat recovery cell Bypass damper of the HR cell Fine filter for supply air Coarse filter for supply air Coarse filter for extract air Post-heating resistor (in the supply air duct)
R model in the figure. In the L model, the parts are mirrored
1
15
2
9
8
3
11
6
10 4
5
7 5
4
3
6 2
7
1
12
13
8
Safety switch 9
Supply air heating adjustment
10
Supply/extract air flow adjustment
11
Vallox Simple Control panel (ordered separately)
12
Vallox ProControl panel (ordered separately)
13
Vallox Delico PTD EC control hood, Vallox Capto PTC EC control hood, Vallox
X-Line PTXP MC control hood, or Vallox X-Line PTXPA MC control hood (ordered
separately)
14
(optional)
14
(optional)
14
Vallox Delico PTD EC (optional)
Vallox Capto PTC EC (optional)
14
Ceiling bushing for electric wires
15
Vallox X-Line PTXP MC
Vallox X-Line PTXPA MC
(optional)
WARNING!
The unit is not intended for use by children under 8 or by persons with
reduced sensory, physical or mental capabilities, or whose lack of knowledge
and experience do not ensure safe operation of the unit. Such persons can use
the unit under supervision, or by following the instructions of someone who is
responsible for their safety.
2
USING THE UNIT
FAN SPEED ADJUSTMENT
The fan speed of the Vallox ventilation unit is adjusted using a four-step
control.
The available speed options of the control switch are 1, 2, 3, and 4:
1. Away mode. The ventilation efficiency can be temporarily reduced when the
apartment is unoccupied.
2-3. Standard mode. In standard mode, the air inside the apartment is replaced
once every two hours.
4. Boost mode. Cooking, sauna, bathing, drying of clothes, guests, and other
similar situations can require that ventilation be increased from the standard
setting.
The fan speed can also be controlled through a separate Vallox control hood,
the Vallox ProControl panel, or directly through voltage messages (0-10 V).
Vallox Simple Control panel
ADJUSTING THE SUPPLY AIR TEMPERATURE AND SUMMER/WINTER FUNCTION
The temperature of the air blown into the apartment can be adjusted
approximately between +10 °C and +30 °C. The unit has an automatic
summer/winter function (a bypass flap).
· When the adjusted temperature is between +10 °C and +30 °C, the heat
recovery cell is not bypassed, i.e. the unit is in winter mode.
· In the OFF position, the unit is in the summer mode, i.e. post-heating is
turned off and the heat recovery cell is bypassed when the outdoor temperature
is above +14 °C. The heat recovery will be turned on when the outdoor
temperature falls below +12 °C.
· In the AUTO position, the unit will operate as follows around the year: The
default post-heating setting is +17 °C. The unit will bypass the heat recovery
cell when the temperature of the outdoor air exceeds +14 °C. The heat recovery
will be turned on when the outdoor temperature falls below +12 °C. During the
bypass, post-heating is turned off.
The winter function of
the ventilation unit
The limit value has been set in the factory for freezing of the heat recovery
cell. When this limit value is exceeded, the ventilation unit starts to
defrost the heat recovery cell by directing the outdoor air past the heat
recovery cell.
The duration of the defrost cycle is 15-45 min depending on the amount of ice
accumulated in the heat recovery cell and on the extract air flow. The factory
settings ensure optimal operation in standard living and detached house
conditions. Even though the winter operation parameters can be adjusted for
certain extreme conditions, such as swimming pool facilities, it is always
advisable to contact Vallox maintenance services.
Adjusting supply air temperature
3
© Vallox Oy – All rights reserved
USING THE UNIT
FIREPLACE SWITCH
A switch with timer functions can be connected to the unit. The switch stops
the extract air fan when the fireplace is being used. NOTE! Starting up the
extract air fan can reduce the draw of the fireplace! In winter, this can
disturb the winter mode of the ventilation unit. The situation will return to
normal soon after the fireplace mode is turned off.
ADJUSTING THE SUPPLY AND EXTRACT AIR RATIO
This function might be needed when the air flows are adjusted at the valves
during installation. The user does not need to adjust this function once the
valves have been adjusted, and indeed should not adjust it at all. A
potentiometer can be used to reduce the supply or extract air flow as
required.
