VALLOX 101 MC R Ventilation Unit User Manual

June 5, 2024
VALLOX

101 MC R Ventilation Unit

MANUAL

Manual

Model Vallox 101 MC R Vallox 101 MC L
Type A3740

Document D4686
Valid from 31.08.2020
Updated 20.01.2021

Ventilation unit

MAIN PARTS

Extract air fan Supply air fan Heat recovery cell Bypass damper of the HR cell Fine filter for supply air Coarse filter for supply air Coarse filter for extract air Post-heating resistor (in the supply air duct)

R model in the figure. In the L model, the parts are mirrored
1

15

2

9

8

3

11

6

10 4
5

7 5
4

3
6 2

7

1

12

13

8

Safety switch 9
Supply air heating adjustment
10
Supply/extract air flow adjustment
11
Vallox Simple Control panel (ordered separately)
12
Vallox ProControl panel (ordered separately)
13
Vallox Delico PTD EC control hood, Vallox Capto PTC EC control hood, Vallox X-Line PTXP MC control hood, or Vallox X-Line PTXPA MC control hood (ordered separately)
14

(optional)
14

(optional)
14

Vallox Delico PTD EC (optional)

Vallox Capto PTC EC (optional)

14

Ceiling bushing for electric wires

15

Vallox X-Line PTXP MC

Vallox X-Line PTXPA MC

(optional)

WARNING!
The unit is not intended for use by children under 8 or by persons with reduced sensory, physical or mental capabilities, or whose lack of knowledge and experience do not ensure safe operation of the unit. Such persons can use the unit under supervision, or by following the instructions of someone who is responsible for their safety.
2

USING THE UNIT

FAN SPEED ADJUSTMENT
The fan speed of the Vallox ventilation unit is adjusted using a four-step control.
The available speed options of the control switch are 1, 2, 3, and 4:
1. Away mode. The ventilation efficiency can be temporarily reduced when the apartment is unoccupied.
2-3. Standard mode. In standard mode, the air inside the apartment is replaced once every two hours.
4. Boost mode. Cooking, sauna, bathing, drying of clothes, guests, and other similar situations can require that ventilation be increased from the standard setting.
The fan speed can also be controlled through a separate Vallox control hood, the Vallox ProControl panel, or directly through voltage messages (0-10 V).

Vallox Simple Control panel

ADJUSTING THE SUPPLY AIR TEMPERATURE AND SUMMER/WINTER FUNCTION

The temperature of the air blown into the apartment can be adjusted approximately between +10 °C and +30 °C. The unit has an automatic summer/winter function (a bypass flap).
· When the adjusted temperature is between +10 °C and +30 °C, the heat recovery cell is not bypassed, i.e. the unit is in winter mode.
· In the OFF position, the unit is in the summer mode, i.e. post-heating is turned off and the heat recovery cell is bypassed when the outdoor temperature is above +14 °C. The heat recovery will be turned on when the outdoor temperature falls below +12 °C.
· In the AUTO position, the unit will operate as follows around the year: The default post-heating setting is +17 °C. The unit will bypass the heat recovery cell when the temperature of the outdoor air exceeds +14 °C. The heat recovery will be turned on when the outdoor temperature falls below +12 °C. During the bypass, post-heating is turned off.

The winter function of
the ventilation unit
The limit value has been set in the factory for freezing of the heat recovery cell. When this limit value is exceeded, the ventilation unit starts to defrost the heat recovery cell by directing the outdoor air past the heat recovery cell.
The duration of the defrost cycle is 15-45 min depending on the amount of ice accumulated in the heat recovery cell and on the extract air flow. The factory settings ensure optimal operation in standard living and detached house conditions. Even though the winter operation parameters can be adjusted for certain extreme conditions, such as swimming pool facilities, it is always advisable to contact Vallox maintenance services.

Adjusting supply air temperature

3

© Vallox Oy – All rights reserved

USING THE UNIT

FIREPLACE SWITCH
A switch with timer functions can be connected to the unit. The switch stops the extract air fan when the fireplace is being used. NOTE! Starting up the extract air fan can reduce the draw of the fireplace! In winter, this can disturb the winter mode of the ventilation unit. The situation will return to normal soon after the fireplace mode is turned off.
ADJUSTING THE SUPPLY AND EXTRACT AIR RATIO
This function might be needed when the air flows are adjusted at the valves during installation. The user does not need to adjust this function once the valves have been adjusted, and indeed should not adjust it at all. A potentiometer can be used to reduce the supply or extract air flow as required.
When the potentiometer is set roughly in the centre position, neither the supply nor the extract air flow has been reduced. When the potentiometer is turned anti-clockwise, the supply air flow is reduced, and when the potentiometer is turned clockwise, the extract air flow is reduced.

Concealed installation of the fireplace switch (optional)
The potentiometer for adjusting the supply and extract air flows

MAINTENANCE REMINDER
If a signal light is connected to the connectors of the unit’s error relay, the unit will send a reminder of service need every six months,. If connected, the signal light will flash every second. Sounds made by the relay can then be heard from inside the unit. The maintenance reminder will be set off automatically when the door of the ventilation unit is opened or the power is turned off. The maintenance reminder can also be set off manually.

The Vallox Simple Control panel, and the Vallox X-Line PTXP MC and PTXPA MC control hoods, VAK 0-10 VDC:
· The low speed is turned on, then higher-lower-higher
– Low speed under 4 V

Vallox Delico PTD EC and Vallox Capto PTC EC control hoods:
· The damper is closed, then open-closed-open · Press at a 1-5 second interval.

– High speed over 6 V

– The selected speed will always be turned on for 1-5 seconds

The service reminder will only be set off if it has been activated. Refer to the maintenance instructions for the necessary maintenance measures.

TROUBLESHOOTING TABLE
If the ventilation unit is affected by any of the errors listed in the table, the unit will report the error through the error relay, signal light, and circuit board LEDS. The number of flashes indicates the nature of the error.
The error relay can be connected to remote monitoring. NOTE! When remote monitoring is used, the signal light of the control panel cannot be turned on.

TROUBLESHOOTING

Flashing LED Problem

1

NTC sensor of the supply air from the cell is faulty

2

NTC sensor of the extract air is faulty

3

NTC sensor of the extract air is faulty

4

NTC sensor of the exhaust air is faulty

5

NTC sensor of the outdoor air is faulty

6

The supply air fan has stopped

7

The extract air fan has stopped

8

EEPROM is faulty

Correction Check the sensor and the wires, replace as required Check the sensor and the wires, replace as required Check the sensor and the wires, replace as required Check the sensor and the wires, replace as required Check the sensor and the wires, replace as required Check the wiring of the fan, replace the fan as required Check the wiring of the fan, replace the fan as required Replace the circuit board

4

MAINTENANCE

BEFORE BEGINNING

MAINTENANCE WORK

When you open the door of Vallox 101 MC, the safety switch (S) cuts the power. Despite this, disconnect the power supply plug anyway. Always disconnect the power plug before starting maintenance on the Vallox 101 MC.
A
FILTERS

When the maintenance reminder becomes activated, S

check the cleanliness of the filters and replace them if

required. The Vallox ventilation unit has three air filters:

B

· Coarse filter for supply air (A) filters insects, heavy pollen and other relatively large foreign objects out of C the outdoor air.

· Fine filter for supply air (B) filters microscopic pollen and dust particles out of the supply air.

· Coarse filter for extract air (C) filters the extract air and keeps the heat recovery cell clean.

Using original Vallox filters ensures the best operation of the ventilation unit and the best filtering results. The filter replacement interval depends on the ambient dust concentration. It is recommended that the filters be replaced every spring and autumn, or at the very least once a year.

The R model is shown in the figures. In the L model, the parts are mirrored.

E

G

HEAT RECOVERY CELL

Check that the heat recovery cell (D) is clean roughly

once a year when the filters are being replaced. Clean by

washing as required.

C

· Remove the sealing strip (E) above the heat recovery

cell in the direction of the arrow. Also remove the

D

extract air filter (C).

· Lift the heat recovery cell and pull it out of the unit.

IMPORTANT! Handle the cell carefully! For example, do not lift the cell by the layers. The cell layers are very thin and easily damaged.
If the heat recovery cell is dirty, clean it by immersing it in water containing a small amount of a mild detergent. Rinse the heat recovery cell clean with a water spray. When all the water has drained from between the layers, the heat recovery cell can be installed.