When the potentiometer is set roughly in the centre position, neither the
supply nor the extract air flow has been reduced. When the potentiometer is
turned anti-clockwise, the supply air flow is reduced, and when the
potentiometer is turned clockwise, the extract air flow is reduced.
Concealed installation of the fireplace switch (optional)
The potentiometer for adjusting the supply and extract air flows
MAINTENANCE REMINDER
If a signal light is connected to the connectors of the unit’s error relay,
the unit will send a reminder of service need every six months,. If connected,
the signal light will flash every second. Sounds made by the relay can then be
heard from inside the unit. The maintenance reminder will be set off
automatically when the door of the ventilation unit is opened or the power is
turned off. The maintenance reminder can also be set off manually.
The Vallox Simple Control panel, and the Vallox X-Line PTXP MC and PTXPA MC
control hoods, VAK 0-10 VDC:
· The low speed is turned on, then higher-lower-higher
– Low speed under 4 V
Vallox Delico PTD EC and Vallox Capto PTC EC control hoods:
· The damper is closed, then open-closed-open · Press at a 1-5 second
interval.
– High speed over 6 V
– The selected speed will always be turned on for 1-5 seconds
The service reminder will only be set off if it has been activated. Refer to the maintenance instructions for the necessary maintenance measures.
TROUBLESHOOTING TABLE
If the ventilation unit is affected by any of the errors listed in the table,
the unit will report the error through the error relay, signal light, and
circuit board LEDS. The number of flashes indicates the nature of the error.
The error relay can be connected to remote monitoring. NOTE! When remote
monitoring is used, the signal light of the control panel cannot be turned on.
TROUBLESHOOTING
Flashing LED Problem
1
NTC sensor of the supply air from the cell is faulty
2
NTC sensor of the extract air is faulty
3
NTC sensor of the extract air is faulty
4
NTC sensor of the exhaust air is faulty
5
NTC sensor of the outdoor air is faulty
6
The supply air fan has stopped
7
The extract air fan has stopped
8
EEPROM is faulty
Correction Check the sensor and the wires, replace as required Check the sensor and the wires, replace as required Check the sensor and the wires, replace as required Check the sensor and the wires, replace as required Check the sensor and the wires, replace as required Check the wiring of the fan, replace the fan as required Check the wiring of the fan, replace the fan as required Replace the circuit board
4
MAINTENANCE
BEFORE BEGINNING
MAINTENANCE WORK
When you open the door of Vallox 101 MC, the safety switch (S) cuts the power.
Despite this, disconnect the power supply plug anyway. Always disconnect the
power plug before starting maintenance on the Vallox 101 MC.
A
FILTERS
When the maintenance reminder becomes activated, S
check the cleanliness of the filters and replace them if
required. The Vallox ventilation unit has three air filters:
B
· Coarse filter for supply air (A) filters insects, heavy pollen and other relatively large foreign objects out of C the outdoor air.
· Fine filter for supply air (B) filters microscopic pollen and dust particles out of the supply air.
· Coarse filter for extract air (C) filters the extract air and keeps the heat recovery cell clean.
Using original Vallox filters ensures the best operation of the ventilation unit and the best filtering results. The filter replacement interval depends on the ambient dust concentration. It is recommended that the filters be replaced every spring and autumn, or at the very least once a year.
The R model is shown in the figures. In the L model, the parts are mirrored.
E
G
HEAT RECOVERY CELL
Check that the heat recovery cell (D) is clean roughly
once a year when the filters are being replaced. Clean by
washing as required.
C
· Remove the sealing strip (E) above the heat recovery
cell in the direction of the arrow. Also remove the
D
extract air filter (C).
· Lift the heat recovery cell and pull it out of the unit.
IMPORTANT! Handle the cell carefully! For example, do not lift the cell by the
layers. The cell layers are very thin and easily damaged.
If the heat recovery cell is dirty, clean it by immersing it in water
containing a small amount of a mild detergent. Rinse the heat recovery cell
clean with a water spray. When all the water has drained from between the
layers, the heat recovery cell can be installed.
· Ensure that the lower support (F) is in place between the knobs at the bottom of the unit before the heat recovery cell is installed.