· Ensure that the lower support (F) is in place between the knobs at the bottom of the unit before the heat recovery cell is installed.

· Push the heat recovery cell in place. Also push the

sealing strip (E) in place so that the strip is supported

by the corner bracket (G) at the rear. Lastly, install the

extract air filter (C) in place.

F

5

© Vallox Oy – All rights reserved

MAINTENANCE

FANS

Check the cleanliness of the fans when servicing the filters and the heat recovery cell. Clean the fans as required. The fans are very sensitive to external impacts, and it is recommended that they be cleaned in place rather than removing them.

You can clean the fan blades with compressed air or by

brushing them gently. Do not remove or move the fan

blade balancing weights.

E

C

Cleaning the fans

D

· Remove the extract air filter (C), the sealing strip (E),

P

and the heat recovery cell (D) from the unit following

the instructions provided earlier. The fans can now be T

cleaned. The air flow control grilles (S) in the suction

outlets of the fans can be removed, if they are in the

way during cleaning. To remove the grilles, undo their

mounting screws (K) (3 screws/grille) and remove the

grilles from the fans. Put the control grilles back in

place after cleaning.

· To remove the fan, disconnect the quick connector

(H) of the supply air fan (T) and/or the extract air fan

(P) cables.

· Push the fan cables and the rubber feed through (I)

H

into the fan chamber.

S

· Remove the wing screws used to fasten the fans (J)

T

(3 screws/fan). The air flow control grille must be

removed from the extract air fan before the fan is

K

removed from the unit.

· Remove the fan from the unit by pulling it forward and by tilting it slightly backwards at the same time.

Mounting the fans
· Ensure that the rubber feed throughs set in place when reinstalling the fan. Fasten the fan in place with wing screws (3 screws/fan). Ensure that the air flow control grilles are in place.

The R model is shown in the figures. In the L model, the parts are mirrored.

H P

J

J

I

I

J

6

MAINTENANCE

CONDENSING WATER
In the heating season, the extract air humidity condenses to water. In new buildings, condensation runoff can form rapidly. Condensed water must be able to freely leave the unit. At some time before the heating season begins (e.g. during autumn maintenance), check that the condensing water outlets in the bottom pool are not clogged. To check this, pour some water into the pool. Clean as required. Water must at all times be kept out of the electrical system.
See the condensing water connections on page 15.

L model

R model

MAINTENANCE
598

147,5

147,5

Installation of the Vallox Silent Klick siphon on the bottom pool

Installation of the Vallox Silent Klick siphon on the wall.

291 291
449 5 3

7

© Vallox Oy – All rights reserved

TECHNICAL SPECIFICATIONS

Air flow measurement points
Measurement points after the outlet collar. The fan curves indicate the total pressure accounted for by duct losses.
Supply air
Extract air

TECHNICAL SPECIFICATIONS

Nimike Vallox 101 MC R Vallox 101 MC L

Air volumes Supply air Extract air

Electrical Connection

Enclosure protection class

Post-heating

Pre-heating

Additional heating

Fans

Supply air Extract air

Specific energy consumption (SEC) in a cold climate in a temperate climate

Operating efficiencies

Annual efficiency Supply air efficiency Specific Fan Power SFP

Filters

Supply air Extract air

Heat recovery bypass

Dimensions (w x h x d) and weight

Product number 4102638 4102629
90 dm3/s, 100 Pa 98 dm3/s, 100 Pa
230 V, 50 Hz, 8,3 A power plug
IP 34
Electrical resistor, 1500 W
­
­
0,119 kW 0,9 A EC 0,119 kW 0,9 A EC
A+ A
70 % A 82 % 1,0 kW (38 dm3/s) A
ISO Coarse > 75 % + ISO ePM ISO Coarse > 75 %
Automatic
598 x 449 x 596 | 58 kg

Fan input power
250
200
150

11,4 V 10,2 V 9,2 V

Power, W

8,1 V 100
7,3 V

50

6,2 V

5,2 V 4,1 V 3,1 V 0
0 10 20 30 40 50 60 70 80

0 36 72 108 144 180 216 252 288

Volume flow rate (dm3/s)
Supply/extract air volumes

90 100 324 360

dm³/s (l/s) m³/h

Pressure loss in ducts. Total pressure (Pa)