· Push the heat recovery cell in place. Also push the
sealing strip (E) in place so that the strip is supported
by the corner bracket (G) at the rear. Lastly, install the
extract air filter (C) in place.
F
5
© Vallox Oy – All rights reserved
MAINTENANCE
FANS
Check the cleanliness of the fans when servicing the filters and the heat recovery cell. Clean the fans as required. The fans are very sensitive to external impacts, and it is recommended that they be cleaned in place rather than removing them.
You can clean the fan blades with compressed air or by
brushing them gently. Do not remove or move the fan
blade balancing weights.
E
C
Cleaning the fans
D
· Remove the extract air filter (C), the sealing strip (E),
P
and the heat recovery cell (D) from the unit following
the instructions provided earlier. The fans can now be T
cleaned. The air flow control grilles (S) in the suction
outlets of the fans can be removed, if they are in the
way during cleaning. To remove the grilles, undo their
mounting screws (K) (3 screws/grille) and remove the
grilles from the fans. Put the control grilles back in
place after cleaning.
· To remove the fan, disconnect the quick connector
(H) of the supply air fan (T) and/or the extract air fan
(P) cables.
· Push the fan cables and the rubber feed through (I)
H
into the fan chamber.
S
· Remove the wing screws used to fasten the fans (J)
T
(3 screws/fan). The air flow control grille must be
removed from the extract air fan before the fan is
K
removed from the unit.
· Remove the fan from the unit by pulling it forward and by tilting it slightly backwards at the same time.
Mounting the fans
· Ensure that the rubber feed throughs set in place when reinstalling the fan.
Fasten the fan in place with wing screws (3 screws/fan). Ensure that the air
flow control grilles are in place.
The R model is shown in the figures. In the L model, the parts are mirrored.
H P
J
J
I
I
J
6
MAINTENANCE
CONDENSING WATER
In the heating season, the extract air humidity condenses to water. In new
buildings, condensation runoff can form rapidly. Condensed water must be able
to freely leave the unit. At some time before the heating season begins (e.g.
during autumn maintenance), check that the condensing water outlets in the
bottom pool are not clogged. To check this, pour some water into the pool.
Clean as required. Water must at all times be kept out of the electrical
system.
See the condensing water connections on page 15.
L model
R model
MAINTENANCE
598
147,5
147,5
Installation of the Vallox Silent Klick siphon on the bottom pool
Installation of the Vallox Silent Klick siphon on the wall.
291 291
449 5 3
7
© Vallox Oy – All rights reserved
TECHNICAL SPECIFICATIONS
Air flow measurement points
Measurement points after the outlet collar. The fan curves indicate the total
pressure accounted for by duct losses.
Supply air
Extract air
TECHNICAL SPECIFICATIONS
Nimike Vallox 101 MC R Vallox 101 MC L
Air volumes Supply air Extract air
Electrical Connection
Enclosure protection class
Post-heating
Pre-heating
Additional heating
Fans
Supply air Extract air
Specific energy consumption (SEC) in a cold climate in a temperate climate
Operating efficiencies
Annual efficiency Supply air efficiency Specific Fan Power SFP
Filters
Supply air Extract air
Heat recovery bypass
Dimensions (w x h x d) and weight
Product number 4102638 4102629
90 dm3/s, 100 Pa 98 dm3/s, 100 Pa
230 V, 50 Hz, 8,3 A power plug
IP 34
Electrical resistor, 1500 W
0,119 kW 0,9 A EC 0,119 kW 0,9 A EC
A+ A
70 % A 82 % 1,0 kW (38 dm3/s) A
ISO Coarse > 75 % + ISO ePM ISO Coarse > 75 %
Automatic
598 x 449 x 596 | 58 kg
Fan input power
250
200
150
11,4 V 10,2 V 9,2 V
Power, W
8,1 V 100
7,3 V
50
6,2 V
5,2 V 4,1 V 3,1 V 0
0 10 20 30 40 50 60 70 80
0 36 72 108 144 180 216 252 288