350

11,4 V

300

10,2 V

9,2 V

250

8,1 V

200

150
5,2 V 100
4,1 V 50
3,1 V

0

0

10

0

36

T = supply air P = extract air

6,2 V

7,3 V

SFP 1,8 SFP 1,5

SFP 1,0

dm³/s

20

30

40

50

60

70

80

90

100 (l/s)

72

108

144

180

216

252

288

324

360 m³/h

Volume flow rate (dm3/s)

SFP rate (Specific Fan Power) recommended value <1,8kW (m3/s)

Combined input power of the fans (kW) SFP =Airflow specified in the ventilation plan (m3/s)

8

TECHNICAL SPECIFICATIONS

Dimensions and duct outlets
Duct outlets R model
Inner diameter of the female collar: ø 125 mm 1. Supply air to the apartment 2. Exhaust air from the apartment to the unit 3. Exhaust air out 4. Outdoor air to the unit
L model
Inner diameter of the female collar: ø 125 mm 1. Exhaust air out 2. Outdoor air to the unit 3. Supply air to the apartment 4. Exhaust air from the apartment to the unit
598

~ 596 322 104

598 461,50 136,50

1

3

125

2

4

154,50 443,50

5 3 449 502
3 8 449 487

The installation space required by the Vallox Silent Click siphon is 73mm. See Condensing water connections, p. 15

The installation space required by the Vallox elbow is 47mm. See Condensing water connections, p. 15

SOUND VALUES

Sound power level in the supply air duct (one duct) by octave band Lw, dB Adjustment position

Sound power level in the extract air duct (one duct) by octave band Lw, dB Adjustment position

Adjustment position (V) 3,1 4,1 5,2 6,2 7,3 8,1 9,2 10,2

11,4 3,1 4,1 5,2 6,2 7,3 8,1 9,2 10,2

11,4

Air flow dm³/s

15 24 34 42 51 62 69 77

83 23 31 41 50 60 70 78 86

92

Air flow m³/h

54 86 122 151 184 223 248 277

299 83 112 148 180 216 252 281 310

331

Medium 63

62 64 69 73 77 82 84 87

88 54 55 62 66 69 75 78 79

80

frequency of the

125

53 63 65 65 67 71 74 76

78 46 50 53 56 59 62 65 67

68

octave 250

48 56 60 65 70 71 73 75

75 39 45 51 55 60 59 61 62

64

band

Hz

500

43 49 56 60 64 67 69 71

73 29 35 40 44 47 50 55 54

56

1000

35 43 49 53 56 61 64 65

67 16 24 30 34 37 40 43 46

46

2000

25 36 44 49 52 56 58 61

62 13 17 23 28 32 36 38 41

42

4000

18 23 32 38 43 48 51 54

55 17 17 18 20 24 28 30 33

35

8000

21 22 29 37 43 49 52 55

57 21 21 21 21 22 23 25 28

29

LW, dB LWA, dB (A)
Adjustment position (V) Air flow dm³/s Air flow m³/h LpA, dB (A)

63 67 71 74 78 83 85 88

88 54 57 63 66 70 75 78 79

80

43 53 57 61 65 68 71 72

74 35 40 45 49 53 55 58 59

60

Sound pressure level coming through the envelope of the unit in the room in which it is installed (10m² sound absorption) Adjustment position / Air flows (supply/extract)

3,1

4,1

5,2

6,2

7,3

8,1

9,2

10,2

11,4

15/20

24/30

33/40

42/48

52/58

61/68

70/76

78/84

83/89

54/72

86/108

119/144

151/173

187/209 220/245 252/274 281/302

299/320

22

27

32

35

38

43

44

46

47

9

© Vallox Oy – All rights reserved

INTERNAL ELECTRICAL CONNECTION 7034800A 10

LINE: Phase NEUTRAL: Neutral SLI: Safety switch phase feed SNI: Safety switch neutral feed SLO: Safety switch phase to the circuit board SNO: Safety switch neutral to the circuit board SFL: Phase to supply air fan SFN: Neutral to supply air fan EFL: Phase to extract air fan EFN: Neutral to extract air fan FSO: Fireplace switch feed FSI: Fireplace switch output AHL: Post-heating phase AHN: Post-heating neutral PHL: Additional heater phase PHN: Additional heater neutral BL: Damper motor phase A BL1: Damper motor phase B BN: Damper motor neutral E/I: Error relay feed E/O: Error relay output

230V 50 Hz Safety / door switch Fireplace switch
*Fan neutral to FSI when the fireplace switch is used

*Without the fireplace switch, the fan neutral is connected to EFN With the fireplace switch, the fan neutral is moved to FSI

An external 0-10VDC voltage supply can be connected to the S and GND signals of the control signal for fan control.

1 234

VAK remote monitoring

Protective earth to a separate block Programming connector

LINE

NEUTRAL

SLI

SNI

9. GND / –

9

SLO

8. Supply fan PWM 8

SNO

7. Supply fan tacho 7

SFL

6. GND / –

6

SFN

5. Extract fan PWM 5

EFL

4. Extract fan tacho 4

EFN

3. GND / –

3

FSO

2. 11,4 VDC / +

2

FSI

1. Control signal S

1

AHL AHN

DIP switch

1

PHL PHN

ERROR RELAY

BL (potential-free)

2 3

BL1

4

BN

E/I

1 234

5

E/O

Extract air NTC Outdoor air NTC Supply air to the apartment NTC Exhaust air NTC Supply air from the cell NTC
Freezing level adjustment

S + – LED 1 2 3 4 5 1 2 3 4 5

Error relay E/O E/I

When remote monitoring is used Leave the signal LED of the external control panel or cooker hood disconnected. Also disconnect the short circuit link between connectors 3 and 5 from the female side of the control panel connector.

Supply air fan

Extract air fan

T1 130 °C

T2 90 °C

R1

LED

Electric post-heating

M

radiator 1500 W

Belimo damper motor 230 VAC

Post-heating control

PWM level adjustment

DIP Switch

Up

1. Post-heating

Electric

2. Additional heating Electric

3. Type of the unit Bypass

4. Extra

Down VKL MLV Supply fan stop

ELECTRICAL CONNECTIONS

ELECTRICAL CONNECTIONS

EXTERNAL ELECTRICAL CONNECTION
With Vallox Delico PTD EC and Vallox Capto PTC EC control hood

3 POTENTIAL FREE CONTACT DATA 24VDC/5A

F ALARM

RS 485

MODE DAMP PIEZO

A B GND IN OUT IN OUT IN OUT + –

TACHO GND 0-11V

PE

DAMPER LIGHT FAN NL 123 NL NL

ALARM *NOTE!

CONTACT DATA: GUARD FUNCTION: NORMAL SITUATION = OPEN ACTIVATED = CLOSED
HOUSE AUTOMATION: NORMAL SITUATION = OPEN ERROR SITUATION (HOOD OR VENTILATION UNIT) = CLOSED ACTIVATED GUARD FUNCTION = FLASHING
POSITION OF THE DAMPER: DAMPER CLOSED = CONTACT OPEN DAMPER OPEN = CONTACT CLOSED

MV VENTILATION UNIT
RM/I RM/O
GND AN/I

MC VENTILATION UNIT Five terminal connector**
E/I LED / E/O
GND S

MC VENTILATION UNIT Four terminal connector
GND S

EC roof fan
Tacho S

  • External error data is connected in the place ** Disconnect the short circuit link between connectors

of the short circuit link of the mother board

3 and 5 from the MC unit’s control panel connector

PROGRAMMING CONNECTORS OF THE MOTHERBOARD GUARD FUNCTION CONTACT DATA HOUSE AUTOMATION CONTACT DATA DAMPER POSITION CONTACT DATA
EXTRA

EXTERNAL ELECTRICAL CONNECTION
with the Vallox Simple Control panel / Vallox PTXP MC, Vallox PTXPA MC cooker hood

Internal connection of the ventilation unit

Control signal S
11.2 VDC / + GND / Error relay / LED

Simple Control
S + – LED

PTXP MC, PTXPA MC
– + S LED

– +S – +S

LED LED

7034500A

11

© Vallox Oy – All rights reserved

ELECTRICAL CONNECTIONS

EXTERNAL ELECTRICAL CONNECTION

with Vallox ProControl panel
Control signal S Internal connection 11.2 VDC / + of the ventilation unit GND / –
Error relay / LED