Volume flow rate (dm3/s)
Supply/extract air volumes
90 100 324 360
dm³/s (l/s) m³/h
Pressure loss in ducts. Total pressure (Pa)
350
11,4 V
300
10,2 V
9,2 V
250
8,1 V
200
150
5,2 V 100
4,1 V 50
3,1 V
0
0
10
0
36
T = supply air P = extract air
6,2 V
7,3 V
SFP 1,8 SFP 1,5
SFP 1,0
dm³/s
20
30
40
50
60
70
80
90
100 (l/s)
72
108
144
180
216
252
288
324
360 m³/h
Volume flow rate (dm3/s)
SFP rate (Specific Fan Power) recommended value <1,8kW (m3/s)
Combined input power of the fans (kW) SFP =Airflow specified in the ventilation plan (m3/s)
8
TECHNICAL SPECIFICATIONS
Dimensions and duct outlets
Duct outlets R model
Inner diameter of the female collar: ø 125 mm 1. Supply air to the apartment
2. Exhaust air from the apartment to the unit 3. Exhaust air out 4. Outdoor
air to the unit
L model
Inner diameter of the female collar: ø 125 mm 1. Exhaust air out 2. Outdoor
air to the unit 3. Supply air to the apartment 4. Exhaust air from the
apartment to the unit
598
~ 596 322 104
598 461,50 136,50
1
3
125
2
4
154,50 443,50
5 3 449 502
3 8 449 487
The installation space required by the Vallox Silent Click siphon is 73mm. See Condensing water connections, p. 15
The installation space required by the Vallox elbow is 47mm. See Condensing water connections, p. 15
SOUND VALUES
Sound power level in the supply air duct (one duct) by octave band Lw, dB Adjustment position
Sound power level in the extract air duct (one duct) by octave band Lw, dB Adjustment position
Adjustment position (V) 3,1 4,1 5,2 6,2 7,3 8,1 9,2 10,2
11,4 3,1 4,1 5,2 6,2 7,3 8,1 9,2 10,2
11,4
Air flow dm³/s
15 24 34 42 51 62 69 77
83 23 31 41 50 60 70 78 86
92
Air flow m³/h
54 86 122 151 184 223 248 277
299 83 112 148 180 216 252 281 310
331
Medium 63
62 64 69 73 77 82 84 87
88 54 55 62 66 69 75 78 79
80
frequency of the
125
53 63 65 65 67 71 74 76
78 46 50 53 56 59 62 65 67
68
octave 250
48 56 60 65 70 71 73 75
75 39 45 51 55 60 59 61 62
64
band
Hz
500
43 49 56 60 64 67 69 71
73 29 35 40 44 47 50 55 54
56
1000
35 43 49 53 56 61 64 65
67 16 24 30 34 37 40 43 46
46
2000
25 36 44 49 52 56 58 61
62 13 17 23 28 32 36 38 41
42
4000
18 23 32 38 43 48 51 54
55 17 17 18 20 24 28 30 33
35
8000
21 22 29 37 43 49 52 55
57 21 21 21 21 22 23 25 28
29
LW, dB LWA, dB (A)
Adjustment position (V) Air flow dm³/s Air flow m³/h LpA, dB (A)
63 67 71 74 78 83 85 88
88 54 57 63 66 70 75 78 79
80
43 53 57 61 65 68 71 72
74 35 40 45 49 53 55 58 59
60
Sound pressure level coming through the envelope of the unit in the room in which it is installed (10m² sound absorption) Adjustment position / Air flows (supply/extract)
3,1
4,1
5,2
6,2
7,3
8,1
9,2
10,2
11,4
15/20
24/30
33/40
42/48
52/58
61/68
70/76
78/84
83/89
54/72
86/108
119/144
151/173
187/209 220/245 252/274 281/302
299/320
22
27
32
35
38
43
44
46
47
9
© Vallox Oy – All rights reserved
INTERNAL ELECTRICAL CONNECTION 7034800A 10
LINE: Phase NEUTRAL: Neutral SLI: Safety switch phase feed SNI: Safety switch neutral feed SLO: Safety switch phase to the circuit board SNO: Safety switch neutral to the circuit board SFL: Phase to supply air fan SFN: Neutral to supply air fan EFL: Phase to extract air fan EFN: Neutral to extract air fan FSO: Fireplace switch feed FSI: Fireplace switch output AHL: Post-heating phase AHN: Post-heating neutral PHL: Additional heater phase PHN: Additional heater neutral BL: Damper motor phase A BL1: Damper motor phase B BN: Damper motor neutral E/I: Error relay feed E/O: Error relay output
230V 50 Hz Safety / door switch Fireplace switch
*Fan neutral to FSI when the fireplace switch is used
*Without the fireplace switch, the fan neutral is connected to EFN With the fireplace switch, the fan neutral is moved to FSI
An external 0-10VDC voltage supply can be connected to the S and GND signals of the control signal for fan control.
1 234
VAK remote monitoring
Protective earth to a separate block Programming connector
LINE
NEUTRAL
SLI
SNI
9. GND / –
9
SLO
8. Supply fan PWM 8
SNO
7. Supply fan tacho 7
SFL
6. GND / –
6
SFN
5. Extract fan PWM 5
EFL
4. Extract fan tacho 4
EFN
3. GND / –
3
FSO
2. 11,4 VDC / +
2
FSI
1. Control signal S
1
AHL AHN
DIP switch
1
PHL PHN
ERROR RELAY
BL (potential-free)
2 3
BL1
4
BN
E/I
1 234
5
E/O
Extract air NTC Outdoor air NTC Supply air to the apartment NTC Exhaust air
NTC Supply air from the cell NTC
Freezing level adjustment
S + – LED 1 2 3 4 5 1 2 3 4 5
Error relay E/O E/I
When remote monitoring is used Leave the signal LED of the external control panel or cooker hood disconnected. Also disconnect the short circuit link between connectors 3 and 5 from the female side of the control panel connector.
Supply air fan
Extract air fan
T1 130 °C
T2 90 °C
R1
LED
Electric post-heating
M
radiator 1500 W
Belimo damper motor 230 VAC
Post-heating control
PWM level adjustment
DIP Switch
Up
1. Post-heating
Electric
2. Additional heating Electric
3. Type of the unit Bypass
4. Extra
Down VKL MLV Supply fan stop
ELECTRICAL CONNECTIONS
ELECTRICAL CONNECTIONS
EXTERNAL ELECTRICAL CONNECTION
With Vallox Delico PTD EC and Vallox Capto PTC EC control hood
3 POTENTIAL FREE CONTACT DATA 24VDC/5A
F ALARM
RS 485
MODE DAMP PIEZO
A B GND IN OUT IN OUT IN OUT + –
TACHO GND 0-11V
PE
DAMPER LIGHT FAN NL 123 NL NL
ALARM *NOTE!
CONTACT DATA: GUARD FUNCTION: NORMAL SITUATION = OPEN ACTIVATED = CLOSED
HOUSE AUTOMATION: NORMAL SITUATION = OPEN ERROR SITUATION (HOOD OR VENTILATION
UNIT) = CLOSED ACTIVATED GUARD FUNCTION = FLASHING
POSITION OF THE DAMPER: DAMPER CLOSED = CONTACT OPEN DAMPER OPEN = CONTACT
CLOSED
MV VENTILATION UNIT
RM/I RM/O
GND AN/I
MC VENTILATION UNIT Five terminal connector**
E/I LED / E/O
GND S
MC VENTILATION UNIT Four terminal connector
GND S
EC roof fan
Tacho S
- External error data is connected in the place ** Disconnect the short circuit link between connectors
of the short circuit link of the mother board
3 and 5 from the MC unit’s control panel connector
PROGRAMMING CONNECTORS OF THE MOTHERBOARD GUARD FUNCTION CONTACT DATA HOUSE
AUTOMATION CONTACT DATA DAMPER POSITION CONTACT DATA
EXTRA
EXTERNAL ELECTRICAL CONNECTION
with the Vallox Simple Control panel / Vallox PTXP MC, Vallox PTXPA MC cooker
hood
Internal connection of the ventilation unit
Control signal S
11.2 VDC / + GND / Error relay / LED
Simple Control
S + – LED
PTXP MC, PTXPA MC
– + S LED
– +S – +S
LED LED
7034500A
11
© Vallox Oy – All rights reserved
ELECTRICAL CONNECTIONS
EXTERNAL ELECTRICAL CONNECTION
with Vallox ProControl panel
Control signal S Internal connection 11.2 VDC / + of the ventilation unit GND
/ –
Error relay / LED
Wiring between the control panel and the ventilation unit, NOMAK 2x2x0.5+0.5
Ventilation unit cable
Control panel connector
S
Y1
leave disconnected
–
G0
LED
S/DI2
Cable types specified in the drawing are indicative
Cooker hood or boost switch
optional 946147
RH%
DISTRIBUTION BOARD
24V L N
Nomak 2x2x0,5+0,5
0…10V
2×0.5
The phase of 24 VAC feed is connected to the control panel connector G and the neutral to the connector G0
CONTROL PANEL G 24 VAC feed G0 0 VAC Y1 10 V, control voltage
of the ventilation unit
Y2 DI1 Boost at the cooker hood A1 24 VAC 1 A, intermediate
relay control
Y3 A2 Y4 U1 0…10 V, humidity boost A+ RS-485 B- RS-485 C RS-485 Common
S/DI2 G0
Error relay 0 VAC
2×0.5
Vallox Procontrol 949034
– +S – +S
LED
LED
Nomak 2x2x0,5+0,5
Modbus RS-485 Nomak
2x2x0,5+0,5
G G0 Y1 Y2 DI1 A1 Y3 A2 Y4 U1 A+ B term
CONFIG
BC
S/DI2 G0
EXTERNAL ELECTRICAL CONNECTION
With an external control panel
Internal connection of the ventilation unit
Control signal S 11.2 VDC / + GND / Error relay / LED
– +S – +S
LED LED
Control signal S GND / –
External control panel
An external 0-10 VDC voltage can be connected to the S and GND connectors for
fan control.
12
INSTALLATION
INSTALLATION SITE
Vallox 101 MC must be installed in a location where the
The top surface of the side panel of the unit can
temperature remains above +10 °C. When the unit is
be installed against the finished ceiling surface.
installed without a protective enclosure, the location must be chosen so that its noise does not cause any disturbance. Such locations include storage premises and
When the wall mounting plate is used, it must be observed that the ventilation unit will rise roughly 10mm above the final installation height!
technical spaces. NOTE!
604 6
Remember to make a service door in the finished ceiling
so that the connection cables can be accessed. The
service door should be located roughly 500 mm from the
unit door.
Bottom edge of the wall mounting plate
166
283
The outer diameter of the duct is 12mm
12
21
25
Wall mounting
Mount the Vallox 101 MC on the wall with a mounting plate, as shown in the
adjacent figure. Make sure that the unit is horizontally level after mounting.
Wall structure
The wall structure must be observed in the mounting. Avoid mounting the unit
on hollow, echoing intermediate walls and on bedroom walls, or take measures
to prevent conduction of noise.
Wall mounting plate
84 2030 30
35 30
84
30 30 20
30°
25
30 35
162
11
20 60
ø7 14 kpl 550
13
60 20
11
© Vallox Oy – All rights reserved
INSTALLATION
Ceiling mounting by using
a ceiling mounting plate
(optional)
The unit can be equipped with an optional ceiling mounting plate. The ceiling
mounting plate must be fastened on rafter frames or other frame structure with
M8 thread bars. The bars must be fastened so that they withstand the weight of
the unit.
The ceiling mounting plate must be fastened horizontally to make sure that the
unit is level. The ceiling mounting plate must be fastened so that there is a
10 mm gap between its rear edge and the finished wall. This way the
ventilation unit will be installed as close to the wall as possible. The top
edge of the white covering strip of the ceiling mounting plate can be
installed against the finished ceiling. Alternatively, a concealed mounting
method can be used, in which case the finished ceiling can be 30 mm or less
from the top edge of the white covering strip.
The ceiling mounting plate is fastened to the M8 thread bars with the mounting
supplies delivered with the mounting plate. NOTE! The end of the thread bars
must be 5mm or less below the fastening nut (more detailed instructions are
provided with the ceiling mounting plate).
Installing the ventilation unit to the ceiling mounting plate
Remove the unit door. Lift the unit and take the wires through the opening in
the ceiling mounting plate. Lift the ventilation unit against the ceiling
mounting plate so that it locks in place. The unit has become locked on the
ceiling mounting plate when the two operating levers on the mounting plate
have been restored to the same level with the white covering strip of the
ceiling mounting plate (more detailed instructions are provided with the
ceiling mounting plate).
Ceiling mounting plate (optional)
The top edge of the white covering strip of the ceiling mounting plate can be
installed against the finished ceiling. Alternatively, a concealed mounting
method can be used, in which case the finished ceiling can be 30 mm or less
from the top edge of the white covering strip.
The minimum distance from the finished rear wall is 10 mm
The recommended distance from the finished side wall is 10 mm
10
10
598
10
Finished wall
Finished ceiling
Concealed installation of the ceiling mounting plate on the ceiling, max. 30 mm
Finished ceiling
Finished wall
598 Finished wall
Concealed installation of the ceiling mounting plate on the ceiling, max. 30
mm
453
483
453
5 3
3 8
3 8
Installation space of the siphon 73 mm
Siphon Silent Klick
Installation space of the elbow 47 mm
Elbow
14
483
5 3
INSTALLATION
Attic floor penetration plate (optional)
When an attic floor penetration plate is used, the tightness of the vapour
barrier has to be ensured.
Finished wall
The attic floor penetration plate can be fastened on the finished rear wall.
The minimum distance from the side walls is 15 mm.
15
15
CONDENSING WATER CONNECTIONS
Installation of the Vallox Silent Klick siphon on the bottom pool
The delivery includes the Vallox Silent Klick siphon. A pipe will be connected
to the siphon that leads the water that is condensed from the extract air to
the floor drain (not directly into the sewer). The pipe must not rise after
the siphon. The ventilation unit must be installed straight to ensure that
condensing water can exit the unit unobstructed.
Vallox Silent Klick siphon
Installation height 53 mm, installation space 73 mm, outer diameter of the
duct 12 mm
L model
R model
291 291
147,5
147,5
Location of the condensing water outlets, R and L models
Installation of the Vallox Silent Klick siphon on the bottom pool
53
73
Installation of the Vallox Silent Klick siphon on the wall
If the Vallox Silent Klick siphon does not fit into the unit directly, the elbow can be installed at the bottom, and the siphon can be installed on the wall. This installation method requires that there is a 47 mm space underneath the unit. The elbow requires a 38 mm space when installed.
Installation of the Vallox Silent Klick siphon on the wall. The elbow underneath the unit takes less space than the siphon.
Elbow
Installation height 38 mm, installation space 47 mm, outer diameter of the
duct 12 mm
38
47
15
© Vallox Oy – All rights reserved
EXPLODED VIEW
EXPLODED VIEW AND PARTS LIST
(Type B3740)
R model in the figure. In the L model, the parts are mirrored
19
18 16 13
17
1
2 11
10 12
9
5
1
2
15 14
86
7
NO. Part
Product number
1 Supply / extract air fan …………………………………………………………………………935450
2 Supply air fan attenuation grid…………………………………………………………….935451.
3 Wall mounting plate ………………………………………………………………………….. 3080700
4 Siphon Vallox Silent Klick ………………………………………………………………….3292500
5 Coarse and fine filter for supply air …………………………………………………….978225
6 HR cell …………………………………………………………………………………………………..933260
7 Lower support for the HR cell …………………………………………………………… 4102504
8 Upper support for HR cell ………………………………………………………………… 3467200
9 Filter frame (extraction) ………………………………………………………………………..978226
10 Coarse filter for extract air ………………………………………………………………….. 978227
NO. Part
Product number
11 HR cell bypass damper assembly…………………………………………………….. 4102523
12 Damper motor ……………………………………………………………………………………….930621
13 Post-heating resistor…………………………………………………………………………….942220
14 Door ……………………………………………………………………………………………………. 4102334
15 Mounting screw of the door …………………………………………………………………990712
16 Motherboard…………………………………………………………………………………………949035
17 Safety switch………………………………………………………………………………………… 948370
18 Glass tube fuse 320 mA slow 5×20 mm …………………………………………….952486
19 NTC sensor (specify the sensor reference number in the order)………946140
D4686 | 20.01.2021 | PDF
www.vallox.com
Vallox Oy | Myllykyläntie 9-11 | 32200 LOIMAA | FINLAND Customer Service +358
10 7732 200 | Technical support +358 10 7732 270
© Vallox – All rights reserved
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>