Wiring between the control panel and the ventilation unit, NOMAK 2x2x0.5+0.5

Ventilation unit cable

Control panel connector

S

Y1

leave disconnected

G0

LED

S/DI2

Cable types specified in the drawing are indicative

Cooker hood or boost switch

optional 946147
RH%

DISTRIBUTION BOARD
24V L N

Nomak 2x2x0,5+0,5

0…10V

2×0.5

The phase of 24 VAC feed is connected to the control panel connector G and the neutral to the connector G0

CONTROL PANEL G 24 VAC feed G0 0 VAC Y1 10 V, control voltage
of the ventilation unit
Y2 DI1 Boost at the cooker hood A1 24 VAC 1 A, intermediate
relay control
Y3 A2 Y4 U1 0…10 V, humidity boost A+ RS-485 B- RS-485 C RS-485 Common

S/DI2 G0

Error relay 0 VAC

2×0.5

Vallox Procontrol 949034

– +S – +S

LED

LED

Nomak 2x2x0,5+0,5

Modbus RS-485 Nomak
2x2x0,5+0,5

G G0 Y1 Y2 DI1 A1 Y3 A2 Y4 U1 A+ B term
CONFIG
BC

S/DI2 G0

EXTERNAL ELECTRICAL CONNECTION
With an external control panel

Internal connection of the ventilation unit

Control signal S 11.2 VDC / + GND / Error relay / LED

– +S – +S

LED LED

Control signal S GND / –

External control panel
An external 0-10 VDC voltage can be connected to the S and GND connectors for fan control.

12

INSTALLATION

INSTALLATION SITE

Vallox 101 MC must be installed in a location where the

The top surface of the side panel of the unit can

temperature remains above +10 °C. When the unit is

be installed against the finished ceiling surface.

installed without a protective enclosure, the location must be chosen so that its noise does not cause any disturbance. Such locations include storage premises and

When the wall mounting plate is used, it must be observed that the ventilation unit will rise roughly 10mm above the final installation height!

technical spaces. NOTE!

604 6

Remember to make a service door in the finished ceiling

so that the connection cables can be accessed. The

service door should be located roughly 500 mm from the

unit door.

Bottom edge of the wall mounting plate

166

283

The outer diameter of the duct is 12mm

12

21

25

Wall mounting
Mount the Vallox 101 MC on the wall with a mounting plate, as shown in the adjacent figure. Make sure that the unit is horizontally level after mounting.
Wall structure
The wall structure must be observed in the mounting. Avoid mounting the unit on hollow, echoing intermediate walls and on bedroom walls, or take measures to prevent conduction of noise.
Wall mounting plate
84 2030 30
35 30

84

30 30 20

30°

25

30 35

162

11

20 60

ø7 14 kpl 550

13

60 20

11

© Vallox Oy – All rights reserved

INSTALLATION

Ceiling mounting by using
a ceiling mounting plate
(optional)
The unit can be equipped with an optional ceiling mounting plate. The ceiling mounting plate must be fastened on rafter frames or other frame structure with M8 thread bars. The bars must be fastened so that they withstand the weight of the unit.
The ceiling mounting plate must be fastened horizontally to make sure that the unit is level. The ceiling mounting plate must be fastened so that there is a 10 mm gap between its rear edge and the finished wall. This way the ventilation unit will be installed as close to the wall as possible. The top edge of the white covering strip of the ceiling mounting plate can be installed against the finished ceiling. Alternatively, a concealed mounting method can be used, in which case the finished ceiling can be 30 mm or less from the top edge of the white covering strip.

The ceiling mounting plate is fastened to the M8 thread bars with the mounting supplies delivered with the mounting plate. NOTE! The end of the thread bars must be 5mm or less below the fastening nut (more detailed instructions are provided with the ceiling mounting plate).
Installing the ventilation unit to the ceiling mounting plate
Remove the unit door. Lift the unit and take the wires through the opening in the ceiling mounting plate. Lift the ventilation unit against the ceiling mounting plate so that it locks in place. The unit has become locked on the ceiling mounting plate when the two operating levers on the mounting plate have been restored to the same level with the white covering strip of the ceiling mounting plate (more detailed instructions are provided with the ceiling mounting plate).

Ceiling mounting plate (optional)
The top edge of the white covering strip of the ceiling mounting plate can be installed against the finished ceiling. Alternatively, a concealed mounting method can be used, in which case the finished ceiling can be 30 mm or less from the top edge of the white covering strip.

The minimum distance from the finished rear wall is 10 mm

The recommended distance from the finished side wall is 10 mm

10

10

598

10

Finished wall

Finished ceiling

Concealed installation of the ceiling mounting plate on the ceiling, max. 30 mm

Finished ceiling

Finished wall

598 Finished wall
Concealed installation of the ceiling mounting plate on the ceiling, max. 30 mm

453

483

453

5 3

3 8

3 8

Installation space of the siphon 73 mm

Siphon Silent Klick

Installation space of the elbow 47 mm

Elbow

14

483

5 3

INSTALLATION

Attic floor penetration plate (optional)
When an attic floor penetration plate is used, the tightness of the vapour barrier has to be ensured.

Finished wall
The attic floor penetration plate can be fastened on the finished rear wall.

The minimum distance from the side walls is 15 mm.

15

15

CONDENSING WATER CONNECTIONS

Installation of the Vallox Silent Klick siphon on the bottom pool
The delivery includes the Vallox Silent Klick siphon. A pipe will be connected to the siphon that leads the water that is condensed from the extract air to the floor drain (not directly into the sewer). The pipe must not rise after the siphon. The ventilation unit must be installed straight to ensure that condensing water can exit the unit unobstructed.
Vallox Silent Klick siphon
Installation height 53 mm, installation space 73 mm, outer diameter of the duct 12 mm

L model

R model

291 291

147,5

147,5

Location of the condensing water outlets, R and L models

Installation of the Vallox Silent Klick siphon on the bottom pool

53

73

Installation of the Vallox Silent Klick siphon on the wall

If the Vallox Silent Klick siphon does not fit into the unit directly, the elbow can be installed at the bottom, and the siphon can be installed on the wall. This installation method requires that there is a 47 mm space underneath the unit. The elbow requires a 38 mm space when installed.

Installation of the Vallox Silent Klick siphon on the wall. The elbow underneath the unit takes less space than the siphon.

Elbow
Installation height 38 mm, installation space 47 mm, outer diameter of the duct 12 mm

38

47

15

© Vallox Oy – All rights reserved

EXPLODED VIEW

EXPLODED VIEW AND PARTS LIST
(Type B3740)

R model in the figure. In the L model, the parts are mirrored
19

18 16 13

17
1
2 11
10 12
9

5

1

2

15 14

86

7

NO. Part

Product number

1 Supply / extract air fan …………………………………………………………………………935450

2 Supply air fan attenuation grid…………………………………………………………….935451.

3 Wall mounting plate ………………………………………………………………………….. 3080700

4 Siphon Vallox Silent Klick ………………………………………………………………….3292500

5 Coarse and fine filter for supply air …………………………………………………….978225

6 HR cell …………………………………………………………………………………………………..933260

7 Lower support for the HR cell …………………………………………………………… 4102504

8 Upper support for HR cell ………………………………………………………………… 3467200

9 Filter frame (extraction) ………………………………………………………………………..978226

10 Coarse filter for extract air ………………………………………………………………….. 978227

NO. Part

Product number

11 HR cell bypass damper assembly…………………………………………………….. 4102523

12 Damper motor ……………………………………………………………………………………….930621

13 Post-heating resistor…………………………………………………………………………….942220

14 Door ……………………………………………………………………………………………………. 4102334

15 Mounting screw of the door …………………………………………………………………990712

16 Motherboard…………………………………………………………………………………………949035

17 Safety switch………………………………………………………………………………………… 948370

18 Glass tube fuse 320 mA slow 5×20 mm …………………………………………….952486

19 NTC sensor (specify the sensor reference number in the order)………946140

D4686 | 20.01.2021 | PDF

www.vallox.com
Vallox Oy | Myllykyläntie 9-11 | 32200 LOIMAA | FINLAND Customer Service +358 10 7732 200 | Technical support +358 10 7732 270
© Vallox – All rights reserved

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals