BANNER S4B Safety Light Curtain Instruction Manual

June 9, 2024
BANNER

S4B Safety Light Curtain

S4B Safety Light Curtain
Instruction Manual

Original Instructions 230287 Rev. A 15 February 2023 © Banner Engineering Corp. All rights reserved

230287

S4B Safety Light Curtain
Contents
1 About This Document ……………………………………………………………………………………………………………………………….. 4 1.1 Important… Read This Before Proceeding! ……………………………………………………………………………………………………………………..4 1.2 Use of Warnings and Cautions …………………………………………………………………………………………………………………………………….. 4 1.3 EU Declaration of Conformity (DoC) ……………………………………………………………………………………………………………………………… 4
2 Standards and Regulations ………………………………………………………………………………………………………………………… 5 2.1 Applicable U.S. Standards …………………………………………………………………………………………………………………………………………… 5 2.2 OSHA Regulations ………………………………………………………………………………………………………………………………………………………5 2.3 International/European Standards ………………………………………………………………………………………………………………………………… 5
3 Introduction ……………………………………………………………………………………………………………………………………………….7 3.1 Features ……………………………………………………………………………………………………………………………………………………………………7 3.2 System Description ……………………………………………………………………………………………………………………………………………………. 7 3.2.1 Components ………………………………………………………………………………………………………………………………………………………. 8 3.2.2 Models ………………………………………………………………………………………………………………………………………………………………. 8 3.3 Appropriate Applications and Limitations ……………………………………………………………………………………………………………………….9 3.3.1 Appropriate Applications ……………………………………………………………………………………………………………………………………….9 3.3.2 Examples: Inappropriate Applications …………………………………………………………………………………………………………………… 10 3.4 Control Reliability: Redundancy and Self-Checking ……………………………………………………………………………………………………….10 3.5 Operating Features ………………………………………………………………………………………………………………………………………………….. 10 3.5.1 Trip Output ………………………………………………………………………………………………………………………………………………………..11 3.5.2 Scan Code Configuration …………………………………………………………………………………………………………………………………… 11 3.5.3 Weak Beam Strength Indication …………………………………………………………………………………………………………………………… 12
4 Specifications …………………………………………………………………………………………………………………………………………. 13 4.1 General Specifications ……………………………………………………………………………………………………………………………………………… 13 4.2 Emitter Specifications ………………………………………………………………………………………………………………………………………………..13 4.3 Receiver Specifications ……………………………………………………………………………………………………………………………………………..14
5 Mechanical Installation …………………………………………………………………………………………………………………………….. 15 5.1 Mechanical Installation Considerations ………………………………………………………………………………………………………………………..15 5.2 Calculating the Safety Distance (Minimum Distance) …………………………………………………………………………………………………….. 15 5.2.1 Formula and Examples ……………………………………………………………………………………………………………………………………….16 5.2.2 Examples ………………………………………………………………………………………………………………………………………………………….17 5.3 Reducing or Eliminating Pass-Through Hazards ………………………………………………………………………………………………………….. 18 5.4 Supplemental Safeguarding ……………………………………………………………………………………………………………………………………….18 5.5 Reset Switch Location ………………………………………………………………………………………………………………………………………………..19 5.6 Other Considerations ……………………………………………………………………………………………………………………………………………….. 20 5.6.1 Adjacent Reflective Surfaces ……………………………………………………………………………………………………………………………….20 5.6.2 Use of Corner Mirrors ………………………………………………………………………………………………………………………………………… 21 5.6.3 Emitter and Receiver Orientation ………………………………………………………………………………………………………………………… 22 5.6.4 Installation of Multiple Systems …………………………………………………………………………………………………………………………… 23 5.7 Mounting System Components ……………………………………………………………………………………………………………………………………24 5.7.1 Mounting Hardware …………………………………………………………………………………………………………………………………………… 24 5.7.2 Sensor Mounting and Mechanical Alignment Verification ………………………………………………………………………………………… 26 5.7.3 Mounting Dimensions and Defined Area ………………………………………………………………………………………………………………. 27
6 Electrical Installation and Testing ……………………………………………………………………………………………………………..28 6.1 Routing Cordsets …………………………………………………………………………………………………………………………………………………….. 28 6.2 Scan Code Selection …………………………………………………………………………………………………………………………………………………28 6.3 Initial Electrical Connections ……………………………………………………………………………………………………………………………………… 30 6.4 Initial Checkout Procedure ………………………………………………………………………………………………………………………………………….30 6.4.1 Configuring the System for Initial Checkout ………………………………………………………………………………………………………….. 30 6.4.2 Apply Initial Power to the S4B System …………………………………………………………………………………………………………………. 30 6.4.3 Optically Align the System Components ………………………………………………………………………………………………………………. 31 6.4.4 Optical Alignment Procedure with Mirrors …………………………………………………………………………………………………………….. 32 6.4.5 Conduct a Trip Test …………………………………………………………………………………………………………………………………………… 32 6.5 Electrical Connections to the Guarded Machine ……………………………………………………………………………………………………………34 6.5.1 Protective Stop (Safety Stop) Circuits ………………………………………………………………………………………………………………….. 34 6.5.2 Preparing for System Operation ………………………………………………………………………………………………………………………….. 35 6.5.3 Sensor Interchangeability ……………………………………………………………………………………………………………………………………. 36 6.5.4 Commissioning Checkout ……………………………………………………………………………………………………………………………………36 6.6 Wiring Diagrams ………………………………………………………………………………………………………………………………………………………..38 6.6.1 Generic Emitter Wiring Diagram …………………………………………………………………………………………………………………………..38 6.6.2 Generic Receiver Wiring Diagram–Self-checking Safety Module, Safety Controller, Safety PLC …………………………………39
7 System Operation ……………………………………………………………………………………………………………………………………. 40 7.1 Security Protocol ………………………………………………………………………………………………………………………………………………………40 7.2 Normal Operation ……………………………………………………………………………………………………………………………………………………..40

S4B Safety Light Curtain
7.2.1 System Power-Up ………………………………………………………………………………………………………………………………………………40 7.2.2 Run Mode …………………………………………………………………………………………………………………………………………………………. 40 7.2.3 Emitter Indicators ……………………………………………………………………………………………………………………………………………….40 7.2.4 Receiver Indicators …………………………………………………………………………………………………………………………………………….41 7.3 Periodic Checkout Requirements ………………………………………………………………………………………………………………………………..41 8 Troubleshooting ……………………………………………………………………………………………………………………………………… 42 8.1 Lockout Conditions ……………………………………………………………………………………………………………………………………………………42 8.2 Receiver Error Codes ………………………………………………………………………………………………………………………………………………..42 8.3 Electrical and Optical Noise ………………………………………………………………………………………………………………………………………. 42 8.3.1 Checking for Sources of Electrical Noise ……………………………………………………………………………………………………………… 42 8.3.2 Check for Sources of Optical Noise ………………………………………………………………………………………………………………………43 9 Checkout Procedures ………………………………………………………………………………………………………………………………..44 9.1 Schedule of Checkouts …………………………………………………………………………………………………………………………………………….. 44 10 Product Support and Maintenance …………………………………………………………………………………………………………. 45 10.1 Cleaning ………………………………………………………………………………………………………………………………………………………………..45 10.2 Warranty Service …………………………………………………………………………………………………………………………………………………….45 10.3 Manufacturing Date …………………………………………………………………………………………………………………………………………………45 10.4 Disposal ………………………………………………………………………………………………………………………………………………………………… 45 10.5 Banner Engineering Corp Limited Warranty ………………………………………………………………………………………………………………. 45 10.6 Contact Us …………………………………………………………………………………………………………………………………………………………….. 46 11 Accessories …………………………………………………………………………………………………………………………………………….47 11.1 Safety Controllers …………………………………………………………………………………………………………………………………………………….47 11.2 In-Line Sensor Status Indicator …………………………………………………………………………………………………………………………………47 11.3 Literature ……………………………………………………………………………………………………………………………………………………………….47 11.4 Brackets ……………………………………………………………………………………………………………………………………………………………….. 47 11.5 Cordsets ………………………………………………………………………………………………………………………………………………………………..48 11.6 Test Piece …………………………………………………………………………………………………………………………………………………………….. 49 11.7 Universal (Input) Safety Modules ………………………………………………………………………………………………………………………………49 11.8 Alignment Aids ………………………………………………………………………………………………………………………………………………………. 50 11.9 MSM Series Corner Mirrors …………………………………………………………………………………………………………………………………….. 50 11.10 SSM Series Corner Mirrors ……………………………………………………………………………………………………………………………………. 51 11.11 MSA Series Stands ……………………………………………………………………………………………………………………………………………….52 12 Glossary ……………………………………………………………………………………………………………………………………………….. 54

S4B Safety Light Curtain
1 About This Document
1.1 Important… Read This Before Proceeding!
It is the responsibility of the machine designer, controls engineer, machine builder, machine operator, and/or maintenance personnel or electrician to apply and maintain this device in full compliance with all applicable regulations and standards. The device can provide the required safeguarding function only if it is properly installed, properly operated, and properly maintained. This manual attempts to provide complete installation, operation, and maintenance instruction. Reading the manual in its entirety is highly recommended to ensure proper understanding of the operation, installation, and maintenance. Please direct any questions regarding the application or use of the device to Banner.
For more information regarding U.S. and international institutions that provide safeguarding application and safeguarding device performance standards, see Standards and Regulations on page 5.
WARNING: · The user is responsible for following these instructions. · Failure to follow any of these responsibilities may potentially create a dangerous condition that could result in serious injury or death. · Carefully read, understand, and comply with all instructions for this device. · Perform a risk assessment that includes the specific machine guarding application. Guidance on a compliant methodology can be found in ISO 12100 or ANSI B11.0. · Determine what safeguarding devices and methods are appropriate per the results of the risk assessment and implement per all applicable local, state, and national codes and regulations. See ISO 13849-1, ANSI B11.19, and/or other appropriate standards. · Verify that the entire safeguarding system (including input devices, control systems, and output devices) is properly configured and installed, operational, and working as intended for the application. · Periodically re-verify, as needed, that the entire safeguarding system is working as intended for the application.

1.2 Use of Warnings and Cautions

The precautions and statements used throughout this document are indicated by alert symbols and must be followed for the safe use of the S4B Safety Light Curtain. Failure to follow all precautions and alerts may result in unsafe use or operation. The following signal words and alert symbols are defined as follows:

Signal Word

Definition

Symbol

WARNING:

Warnings refer to potentially hazardous situations which, if not avoided, could result in serious injury or death.

CAUTION:

Cautions refer to potentially hazardous situations which, if not avoided, could result in minor or moderate injury.

These statements are intended to inform the machine designer and manufacturer, the end user, and maintenance personnel, how to avoid misapplication and effectively apply the S4B Safety Light Curtain to meet the various safeguarding application requirements. These individuals are responsible to read and abide by these statements.

1.3 EU Declaration of Conformity (DoC)

Banner Engineering Corp. herewith declares that these products are in conformity with the provisions of the listed directives and all essential health and safety requirements have been met. For the complete DoC, please go to www.bannerengineering.com.

Product

Directive

S4B Safety Light Curtain

Machinery Directive 2006/42/EC

Representative in EU: Spiros Lachandidis, Managing Director, Banner Engineering BV. Address: Park Lane, Culliganlaan 2F, bus 3,1831 Diegem, Belgium.

4

www.bannerengineering.com – Tel: + 1 888 373 6767

S4B Safety Light Curtain
2 Standards and Regulations
The list of standards below is included as a convenience for users of this Banner device. Inclusion of the standards below does not imply that the device complies specifically with any standard, other than those specified in the Specifications section of this manual.
2.1 Applicable U.S. Standards
ANSI B11.0 Safety of Machinery, General Requirements, and Risk Assessment ANSI B11.1 Mechanical Power Presses ANSI B11.2 Hydraulic Power Presses ANSI B11.3 Power Press Brakes ANSI B11.4 Shears ANSI B11.5 Iron Workers ANSI B11.6 Lathes ANSI B11.7 Cold Headers and Cold Formers ANSI B11.8 Drilling, Milling, and Boring ANSI B11.9 Grinding Machines ANSI B11.10 Metal Sawing Machines ANSI B11.11 Gear Cutting Machines ANSI B11.12 Roll Forming and Roll Bending Machines ANSI B11.13 Single- and Multiple-Spindle Automatic Bar and Chucking Machines ANSI B11.14 Coil Slitting Machines ANSI B11.15 Pipe, Tube, and Shape Bending Machines ANSI B11.16 Metal Powder Compacting Presses ANSI B11.17 Horizontal Extrusion Presses ANSI B11.18 Machinery and Machine Systems for the Processing of Coiled Strip, Sheet, and Plate ANSI B11.19 Performance Criteria for Safeguarding ANSI B11.20 Manufacturing Systems ANSI B11.21 Machine Tools Using Lasers ANSI B11.22 Numerically Controlled Turning Machines ANSI B11.23 Machining Centers ANSI B11.24 Transfer Machines ANSI/RIA R15.06 Safety Requirements for Industrial Robots and Robot Systems NFPA 79 Electrical Standard for Industrial Machinery ANSI/PMMI B155.1 Package Machinery and Packaging-Related Converting Machinery — Safety Requirements
2.2 OSHA Regulations
OSHA Documents listed are part of: Code of Federal Regulations Title 29, Parts 1900 to 1910 OSHA 29 CFR 1910.212 General Requirements for (Guarding of) All Machines OSHA 29 CFR 1910.147 The Control of Hazardous Energy(lockout/tagout) OSHA 29 CFR 1910.217 (Guarding of) Mechanical Power Presses
2.3 International/European Standards
EN ISO 12100 Safety of Machinery ­ General Principles for Design — Risk Assessment and Risk Reduction ISO 13857 Safety of Machinery ­ Safety Distances to Prevent Hazard Zones Being Reached ISO 13850 (EN 418) Emergency Stop Devices, Functional Aspects ­ Principles for Design ISO 13851 Two-Hand Control Devices ­ Principles for Design and Selection IEC 62061 Functional Safety of Safety-Related Electrical, Electronic and Programmable Control Systems EN ISO 13849-1:2015 Safety-Related Parts of Control Systems

www.bannerengineering.com – Tel: + 1 888 373 6767

5

S4B Safety Light Curtain
EN 13855 (EN 999) The Positioning of Protective Equipment in Respect to Approach Speeds of Parts of the Human Body ISO 14119 (EN 1088) Interlocking Devices Associated with Guards ­ Principles for Design and Selection EN 60204-1 Electrical Equipment of Machines Part 1: General Requirements IEC 61496 Electro-sensitive Protection Equipment IEC 60529 Degrees of Protection Provided by Enclosures IEC 60947-1 Low Voltage Switchgear ­ General Rules IEC 60947-5-1 Low Voltage Switchgear ­ Electromechanical Control Circuit Devices IEC 60947-5-5 Low Voltage Switchgear ­ Electrical Emergency Stop Device with Mechanical Latching Function IEC 61508 Functional Safety of Electrical/Electronic/Programmable Electronic Safety-Related Systems IEC 62046 Safety of Machinery ­ Applications of Protective Equipment to Detect the Presence of Persons ISO 3691-4 Industrial Trucks–Safety Requirements and Verification, Part 4 Driverless Industrial trucks and their Systems

6

www.bannerengineering.com – Tel: + 1 888 373 6767

3 Introduction
3.1 Features

S4B Safety Light Curtain

· A two-piece optoelectronic safeguarding device
· Creates a screen of synchronized, modulated infrared sensing beams that extend from end-to-end of the sensors (no “dead zone”)
· Compact package for smaller production machines, robust for large power presses
· 30 mm resolution
· Defined areas of 300 mm (12 in) to 1800 (71 in) mm, in increments of 150 mm (6 in)
· 0.1 m to 12 m range (4 in to 39 ft); the range decreases with the use of corner mirrors and/or lens shields:
Lens Shields–an approximately 10% reduction in range per shield
Glass-surface mirrors–an approximately 8% reduction in range per mirror
· Zone and Status indicators for diagnostics
· FMEA tested to ensure control reliability
· Highly immune to EMI, RFI, ambient light, weld flash, and strobe light
· Safety PLC input compatible (per OSSD specifications)

3.2 System Description
Banner S4B emitters and receivers provide a redundant, microprocessor- controlled, opposed-mode optoelectronic safety light screen. S4B typically is used for point-of-operation safeguarding, and is suited to safeguard a variety of machinery.
The S4B emitters have a row of synchronized modulated infrared (invisible) light-emitting diodes (LEDs) in a compact housing. Receivers have a corresponding row of synchronized photodetectors. The light screen created by the emitter and receiver is called the defined area; its width and height are determined by the length of the sensor pair and the distance between them. The defined area (sensing area) is equivalent to the height of the sensors. The maximum sensing range is 12 m (39 ft), which decreases if corner mirrors or lens shields are used. The sensing area extends from end to end of the housing; there is no dead zone.
In typical operation, if any part of an operator’s body (or any opaque object) of more than a pre-determined cross section is detected, the solid-state Output Signal Switching Device (OSSD) safety outputs turn OFF. These safety outputs are typically connected to an external monitoring device such as a Banner XS26-2 Safety Controller.
Electrical connections (power, ground, inputs, and outputs) are made via M12 quick-disconnect connections.
All models require a supply voltage of +24 V DC ±15%.
Both the emitter and the receiver feature LEDs to provide continuous indication of operating status and error conditions.
All models include the ability to select between two scan codes.

www.bannerengineering.com – Tel: + 1 888 373 6767

7

S4B Safety Light Curtain

3.2.1 Components
An S4B “System” refers to a compatible emitter and receiver (equal length and resolution), and cordset(s) for each. RD to M12 cordsets, side mounting brackets, and specified test pieces are sold separately.
Figure 1. Main Components

1

4

2

1. Receiver

3

2. Emitter 3. Defined area

4. Specified test piece

5. Location of the status indicators
5

3.2.2 Models

Emitter
S4BE30-300-S S4BE30-450-S S4BE30-600-S S4BE30-750-S S4BE30-900-S S4BE30-1050-S S4BE30-1200-S S4BE30-1350-S S4BE30-1500-S S4BE30-1650-S S4BE30-1800-S

Receiver
S4BR30-300-S S4BR30-450-S S4BR30-600-S S4BR30-750-S S4BR30-900-S S4BR30-1050-S S4BR30-1200-S S4BR30-1350-S S4BR30-1500-S S4BR30-1650-S S4BR30-1800-S

Defined Area (mm)

Response Time, Tr (ms)

300

7.5

450

8.5

600

10.0

750

11.5

900

12.5

1050

14.0

1200

15.0

1350

16.5

1500

17.5

1650

19.0

1800

20.0

Recovery Time, OSSDs OFF to ON (ms)

Non-Sync Beam Blocked

All Beams Blocked

29 typical

49 typical, 295 maximum

35 typical

65 typical, 337 maximum

41 typical

75 typical, 379 maximum

48 typical

85 typical, 421 maximum

54 typical

98 typical, 463 maximum

60 typical

112 typical, 506 maximum

65 typical

122 typical, 544 maximum

71 typical

128 typical, 582 maximum

78 typical

141 typical, 620 maximum

84 typical

150 typical, 658 maximum

90 typical

172 typical, 697 maximum

8

www.bannerengineering.com – Tel: + 1 888 373 6767

S4B Safety Light Curtain
3.3 Appropriate Applications and Limitations
WARNING: · Read this Section Carefully Before Installing the System · Failure to follow these instructions could result in serious injury or death. · If all mounting, installation, interfacing, and checkout procedures are not followed properly, this Banner device cannot provide the protection for which it was designed. · The user is responsible for ensuring that all local, state, and national laws, rules, codes, or regulations relating to the installation and use of this control system in any particular application are satisfied. Ensure that all legal requirements have been met and that all technical installation and maintenance instructions contained in this manual are followed. · The user has the sole responsibility to ensure that this Banner device is installed and interfaced to the guarded machine by Qualified Persons, in accordance with this manual and applicable safety regulations. A Qualified person is a person who, by possession of a recognized degree or certificate of professional training, or who, by extensive knowledge, training and experience, has successfully demonstrated the ability to solve problems relating to the subject matter and work.
The Banner S4B is intended for point-of-operation machine guarding and other safeguarding applications. It is the user’s responsibility to verify whether the safeguarding is appropriate for the application and is installed, as instructed by this manual, by a Qualified Person. The ability of the S4B to perform its safeguarding function depends upon the appropriateness of the application and upon its proper mechanical and electrical installation and interfacing to the guarded machine. If all mounting, installation, interfacing, and checkout procedures are not followed properly, the S4B cannot provide the protection for which it was designed.
WARNING: · Install System Only on Appropriate Applications · Failure to follow these instructions could result in serious injury or death. · Use Banner’s S4B only on machinery that can be stopped immediately after a stop signal is issued at any point in the machine’s stroke or cycle, such as part-revolution clutched machines. Under no circumstances may the S4B be used on full- revolution clutched machinery or in unsuitable applications. · If there is any doubt about whether or not your machinery is compatible with the S4B, contact Banner Engineering.
3.3.1 Appropriate Applications
S4B is typically used for, but is not limited to, the following applications: · Small assembly equipment · Automated production equipment · Robotic work cells · Molding and power presses · Assembly and packaging machines · Lean manufacturing systems

www.bannerengineering.com – Tel: + 1 888 373 6767

9

S4B Safety Light Curtain

Figure 2. Typical Application

3.3.2 Examples: Inappropriate Applications
Do not use the S4B in the following applications:
· With any machine that cannot be stopped immediately after a stop signal is issued, such as single-stroke (or fullrevolution) clutched machinery
· With any machine with inadequate or inconsistent machine response time and stopping performance · With any machine that ejects materials or component parts through the defined area · In any environment that is likely to adversely affect photoelectric sensing efficiency. For example, corrosive chemicals
or fluids or unusually severe levels of smoke or dust, if not controlled, may degrade sensing efficiency · As a tripping device to initiate or reinitiate machine motion (PSDI applications), unless the machine and its control
system fully comply with the relevant standard or regulation (see OSHA 29CFR1910.217, NFPA 79, ANSI B11.19, ISO 12100, IEC 60204-1, IEC 61496-1, or other appropriate standard)
If the S4B is installed for use as a perimeter guard (where a pass-through hazard may exist, see Reducing or Eliminating Pass-Through Hazards on page 18), the dangerous machine motion can be initiated by normal means only after the safeguarded area is clear of individuals and the external safety monitoring device has been manually reset.

3.4 Control Reliability: Redundancy and Self-Checking
Redundancy requires that S4B circuit components be backed up to the extent that, if the failure of a single component will prevent effective machine stopping action when needed, that component must have a redundant counterpart which will perform the same function. The S4B is designed with redundant microprocessors.
Redundancy must be maintained whenever the S4B is in operation. Because a redundant system is no longer redundant after a component has failed, S4B is designed to monitor itself continuously. A component failure detected by or within the self-checking system causes a stop signal to be sent to the guarded machine and puts the S4B into a Lockout condition.
A recovery from this type of Lockout condition requires: · Replacing the failed component (to restore redundancy), and · Performing the appropriate reset procedure.

3.5 Operating Features
The sensing resolution is determined by the emitter and receiver model.
WARNING: · Use of automatic (trip) or manual (latch) start/restart · Failure to follow these instructions could result in a serious injury or death. · Applying power to the Banner device, clearing the defined area, or resetting a latch condition must not initiate dangerous machine motion. Design the machine control circuitry so that one or more initiation devices must be engaged to start the machine (a conscious act), in addition to the Banner device going into Run mode.
Emitter Wiring Options–An S4B emitter can be connected either to its own power supply or to the receiver cable, color-forcolor. The color-for-color wiring allows the emitter and receiver positions to be interchanged without rewiring. Status Indicators–Status indicators on both the emitter and receiver are clearly visible on each sensor’s front panel.

10

www.bannerengineering.com – Tel: + 1 888 373 6767

For more information, see System Operation on page 40. Emitter:

Key Description

1

Status indicator (red/green)–shows whether power is applied or the device is in a

lockout condition.

2

Scan Code indicator (red/green/yellow)–shows the scan code setting (1 or 2) at

power-up

1

S4B Safety Light Curtain
2

Receiver:

Key Description

1

Status indicator (red/green)–shows System status:

· Outputs are ON or OFF (green ON or red ON)

· The System is in Lockout condition (flashing red)

2

Zone indicators (red/green/yellow)–each shows the status of approximately 1/3 of the

total beams: · Aligned and clear (green ON) · Blocked and/or misaligned (red ON)

1

2

· All beams are clear, but one or more beams have weak beam strength

(yellow ON)

The Zone 1 indicator, at the bottom of this view, represents the 1/3 of the unit that is

toward the RD end of the unit. The Zone 2 indicator is in the middle and represents the middle 1/3 of the unit. The Zone 3 indicator is at the top and represents the 1/3 of

3

the unit closest to the end cap.

3

Zone 1 Indicator–indicates beam synchronization status

3.5.1 Trip Output
The System is configured for Trip Output which allows the System to enter Run mode automatically. Other measures must be taken to prevent a pass-through hazard; see Reducing or Eliminating Pass-Through Hazards on page 18 and the warning below for more information.
The OSSD outputs turn ON after power is applied, and the receiver passes its internal self-test/synchronization and recognizes that all beams are clear. The Trip Output also automatically resets after all beams are cleared.
WARNING: · Use of automatic (trip) or manual (latch) start/restart · Failure to follow these instructions could result in a serious injury or death. · Applying power to the Banner device, clearing the defined area, or resetting a latch condition must not initiate dangerous machine motion. Design the machine control circuitry so that one or more initiation devices must be engaged to start the machine (a conscious act), in addition to the Banner device going into Run mode.

3.5.2 Scan Code Configuration
Use the scan code to allow operation of multiple pairs of emitters and receivers in close proximity without the effects of crosstalk.
The emitter and receiver may be configured to use one of two scan codes (1 or 2); a receiver recognizes light only from an emitter with the same scan code. Set the scan code switches of the removable disconnect of each sensor (see Scan Code Selection on page 28). Both the emitter and its corresponding receiver must have the same setting.
The default setting is Scan Code 1.

www.bannerengineering.com – Tel: + 1 888 373 6767

11

S4B Safety Light Curtain
3.5.3 Weak Beam Strength Indication
Weak beam strength is indicated when one or more channels are made, but the beam strength is marginal. This indication can be used to aid alignment of the sensor and also to indicate when window cleaning might be needed. The Zone indicator representing the area of the channel(s) with the weak beam strength immediately turns yellow when the marginal signal is detected. The Weak Beam Strength Output, receiver pin 5, turns ON any time one or more channels are detected with a marginal signal for longer than 1 minute. After the signal rises above the marginal level, the Weak Beam Strength Output turns OFF.

12

www.bannerengineering.com – Tel: + 1 888 373 6767

S4B Safety Light Curtain

4 Specifications

4.1 General Specifications
Short Circuit Protection All inputs and outputs are protected from short circuits to +24 V DC or DC common
Electrical Safety Class III (per IEC 61140)
Safety Ratings Type 4 per IEC 61496-1, -2 Category 4 PL e per EN ISO 13849-1:2015 SIL3 per IEC 61508 PFHd: 1.56 × 10-8 MTTFd: 71 years
Effective Aperture Angle (EAA) Meets Type 4 requirements per IEC 61496-2
Operating Conditions ­20 °C to +55 °C (­4 °F to +131°F) 95% maximum relative humidity (non-condensing)
Storage Temperature ­30 °C to +65 °C (­22 °F to +149 °F)
Certifications

Environmental Rating For indoor use only IP65 (EN 60529)
Resolution 30 mm
Operating Range 0.1 m to 12 m (4 in to 39 ft)
Enclosure Anodized aluminum housing with well-sealed zinc die-cast end-caps, polycarbonate window
Mounting Hardware Mounting brackets are made from glass-filled polycarbonate
Vibration and Mechanical Shock Components have passed vibration and shock tests according to IEC 61496-1 (Class 3M4). This includes vibration (30 cycles) of 5 Hz to 150 Hz at 3.5 mm (0.14 in) amplitude and 1 g acceleration, and shock of 15 g for 6 milliseconds (600 cycles).

4.2 Emitter Specifications

Supply Voltage at the Device +24 V DC ±15% (use a SELV-rated power supply according to EN IEC 60950) Power supply must meet the requirements of IEC 60204-1 and IEC 61496-1.
Status Indicators One bi-color (red/green) Status Indicator: indicates operating mode, lockout or power Off condition Two tri-color (red/green/yellow) Scan Code Indicators: shows scan code setting (1 or 2) at power-up

Supply Current 26 mA typical 40 mA maximum 1
Residual Ripple ± 10% maximum
Wavelength of Emitter Elements Infrared LEDs, 860 nm at peak emission
Controls and Adjustments Scan Code Selection: 2 dual-position switches, located in the removable cordset assembly, to select between scan codes (code 1 or 2) Factory default position is code 1

1 Maximum current occurs at a supply voltage of 20 V DC.

www.bannerengineering.com – Tel: + 1 888 373 6767

13

S4B Safety Light Curtain

4.3 Receiver Specifications

Supply Voltage at the Device +24 V DC ±15% (use a SELV-rated power supply according to EN IEC 60950) Power supply must meet the requirements of IEC 60204-1 and IEC 61496-1.
Status Indicators Bi-color (red/green) Status indicator: indicates general system and output status Tri-color (red/green/yellow) Zone Status indicators: indicate condition (clear, weak, or blocked beam) of a defined group of beams and also shows the scan code at start up
Output Signal Switching Devices (OSSDs) Two redundant solid-state 24 V DC, 0.5 A maximum sourcing OSSD (Output Signal Switching Device) safety outputs (use optional interface solutions for AC or larger DC loads) ON-State voltage: > Vin – 1.5 V DC OFF-State voltage: 0 V DC typical, 1 V DC maximum (no load) OFF-State, maximum allowed external voltage: 1.5 V DC 2 Maximum load capacitance: 1.0 µF Maximum cable resistance to load: 5 ohms per wire Maximum leakage current: 50 µA (with open 0 V) OSSD test pulse width: 200 µs typical OSSD test pulse period: 200 ms typical Switching current: 0 A minimum; 0.5 A maximum (per OSSD)

Weak Beam Strength Output Current-sourcing (PNP) solid-state output, 100 mA at 24 V DC
Supply Current (no load) 58 mA typical 82 mA maximum 3 Exclusive of OSSD1 and OSSD2 loads (up to additional 0.5 A each)
Residual Ripple ±10% maximum
Response Time See Models on page 8
Recovery Time Blocked to Clear (OSSDs Off to On; varies with total number of sensing beams and whether Sync beam is blocked). See Models on page 8
Controls and Adjustments Scan Code Selection: 2 dual position switches, located in removable cordset assembly, to select between scan codes (code 1 or 2). Factory default position is code 1.

2 The maximum voltage allowed on the OSSDs in the OFF-state without a lockout occurring. This voltage may occur, for example, from the input structure of a safety relay module connected to the S4B OSSDs.
3 Maximum current occurs at a supply voltage of 20 V DC.

14

www.bannerengineering.com – Tel: + 1 888 373 6767

S4B Safety Light Curtain
5 Mechanical Installation
The S4B system performance as a safety guarding device depends on: · The suitability of the application · The proper mechanical and electrical installation and interfacing to the guarded machine
WARNING: · Read this Section Carefully Before Installing the System · Failure to follow these instructions could result in serious injury or death. · If all mounting, installation, interfacing, and checkout procedures are not followed properly, this Banner device cannot provide the protection for which it was designed. · The user is responsible for ensuring that all local, state, and national laws, rules, codes, or regulations relating to the installation and use of this control system in any particular application are satisfied. Ensure that all legal requirements have been met and that all technical installation and maintenance instructions contained in this manual are followed. · The user has the sole responsibility to ensure that this Banner device is installed and interfaced to the guarded machine by Qualified Persons, in accordance with this manual and applicable safety regulations. A Qualified person is a person who, by possession of a recognized degree or certificate of professional training, or who, by extensive knowledge, training and experience, has successfully demonstrated the ability to solve problems relating to the subject matter and work.

5.1 Mechanical Installation Considerations
The two primary factors that influence the layout of the S4B system mechanical installation are: · Safety Distance (Minimum Distance) (see Calculating the Safety Distance (Minimum Distance) on page 15) · Supplemental safeguarding/eliminating pass-through hazards (see Reducing or Eliminating Pass-Through Hazards on page 18)
Other considerations include: · Emitter and Receiver Orientation (see Emitter and Receiver Orientation on page 22) · Adjacent Reflective Surfaces (see Adjacent Reflective Surfaces on page 20) · Use of Corner Mirrors (see Use of Corner Mirrors on page 21) · Installation of Multiple Systems (see Installation of Multiple Systems on page 23)
WARNING: · Position the System Components Carefully · Failure to observe this warning could result in serious injury or death. · Position the system components such that the hazard cannot be accessed by reaching over, under, around, or through the sensing field. Additional and supplemental guarding may be required.

5.2 Calculating the Safety Distance (Minimum Distance)
Safety Distance (Ds), also called Minimum Distance (S), is the minimum distance required between the defined area and the closest reachable hazard point. The distance is calculated so that when an object or a person is detected (by blocking a sensing beam), the S4B sends a stop signal to the machine, causing it to stop by the time the object or person can reach any machine hazard point.
The distance is calculated differently for U.S. and European installations. Both methods take into account several factors, including a calculated human speed, the total system stopping time (which itself has several components), and the depth penetration factor. After the distance has been determined, record the calculated distance on the Daily Checkout Card.
WARNING: · Calculate the Safety Distance (Minimum Distance) · Failure to establish and maintain the safety distance (minimum distance) could result in serious injury or death. · Mount the components at a distance from the nearest hazard such that an individual cannot reach the hazard before cessation of the hazardous motion or situation. Calculate this distance using the supplied formulas, as described by ANSI B11.19 and ISO 13855. Mount the components more than 100 mm (4 in) away from the hazard, regardless of the calculated value.

www.bannerengineering.com – Tel: + 1 888 373 6767

15

S4B Safety Light Curtain

Figure 3. Safety distance (minimum distance) and hard (fixed) guarding Hard (fixed) Guarding

Hard (fixed) Guarding

Robot
TurnTable

Safety Light Curtain/Screen Reset Switch

Nearest Hazard Point

5.2.1 Formula and Examples
U.S. Applications The Safety (Separation) Distance formula for U.S. applications: Ds = K × (Ts + Tr) + Dpf

European Applications The Minimum Distance formula for European applications: S = (K × T) + C

Ds the Safety Distance (in inches)
K
1600 mm per second (or 63 in per second), the OSHA 29CFR1910.217, and ANSI B11.19 recommended hand-speed constant (see Note 1 below)
Ts the overall stop time of the machine (in seconds) from the initial stop signal to the final ceasing of all motion, including stop times of all relevant control elements (for example, XS26-2 Safety Controllers) and measured at maximum machine velocity (see Note 3 below)
Tr the maximum response time, in seconds, of the S4B emitter/ receiver pair (depending on model)
Dpf the added distance due to the depth penetration factor as prescribed in OSHA 29CFR1910.217, and ANSI B11.19 for U.S. applications. See Depth Penetration Factor (Dpf) table below or calculate using the formula (in mm): Dpf = 3.4 × (S ­ 7) where S is the resolution of the light curtain (for S 63 mm).

S the Minimum Distance, in mm, from danger zone to light screen center line; minimum allowable distance is 100 mm ( 175 mm for non-industrial applications), regardless of calculated value
K hand-speed constant (see Note 2 below); 2000 mm/s (for Minimum Distances < 500 mm) 1600 mm/s (for Minimum Distances > 500 mm)
T the overall machine stopping response time (in seconds), from the physical initiation of the safety device and the machine coming to a stop (or the hazard removed). This can be broken down into two parts: Ts and Tr where T = Ts + Tr
C the additional distance, in mm, based on intrusion of a hand or object towards the danger zone prior to actuation of a safety device. Calculate using the formula (in mm):
C = 8 × (d – 14)
where d is the resolution of the light curtain (for d 40 mm), or use 850 mm for C.

Table 1: Depth Penetration Factor (Dpf)

30 mm Systems 78 mm (3.1 in)

16

www.bannerengineering.com – Tel: + 1 888 373 6767

S4B Safety Light Curtain
Notes: 1. The OSHA-recommended hand speed constant K has been determined by various studies and, although these studies indicate speeds of 1600 mm/sec. (63 in/sec.) to more than 2500 mm/sec. (100 in/sec.), they are not conclusive determinations. Consider all factors, including the physical ability of the operator, when determining the value of K to be used. 2. The recommended hand speed constant K, derived from data on approach speeds of the body or parts of the body as stated in ISO 13855. 3. Ts is usually measured by a stop-time measuring device. If the machine manufacturer’s specified stop time is used, at least 20% should be added to allow for possible clutch/ brake system deterioration. This measurement must take into account the slower of the two MPCE channels, and the response time of all devices or controls that react to stop the machine.
WARNING: · Stop time (Ts) must include the response time of all devices or controls that react to stop the machine · If all devices are not included, the calculated safety distance (Ds or S) will be too short, which can lead to serious injury or death. · Include the stop time of all relevant devices and controls in your calculations. · If required, each of the two machine primary control elements (MPCE1 and MPCE2) must be capable of immediately stopping the dangerous machine motion, regardless of the state of the other. These two channels of machine control need not be identical, but the stop time performance of the machine (Ts, used to calculate the safety distance) must take into account the slower of the two channels.
5.2.2 Examples
U.S. Applications, Model S4BR30-600-S
K = 63 inches per second (the hand speed constant set by OSHA) Ts = 0.31 (0.250 second is specified by the machine manufacturer; plus 20% safety factor; plus 13 ms for XS26-2
Safety Controller response time) Tr = 0.010 seconds (the specified response time of a S4BR30-600-S System) Dpf = 3.1 inches (30 mm resolution) Substitute the numbers into the formula as follows:
Ds = K × ( Ts + Tr ) + Dpf
Ds = 63 × (0.31 + 0.010) + 3.1 = 23.3 in Mount the S4B emitter and receiver so that no part of the defined area will be closer than 23.3 inches to the closest reachable hazard point on the guarded machine.
European Applications, Model S4BR30-600-S
K = 1600 mm per second T = 0.32 (0.250 second specified by machine manufacturer; plus 20% safety factor; plus 13 ms XS26-2 Safety
Controller response time), plus 0.010 seconds (the specified response time of a S4BR30-600-S System) C = 8 × (30 ­ 14) = 128 mm (30 mm resolution) Substitute the numbers into the formula as follows:
S = (K × T ) + C
S = (1600 × 0.32) + 128 = 640 mm Mount the S4B emitter and receiver so that no part of the defined area will be closer than 640 mm to the closest reachable hazard point on the guarded machine.

www.bannerengineering.com – Tel: + 1 888 373 6767

17

S4B Safety Light Curtain

5.3 Reducing or Eliminating Pass-Through Hazards
A pass-through hazard is associated with applications where personnel may pass through a safeguard, such as the S4B Safety Light Curtain (which issues a stop command to remove the hazard), and then continues into the guarded area. This is common in access and perimeter guarding applications. Subsequently, their presence is no longer detected, and the related danger becomes the unexpected start or restart of the machine while personnel are within the guarded area.
In the use of light screens, a pass-through hazard typically results from large safety distances calculated from long stopping times, large minimum object sensitivities, reach-over, reach-through, or other installation considerations. A pass-through hazard can be generated with as little as 75 mm (3 in) between the sensing field and the machine frame or hard (fixed) guarding.
Eliminate or reduce pass-through hazards whenever possible. While it is recommended to eliminate the pass-through hazard altogether, this may not be possible due to machine layout, machine capabilities, or other application considerations.
One solution is to ensure that personnel are continually sensed while within the hazardous area. This can be accomplished by using supplemental safeguarding, such as described by the safety requirements in ANSI B11.19 or other appropriate standards.
An alternative method is to ensure that after the safeguarding device is tripped, the corresponding safety monitoring device latches and requires a deliberate manual action to reset. This method of safeguarding relies upon the location of the reset switch as well as safe work practices and procedures to prevent an unexpected start or restart of the guarded machine. The S4B Safety Light Curtain does not provide a configurable Manual Start/Restart (Latch Output) function. For these applications, this function must be implemented in the external safety monitoring device.
WARNING: · Use of the Banner device for Access or Perimeter Guarding · Failure to observe this warning could result in serious injury or death. · If a Banner device is installed in an application that results in a pass-through hazard (for example, perimeter guarding), either the Banner device System or the Machine Primary Control Elements (MPCEs) of the guarded machine must cause a Latched response following an interruption of the defined area. The reset of this Latched condition may only be achieved by actuating a reset switch that is separate from the normal means of machine cycle initiation. Lockout/Tagout procedures per ANSI Z244.1 may be required, or additional safeguarding, as described by ANSI B11.19 safety requirements or other appropriate standards, must be used if a passthrough hazard can not be eliminated or reduced to an acceptable level of risk.

5.4 Supplemental Safeguarding

As described in Calculating the Safety Distance (Minimum Distance) on page 15, position the S4B such that an individual cannot reach through the defined area and access the hazard point before the machine has stopped.
Additionally, the hazard cannot be accessible by reaching around, under, or over the defined area. To accomplish this, supplemental guarding (mechanical barriers, such as screens or bars), as described by ANSI B11.19 safety requirements or other appropriate standards, must be installed. Access will then be possible only through the defined area of the S4B System or through other safeguarding that prevents access to the hazard.
The mechanical barriers used for this purpose are typically called “hard (fixed) guarding”; there must be no gaps between the hard (fixed) guarding and the defined area. Any openings in the hard (fixed) guarding must comply with the safe opening requirements of ANSI B11.19 or other appropriate standard.

Figure 4. An example of supplemental safeguarding

Hard (fixed) Guarding

Opening

Hard (fixed) Guarding

Area Guarding

Robot

TurnTable

Area Guarding

Conveyor

Safety Light Curtain/Screen Reset Switch

This is an example of supplemental safeguarding inside a robotic work cell. The S4B, in conjunction with the hard (fixed) guarding, is the primary safeguard. Supplemental safeguarding (such as a horizontal-mounted safety light screen as an area guard) is required in areas that cannot be viewed from the reset switch (for example, behind the robot and the conveyor).

18

www.bannerengineering.com – Tel: + 1 888 373 6767

S4B Safety Light Curtain
Additional supplemental safeguarding may be required to prevent clearance or trapping hazards (for example, a safety mat as an area guard between the robot, the turntable, and the conveyor).
WARNING: · The hazard must be accessible only through the sensing field · Incorrect system installation could result in serious injury or death. · The installation of the S4B must prevent any individual from reaching around, under, over or through the defined area and into the hazard without being detected. · See OSHA CFR 1910.217, ANSI B11.19, and/or ISO 14119, ISO 14120 and ISO 13857 for information on determining safety distances and safe opening sizes for your guarding device. Mechanical barriers (for example, hard (fixed) guarding) or supplemental safeguarding might be required to comply with these requirements.
5.5 Reset Switch Location
The S4B has a trip output (auto power-up and automatic reset) that turns the OSSD outputs ON when the defined area is unobstructed (clear). Per application requirements, a latch response requiring a manual reset to a power-up condition or after an interruption has cleared the defined area might be required. The latch function can be provided by interfacing the S4B OSSD outputs to the machine’s safety-related control system, a safety controller (such as SC10-2roe or XS/SC26-2), or safety module (such as the UM-FA-9A/11A). The system or device providing the latch/reset function must conform to the level of performance required by the risk assessment. In applications requiring Control Reliability and/or ISO 13849-1:2015 Categories 3 or 4 and PL d or e, it is recommended that a monitored manual reset (for example, open- closed-open action), such that a shorted or tied-down button cannot cause a reset be used. The reset switch must be mounted at a location that complies with the warning and guidelines below. If any hazardous areas are not in view from the switch location, additional means of safeguarding must be provided. The switch should be protected from accidental or unintended actuation (for example, through the use of rings or guards). A key-actuated reset switch provides some operator or supervisory control, as the key can be removed from the switch and taken into the guarded area. However, this does not prevent unauthorized or inadvertent resets due to spare keys in the possession of others, or additional personnel entering the guarded area unnoticed. When considering where to locate the reset switch, follow the guidelines below.
WARNING: · Install reset switches properly · Failure to properly install reset switches could result in serious injury or death. · Install reset switches so that they are accessible only from outside, and in full view of, the safeguarded space. Reset switches cannot be accessible from within the safeguarded space. Protect reset switches against unauthorized or inadvertent operation (for example, through the use of rings or guards). If there are any hazardous areas that are not visible from the reset switches, provide additional safeguarding.
All reset switches must be: · Outside the guarded area · Located to allow the switch operator a full, unobstructed, view of the entire guarded area while the reset is performed · Out of reach from within the guarded area · Protected against unauthorized or inadvertent operation (such as through the use of rings or guards).
Important: Resetting a safeguard must not initiate hazardous motion. Safe work procedures require a start-up procedure to be followed and the individual performing the reset to verify that the entire hazardous area is clear of all personnel before each reset of the safeguard is performed. If any area cannot be observed from the reset switch location, additional supplemental safeguarding must be used: at a minimum, visual and audible warnings of machine start-up.

www.bannerengineering.com – Tel: + 1 888 373 6767

19

S4B Safety Light Curtain

5.6 Other Considerations
5.6.1 Adjacent Reflective Surfaces
A reflective surface located adjacent to the defined area may deflect one or more beams around an object in the defined area. In the worst case, an optical short circuit may occur, allowing an object to pass undetected through the defined area.
WARNING: · Do not install the system near reflective surfaces · Reflective surfaces could reflect the sensing beam(s) around an object or person within the defined area, preventing detection by the system. Failure to prevent reflection problems results in incomplete guarding and an optical short circuit that could result in serious injury or death. · Do not locate the defined area near a reflective surface. Perform the trip test, as described in the product documentation, to detect such reflection(s).
This reflective surface may result from shiny surfaces or glossy paint on the machine, the workpiece, the work surface, the floor, or the walls. Beams deflected by reflective surfaces are discovered by performing the trip test and the periodic checkout procedures. To eliminate problem reflections:
· If possible, relocate the sensors to move the beams away from the reflective surface(s) (see Figure 5 on page 20), being careful to maintain adequate Safety Distance (Minimum Distance)
· Otherwise, if possible, paint, mask, or roughen the shiny surface to reduce its reflectivity · Where these are not possible (as with a shiny workpiece or machine frame), determine the worst-case resolution (see
Figure 6 on page 20) resulting from the optical short circuit and use the corresponding depth penetration factor (Dpf or C) in the Safety Distance (Minimum Distance) formula (see Calculating the Safety Distance (Minimum Distance) on page 15); or mount the sensors in such a way that the receiver’s field of view and/or the emitter’s spread of light are restricted from the reflective surface · Repeat the trip test (see Trip Test under Initial Checkout Procedure on page 30) to verify these changes have eliminated the problem reflection(s). If the workpiece is especially reflective and comes close to the defined area, perform the trip test with the workpiece in place
Figure 5. Adjacent Reflective Surfaces

Emitter

Do not position reflective surfaces within the shaded area

Reflective Surface d

Receiver

d top view
Operating Range (R)

d side view
Reflective Surface

Operating range 0.1 m to 3 m (4 in to 10 ft): d = 0.13 m (5 in) Operating range > 3 m (>10 ft): d = 0.0437 × R (m or ft)
Figure 6. Determining Worst-Case Resolution With Larger Test Piece

Reflective Surface
If an optical short circuit exists due to a reflective adjacent surface, a test piece (represented by the dark gray circle) with the specified system resolution will not cause a blocked condition. In this situation, during the Trip Test, the Zone indicators and Status indicator will be green and the OSSDs will be on.

20

www.bannerengineering.com – Tel: + 1 888 373 6767

S4B Safety Light Curtain

To determine the worst-case resolution, select larger test pieces (represented by the light gray circle) and perform a Trip Test. The midpoint between the emitter and receiver may cause the most optical short circuits. The test piece that passes the Trip Test determines the worst-case resolution for this installation. Use the table below to calculate a new depth penetration factor Dpf or Factor “C”.

Test Piece Model

Resolution

Depth Penetration Factor for U.S. Applications

Factor “C” for European Applications

STP-13

14 mm

24 mm (1 in)

0 mm

STP-2

19 mm

41 mm (1.6 in)

40 mm (1.6 in)

STP-16

25 mm

61 mm (2.5 in)

88 mm (3.5 in)

STP-14

30 mm

78 mm (3.1 in)

128 mm (5 in)

STP-4

32 mm

85 mm (3.3 in)

144 mm (5.7 in)

STP-17

34 mm

92 mm (3.6 in)

160 mm (6.3 in)

STP-1

38 mm

106 mm (4.2 in)

192 mm (7.6 in)

STP-3

45 mm

129 mm (5 in)

850 mm (33.5 in)

STP-8

51 mm

150 mm (5.9 in)

850 mm (33.5 in)

STP-5

58 mm

173 mm (6.8 in)

850 mm (33.5 in)

STP-15

60 mm

180 mm (7 in)

850 mm (33.5 in)

STP-12

62 mm

187 mm (7.4 in)

850 mm (33.5 in)

5.6.2 Use of Corner Mirrors

S4B may be used with one or more corner mirrors. Mirrors are not allowed for applications that would allow undetected personnel access into the safeguarded area.
The use of glass-surface corner mirrors reduces the maximum specified emitter/receiver separation by approximately 8 percent per mirror, as follows:
Table 2: Light Screen Maximum Range

Light Screen Series

0 Mirrors

1 Mirror

2 Mirrors

3 Mirrors

4 Mirrors

SLC4 Safety Light Curtain EZ-SCREEN® LP Basic (SLPVA)

2 m (6.6 ft) 4 m (13 ft)

1.8 m (5.9 ft) 3.7 m (12.1 ft)

1.6 m (5.2 ft) 3.4 m (11.2 ft)

1.5 m (4.9 ft) 3.1 ft m (10.3 ft)

1.4 m (4.6 ft) 2.8 m (9.2 ft)

14 mm EZ-SCREEN® (SLS) EZ-SCREEN® LP (SLP) EZ-SCREEN® LS Basic (SLLV)

6 m (20 ft) 7 m (23 ft) 8 m (26.2 ft)

5.6 m (18.4 ft) 6.5 m (21.2 ft) 7.4 m (24.3 ft)

5.2 m (17.0 ft) 6.0 m (19.5 ft) 6.8 m (22.3 ft)

4.8 m (15.7 ft) 5.5 m (18.0 ft) 6.2 m (20.3 ft)

4.4 m (14.5 ft) 5.1 m (16.6 ft) 5.7 m (18.7 ft)

EZ-SCREEN® LS (SLL)

12 m (39 ft)

11 m (36 ft)

10.1 m (33 ft)

9.3 m (30.5 ft)

8.6 m (28 ft)

S4B Safety Light Curtain EZ-SCREEN® Type 2 (LS2)

12 m (39 ft) 15 m (50 ft)

11 m (36 ft) 13.8 m (45 ft)

10.1 m (33 ft) 12.7 m (42 ft)

9.3 m (30.5 ft) 11.7 m (38 ft)

8.6 m (28 ft) 10.8 m (35 ft)

30 mm EZ-SCREEN® (SLS)

18 m (60 ft)

16.8 m (55 ft)

15.5 m (51 ft)

14.3 m (47 ft)

13.1 m (43 ft)

See the specific mirror datasheet or www.bannerengineering.com for more information.
If mirrors are used, the difference between the angle of incidence from the emitter to the mirror and from the mirror to the receiver must be between 45° and 120°. If placed at a sharper angle, an object in the light screen may deflect beam(s) to the receiver, preventing the object from being detected, also know as false proxing. Angles greater than 120° result in difficult alignment and possible optical short circuits.

WARNING: · Retroreflective Mode Installation · Failure to follow these instructions may create unreliable sensing and may result in serious injury or death.
· Do not install emitters and receivers in retroreflective mode with less than a 45° angle of incidence. Install emitters and receivers at an appropriate angle.

www.bannerengineering.com – Tel: + 1 888 373 6767

21

S4B Safety Light Curtain

Figure 7. Using S4B sensors in a retroreflective mode

Emitter

Mirror

A
45º < A < 120º

A < 45º

Receiver

A > 120º

5.6.3 Emitter and Receiver Orientation
The emitter and receiver must be mounted parallel to each other and aligned in a common plane, with both machine interface cable ends pointing in the same direction. Never mount the emitter with its machine interface cable end oriented in the opposite direction of the cable end of the receiver. If this occurs, voids in the light screen may allow objects or personnel to pass through the defined area undetected. The emitter and receiver may be oriented in a vertical or horizontal plane, or at any angle between horizontal and vertical, as long as they are parallel to each other and their cable ends point in the same direction. Verify that the light screen completely covers all access to the hazard point that is not already protected by hard (fixed) guarding or other supplemental guarding.
WARNING: · Properly install system components · Incorrectly orienting the system components impairs the performance of the system and results in incomplete guarding, which can result in serious injury or death. · Install the system components with their corresponding cable ends pointing in the same direction.
Figure 8. Examples of Correct Emitter/Receiver Orientation
Receiver
Emitter

Both cable ends down

Receiver Emitter
Both cable ends up

Receiver
Emitter
Orientation parallel to floor with both cable ends pointing in the same direction

22

www.bannerengineering.com – Tel: + 1 888 373 6767

Figure 9. Examples of Incorrect Emitter/Receiver Orientation

Emitter

Receiver

S4B Safety Light Curtain
Emitter

Receiver

Cable ends point in opposite directions Problem: Voids in defined area

Emitter and receiver not parallel to each other Problem: Reduced excess gain

5.6.4 Installation of Multiple Systems

Whenever two or more S4B emitter and receiver pairs are adjacent to one another, optical crosstalk may take place between the systems.

To minimize optical crosstalk, alternate the positions of the emitters and receivers as shown in Figure 11 on page 24, or alternate scan codes.
When three or more systems are installed in the same plane, optical crosstalk may occur between sensor pairs whose emitter and receiver lenses are oriented in the same direction. In this situation, eliminate optical crosstalk by mounting these sensor pairs exactly in line with each other within one plane, or by adding a mechanical barrier between the pairs as shown in Figure 11 on page 24.

Figure 10. Optical Crosstalk

Emitter 2

Receiver 2

Emitter 1

Receiver 1

WARNING: · Adjacent components can synchronize incorrectly · The light curtain’s safety function is reduced when components are not synchronized correctly, creating an unsafe condition that could result in serious injury or death. · When multiple systems are mounted closely together, or where a secondary emitter is in view (within ±5°) and within range of an adjacent receiver, a receiver can synchronize to the signal from the wrong emitter, reducing the safety function of the light curtain.
To further aid in avoiding crosstalk, the sensors feature two selectable scan codes. A receiver set to one scan code will not respond to an emitter set to another code. The emitter and receiver within a system must be set to the same scan code.
Scan codes are set via the switches in the removable DES4E-… cordsets on the emitters and receivers. See Scan Code Selection on page 28 for the switch settings.

www.bannerengineering.com – Tel: + 1 888 373 6767

23

S4B Safety Light Curtain

Figure 11. Installation of Multiple Systems

Receiver

Scan Code 1

Emitter

Receiver

Scan Code 1
Emitter

Receiver

Scan Code 2
Emitter

Emitter

Scan Code 2

Receiver

Two systems in a horizontal plane

Emitter

Scan Code 1

Receiver

Scan Code 2

Two or three systems stacked (or alternate receiver/emitter positions)

Receiver 3

Scan Code 2
Emitter 3

Opaque Shield

Emitter 2

Scan Code 2
Receiver 2 Receiver 1

Scan Code 1

Emitter 1

Horizontal Receiver

Horizontal Emitter

Two systems at right angles

Multiple systems

WARNING: · Properly connect multiple pairs of sensors · Connecting multiple output signal switching devices (OSSD) safety outputs to one interface module or otherwise parallel OSSD outputs can result in serious bodily injury or death, and is prohibited.
· Do not connect multiple pairs of sensors to a single device.

5.7 Mounting System Components
5.7.1 Mounting Hardware
After the mechanical layout considerations are addressed, mount the sensors and route the cables. All brackets are ordered separately; no brackets are shipped with the sensors. The quantity of brackets ordered and the placement of those brackets must ensure the unsupported distance (distance between brackets) is less than 900 mm (35.4 in).

24

www.bannerengineering.com – Tel: + 1 888 373 6767

S4B Safety Light Curtain

Mounting the S4BA-MBK-16 Side-Mount Bracket

The S4BA-MBK-16 brackets are ordered separately. Two brackets are included in each kit.

Figure 12. Side-Mount Bracket

· See Sensor Mounting and Mechanical Alignment Verification on page 26 for additional mounting recommendations
· The machine interface connector ends of both sensors must point in the same direction
· The sensors are designed to be mounted with up to 900 mm (35.4 in) of unsupported distance between brackets when they are subject to shock or vibration

Note: Note: It is best to place brackets near the ends of each sensor (not on end caps). Add additional brackets per sensor as needed to meet 900 mm unsupported distance requirement. This means that 300 mm to 900 mm sensors can use two brackets per sensor, while 1050 mm to 1800 mm sensors should use three brackets per sensor.
· See Brackets on page 47 for mounting bracket dimensions
· The M4 bolts, washers, and nuts are user-supplied

Note: Use washers under the screw heads to minimize bracket damage.

1. From a common point of reference (ensuring the calculated minimum safety distance), measure to position the emitter and receiver in the same plane, with their midpoints directly opposite each other.
The connector ends of both sensors must point in the same direction (see Emitter and Receiver Orientation on page 22). 2. Mount the emitter and receiver side brackets to the desired surface with user-supplied M4 bolts, washers, and nuts. Tighten to 2.15 N·m (19 in·lbs). 3. Loosen the M4 clamp screws on the side brackets enough to easily insert a sensor. 4. Insert each sensor in to its respective brackets with the front window facing out of the opening in the front of the bracket.
Note: The sensors need to lightly snap into the brackets. If the sensors will not install easily, loosen the M4 clamp screws to allow the clamps to slide out of the way of the sensor.
5. Position the emitter and receiver windows directly facing each other. 6. Measure from a reference plane, for example, a level building floor, to the same point(s) on the emitter and receiver
to verify their mechanical alignment. Use a carpenter’s level, a plumb bob, or the optional LAT-1 Laser Alignment Tool (see Alignment Aids on page 50) or check the diagonal distances between the sensors, to achieve mechanical alignment. See Sensor Mounting and Mechanical Alignment Verification on page 26. 7. Temporarily tighten all fasteners that allow for adjustment. Final alignment procedures are explained in Initial Checkout Procedure on page 30. 8. After the emitter and receiver alignment is completed, tighten the bracket front M4 clamp screws to 2.15 N·m (19 in·lbs).
Note: Each bracket has two clamp screws. Both clamp screws on every bracket need to be fully tightened to provide sufficient strength to hold the sensor. Do not reposition the sensor when the clamps are mostly or fully tightened. Doing so could damage clamp pads.

www.bannerengineering.com – Tel: + 1 888 373 6767

25

S4B Safety Light Curtain

5.7.2 Sensor Mounting and Mechanical Alignment Verification

Verify that: · The emitter and receiver are directly opposite each other
· Nothing is interrupting the defined area
· The defined area is the same distance from a common reference plane for each sensor
· The emitter and receiver are in the same plane and are level/plumb and square to each other (vertical, horizontal, or inclined at the same angle, and not tilted front-to-back or side-to-side)

Figure 13. Incorrect Sensor Alignment

Emitter

Receiver

A

B

X

X

YZ Level Surface

YZ

X

X

Level Surface

Angled or Horizontal Installations ­ verify that: · Distance X at the emitter and receiver are equal
· Distance Y at the emitter and receiver are equal
· Distance Z at the emitter and receiver are equal from parallel surfaces
· Vertical face (the window) is level/plumb
· Defined area is square. Check diagonal measurements if possible; see Vertical Installations, on the right.

Vertical Installations ­ verify that: · Distance X at the emitter and receiver are equal
· Both sensors are level/plumb (check both the side and face)
· Defined area is square. Check diagonal measurements if possible (Diagonal A = Diagonal B).

26

www.bannerengineering.com – Tel: + 1 888 373 6767

5.7.3 Mounting Dimensions and Defined Area

All measurements are listed in millimeters [inches], unless noted otherwise.

38.0 [1.50]

39.6 [1.56]

48.7 [1.92] 38.2 [1.50]

17.5 – 20.3 [0.69 – 0.8]

32.5 [1.28] Last Beam

4X 8.5 [0.33] Position brackets so that the unsupported length is less than 900 mm

4X 7.5 [0.30] 25.0 [0.98]

L1

42.3 [1.67]

18.9 [0.74] 5-pin Male Euro Quick Disconnect

First Beam

Emitter/Receiver Model S4Bx30-300-S S4Bx30-450-S S4Bx30-600-S S4Bx30-750-S S4Bx30-900-S S4Bx30-1050-S S4Bx30-1200-S S4Bx30-1350-S S4Bx30-1500-S S4Bx30-1650-S S4Bx30-1800-S

8X 4.5 [0.18] 4X 25.0 [0.98]

2X 42.0 [1.65]

2X 68.2 [2.68] Mounting Bracket Dimensions
Housing Length (L1) 312.03 mm (12.28 in) 460.73 mm (18.14 in) 609.98 mm (24.01 in) 758.68 mm (29.87 in) 907.93 mm (35.75 in) 1056.63 mm (41.6 in) 1205.88 mm (47.48 in) 1354.58 mm (53.33 in) 1503.83 mm (59.21 in) 1652.53 mm (65.06 in) 1801.78 mm (70.94 in)

S4B Safety Light Curtain
Defined Area (mm) 300 450 600 750 900 1050 1200 1350 1500 1650 1800

www.bannerengineering.com – Tel: + 1 888 373 6767

27

S4B Safety Light Curtain
6 Electrical Installation and Testing
The following are the main steps to electrically install the S4B components and interface with the guarded machine.
WARNING: · Read this Section Carefully Before Installing the System · Failure to follow these instructions could result in serious injury or death. · If all mounting, installation, interfacing, and checkout procedures are not followed properly, this Banner device cannot provide the protection for which it was designed. · The user is responsible for ensuring that all local, state, and national laws, rules, codes, or regulations relating to the installation and use of this control system in any particular application are satisfied. Ensure that all legal requirements have been met and that all technical installation and maintenance instructions contained in this manual are followed. · The user has the sole responsibility to ensure that this Banner device is installed and interfaced to the guarded machine by Qualified Persons, in accordance with this manual and applicable safety regulations. A Qualified person is a person who, by possession of a recognized degree or certificate of professional training, or who, by extensive knowledge, training and experience, has successfully demonstrated the ability to solve problems relating to the subject matter and work.
1. Routing cordsets and making initial electrical connections (see Routing Cordsets on page 28 and Initial Electrical Connections on page 30).
2. Apply power to each emitter/receiver pair (see Initial Electrical Connections on page 30). 3. Perform an Initial Checkout Procedure (see Initial Checkout Procedure on page 30). 4. Make all electrical interface connections to the guarded machine (see Electrical Connections to the Guarded Machine
on page 34). 5. Perform a commissioning checkout procedure (see Commissioning Checkout on page 36).

6.1 Routing Cordsets

Attach the required cordsets to the sensors, and route the sensor cables to the junction box, electrical panel, or other enclosure in which the other safety-related parts of the control system are located. This must be done per local wiring code for low-voltage dc control cables and may require installation of electrical conduit.
See Accessories on page 47 for selection of Banner supplied cables.
The S4B is designed and manufactured to be highly resistant to electrical noise and to operate reliably in industrial settings. However, extreme electrical noise may cause a random Trip condition; in extreme cases, a Lockout is possible.
Emitter and receiver wiring is low voltage; routing the sensor wires alongside power wires, motor/servo wires, or other high voltage wiring may inject noise into the S4B System. It is good wiring practice, and sometimes may be required by code, to isolate emitter and receiver cables from high-voltage wires and to avoid routing cables close to sources of noise.
Sensor cabling and any interconnect wiring should have an insulation temperature rating of at least 90 °C (194 °F).
Table 3: Maximum machine interface cable length versus total load current (OSSDs)

0.1 A

0.25 A

Maximum Machine Interface Cordset Length Total Load Current (OSSD 1 + OSSD 2) 0.5 A

0.75 A

1.0 A

95.7 m (314 ft)

78 m (256 ft)

54.9 m (180 ft)

42.1 m (138 ft)

34.1 m (112 ft)

Note: Emitter and receiver power (current) requirements are accounted for. The above values represent additional current draw that must be accounted for.

Note: Maximum cordset lengths are intended to ensure that adequate power is available to the S4B when the supply is operating at +20 V DC. Values in the previous table are worse case. Contact Banner Engineering if there are any questions.

6.2 Scan Code Selection
The emitter and receiver may be configured to one of two Scan Codes (1 or 2).
A receiver recognizes light only from an emitter with the same scan code. Both the emitter and its corresponding receiver must have the same scan code setting. The scan code must be configured with power off because the DES4E-.. RD to M12 cordset assemblies must be removed from the units.

28

www.bannerengineering.com – Tel: + 1 888 373 6767

S4B Safety Light Curtain The default scan code setting is scan code 1. To change the scan code setting, use the following instructions.
1. Remove the DES4E-51D cordset from the sensor by loosening the two screws (#1 Phillips drive). Note: The screws are captive screws and should not be removed from the cordset assembly.
Figure 14. Remove the Cordset
2. Flip the cordset over to see the two switches.
Figure 15. Scan Code Switches
Scan Code 1: Both switches in the left position Scan Code 2: Both switches in the right position (as shown) 3. Position the cordset onto the sensor. 4. Hand tighten the two screws.

www.bannerengineering.com – Tel: + 1 888 373 6767

29

S4B Safety Light Curtain

6.3 Initial Electrical Connections
WARNING: · Risk of electric shock · Use extreme caution to avoid electrical shock. Serious injury or death could result. · Always disconnect power from the safety system (for example, device, module, interfacing, etc.), guarded machine, and/or the machine being controlled before making any connections or replacing any component. Lockout/tagout procedures might be required. Refer to OSHA 29CFR1910.147, ANSI Z244-1, or the applicable standard for controlling hazardous energy. · Make no more connections to the device or system than are described in this manual. Electrical installation and wiring must be made by a Qualified Person 4 and must comply with the applicable electrical standards and wiring codes, such as the NEC (National Electrical Code), NFPA 79, or IEC 60204-1, and all applicable local standards and codes.
Lockout/tagout procedures may be required (refer to OSHA1910.147, ANSI Z244-1, ISO 14118, or the appropriate standard for controlling hazardous energy). Make the electrical connections in the order described in this section. Do not remove end-caps; no internal connections are to be made. All connections are made through the DES4E-51D connection.
Emitter Cordset S4B emitters require a mating 5-pin cordset, but not all conductors are used. The other wires are in place to allow a parallel connection (color-for-color) to the receiver cable, providing sensor interchangeability (or “swapability”); either sensor may be installed at either cordset connection. In addition to providing similar cabling, this wiring scheme is advantageous during installation, wiring, and troubleshooting.
Receiver Cordset Do not connect any wires to the machine control circuits (OSSD outputs) at this time.

6.4 Initial Checkout Procedure
The initial checkout procedure must be performed by a Qualified Person. It must be performed only after configuring the System and after connecting the components. Perform this procedure to:
· Ensure proper installation when the System is first installed · Ensure proper System function whenever any maintenance or modification is performed on the System or on the
machinery that is guarded by the System.
6.4.1 Configuring the System for Initial Checkout
For the initial checkout, the S4B System must be checked without power available to the guarded machine. Final interface connections to the guarded machine cannot take place until the light screen system has been checked out. This may require lockout/tagout procedures (refer to OSHA1910.147, ANSI Z244-1, ISO 14118, or the appropriate standard for controlling hazardous energy). The OSSD connections will be made after the initial checkout procedure has been successfully completed. Verify that:
· Power has been removed from (or is not available to) the guarded machine and its controls or actuators · The machine control circuit or the Safety/Interface Module is not connected to the OSSD outputs at this time
(permanent connections will be made later)
6.4.2 Apply Initial Power to the S4B System
1. Inspect the area near the light screen for reflective surfaces, including work pieces and the guarded machine. Reflective surfaces may cause light beams to reflect around a person in the light screen, preventing the person from being detected and not stopping the machine motion (see Adjacent Reflective Surfaces on page 20).
2. Eliminate the reflective surfaces as much possible by relocating, painting, masking, or roughening them. Remaining problem reflections will become apparent during the trip test.
4 A person who, by possession of a recognized degree or certificate of professional training, or who, by extensive knowledge, training and experience, has successfully demonstrated the ability to solve problems relating to the subject matter and work.

30

www.bannerengineering.com – Tel: + 1 888 373 6767

S4B Safety Light Curtain
3. Verify that power is removed from the S4B System and from the guarded machine and that the OSSD safety outputs are not connected.
4. Remove all obstructions from the light screen. 5. With the power to the guarded machine off, connect +24 V DC (brown wire) and 0 V DC (blue wire) on both the
emitter and receiver cables to a SELV-rated power supply (see Wiring Diagrams on page 38). 6. Power up the S4B System only. 7. Verify that the input power is present to both the emitter and the receiver. At least one indicator on both the emitter
and the receiver should be on and the start-up sequence should cycle. 8. Watch both the emitter and the receiver Status indicators and the receiver Zone indicators to determine the light
screen alignment status. · Emitter Lockout Condition–the emitter’s red Status indicator is single-flashing and the receiver’s red Status
indicator is on. Proceed to Troubleshooting on page 42 for diagnostic information. · Receiver Lockout Condition –the receiver Status indicator is single-flashing red. Proceed to Troubleshooting
on page 42 for diagnostic information. · Normal Operating Mode (emitter)–The green Status indicator is on. · Clear (Run) Condition (receiver)–The green Status indicator is on. All green Zone indicators are on. · A Blocked Condition (receiver)–The red Status indicator is on and one or more red Zone indicator(s) are on,
identifying the location of the blocked beams. Proceed to Optically Align the System Components on page 31.
Note: If beam 1 is blocked, Zone indicator 1 is red and all others are off. Beam 1 provides the synchronization signal.
See Operating Features on page 10 for indicator and display information.
6.4.3 Optically Align the System Components
To verify the optimal alignment, adjust the sensor rotation with the power on and follow these steps.
WARNING: · Hazard exposure · Failure to follow these instructions could result in serious injury or death. · Verify that no individuals are exposed to any hazard if the output signal switching device (OSSD) outputs turn on when the emitter and receiver become aligned.
Before beginning, verify the sensor mounting. 1. Verify that the emitter and the receiver are pointed squarely at each other. The sensor face must be perpendicular to the optical axis.

If the Channel #1 beam is not aligned, the Status and Zone 1 indicators are red and Zone indicators 2­3 are off.
2. If the green Status indicator is on, go to the next step. If not, rotate each sensor (one at a time) left and right until the green Status indicator is on. (As the sensor rotates out of alignment, the red Status indicator turns on). As more beams are aligned, the Zone indicators turn from red to green.

3. Optimize alignment and maximize excess gain.

www.bannerengineering.com – Tel: + 1 888 373 6767

31

S4B Safety Light Curtain

a) Slightly loosen the sensor mounting screws. b) Rotate one sensor left and right, noting the positions in each arc where the Status indicators turn red (Blocked
condition) or a zone indicator turns yellow (weak beam strength); repeat with the other sensor. c) Center each sensor between those two positions. d) Tighten the mounting screws, making sure to maintain the positioning as the screws are tightened. If at any time the red Status indicator begins to flash, the System has entered a Lockout condition. See Troubleshooting on page 42 for further information.
Flashing
6.4.4 Optical Alignment Procedure with Mirrors
S4B sensors may be used with one or more corner mirrors for guarding more than one side of an area. The MSM-… and SSM-… rear-surface glass mirrors are rated at 85% efficiency. Thus, excess gain and sensing range are reduced when using mirrors; see Use of Corner Mirrors, under Mechanical Installation Considerations on page 15. During any adjustments, allow only one individual to adjust any one item at any one time. In addition to the standard optical alignment procedure, verify:
1. The emitter, receiver, and all mirrors are level and plumb. 2. The middle of the defined area and the center point of the mirrors are approximately the same distance from a
common reference point, such as the same height above a level floor. 3. There are equal amounts of mirror surface above and below the defined area such that the optical beams are not
passing below or above the mirror.
Figure 16. Corner Mirror Alignment
Component 2 (Mirror)
Component 3 (Mirror)

Component 1 (Emitter)

Component 4 (Receiver)

6.4.5 Conduct a Trip Test
After optimizing the optical alignment and configuring fixed blanking and/or reduced resolution (if applicable), perform a trip test to verify the detection capability of the S4B System.
This test also verifies correct sensor orientation, identifies optical short circuits, and verifies the expected resolution for applications using reduced resolution. After the installation has passed the trip test, the safety outputs may be connected and the commissioning checkout may be performed (initial installations only).

32

www.bannerengineering.com – Tel: + 1 888 373 6767

S4B Safety Light Curtain

1. Select the proper test piece, ordered separately.
For 30 mm resolution models: use the 30 mm (0.94 in ) diameter model STP-14. 2. Verify that the System is in run mode, the green Status indicator is on, and all Zone indicators are green. 3. Pass the specified test piece through the defined area in three paths: near the emitter, near the receiver, and midway
between the emitter and receiver.

1

4

1 = Receiver 2 = Emitter 3 = Defined area 4 = Specified test piece 5 = Location of the status indicators

2

3

5

4. During each pass, while the test piece is interrupting the defined area, at least one Zone indicator must be red. The red Zone indicator must change with the position of the test piece within the defined area. The Status indicator must turn red and remain red for as long as the test piece remains in the defined area. If not, the installation has failed the trip test.
If all Zone indicators turn green or fail to follow the position of the test piece while it is within the defined area, the installation has failed the trip test. Check for correct sensor orientation or reflective surfaces. Do not continue until the situation is corrected.
When the test piece is removed from the defined area, the green Status indicator must turn on.
WARNING: · Trip test failure · Using a system that has failed a trip test can result in serious bodily injury or death. If the trip test has failed, the system might not stop dangerous machine motion when a person or object enters the sensing field. · Do not attempt to use the system if the system does not respond properly to the trip test.
5. If mirrors are used in the application: Test the defined area on each leg of the sensing path (for example, emitter to mirror, between mirror and receiver).

Emitter

Test Piece

Receiver

Mirror

www.bannerengineering.com – Tel: + 1 888 373 6767

33

S4B Safety Light Curtain
6. If the S4B System passes all checks during the trip test, go on to Electrical Connections to the Guarded Machine on page 34.
6.5 Electrical Connections to the Guarded Machine
Verify that power has been removed from the S4B and the guarded machine. Make the permanent electrical connections as required by each individual application. Lockout/tagout procedures may be required (refer to OSHA 1910.147, ANSI Z244-1, ISO 14118, or the appropriate standard for controlling hazardous energy). Follow relevant electrical standards and wiring codes, such as the NEC, NFPA79 or IEC 60204-1. Supply power should already be connected. The S4B must also have been aligned and passed the Initial Checkout, as described in Initial Checkout Procedure on page 30. The final connections to be made or verified are:
· OSSD outputs
WARNING: · Risk of electric shock · Failure to follow these instructions could result in serious injury or death. · Disconnect or turn off power before installing, removing, or servicing the device. · Install and connect the device in accordance with the National Electrical Code (NEC) and any applicable local code requirements and supply the device with an appropriate fuse box or circuit breaker (see Specifications).
6.5.1 Protective Stop (Safety Stop) Circuits
A protective stop (safety stop) allows for an orderly cessation of motion for safeguarding purposes, which results in a stop of motion and removal of power from the Machine Primary Control Elements (MPCE) (assuming this does not create additional hazards). A protective stop circuit typically comprises a minimum of two normally open contacts from forced-guided, mechanically linked relays, which are monitored through External Device Monitoring (EDM) to detect certain failures, to prevent the loss of the safety function. Such a circuit can be described as a “safe switching point”. Typically, protective stop circuits are either single channel, which is a series connection of at least two normally open contacts; or dual-channel, which is a separate connection of two normally open contacts. In either method, the safety function relies on the use of redundant contacts to control a single hazard. If one contact fails ON, the second contact arrests the hazards and prevents the next cycle from occurring. The interfacing of the protective stop circuits must be accomplished so that the safety function cannot be suspended, overridden, or defeated, unless accomplished in a manner of the same or greater degree of safety as the machine’s safety related control system that includes the S4B. A Banner XS26-2 Safety Controller with XS1ro or XS2ro Relay Expansion Module, Banner SC10-2roe Safety Controller, or Banner UM-FA-xA Universal Safety Module provides a series connection of redundant contacts that form protective stop circuits for use in either single-channel or dual-channel control.
Output Signal Switching Devices (OSSDs) and External Device Monitoring (EDM)
The S4B is able to detect faults on OSSD1 and OSSD2. These faults include short circuits to +24 V DC and 0 V, and between OSSD1 and OSSD2. Both Output Signal Switching Device (OSSD) outputs must be connected to the machine control so that the machine’s safety-related control system interrupts the circuit or power to the Machine Primary Control Element(s) (MPCE), resulting in a non-hazardous condition. Final Switching Devices (FSDs) typically accomplish this when the OSSDs go to an OFF state. Refer to the output specifications in the Receiver Specifications and these warnings before making OSSD output connections and interfacing the S4B to the machine.

34

www.bannerengineering.com – Tel: + 1 888 373 6767

S4B Safety Light Curtain

WARNING:
· Interfacing both output signal switching devices (OSSD)
· Failure to follow these instructions could result in serious injury or death.
· Unless the same degree of safety is maintained, never wire an intermediate device(s) (PLC, PES, PC) between the safety module outputs and the master stop control element it switches such that a failure causes a loss of the safety stop command or the failure allows the safety function to be suspended, overridden, or defeated.
· Connect both OSSD outputs to the machine control so that the machine’s safety-related control system interrupts the circuit to the machine primary control element(s), resulting in a nonhazardous condition.

WARNING: · OSSD Interfacing · Failure to properly interface the OSSD Outputs to the guarded machine could result in serious injury or death. · To ensure proper operation, the Banner device output parameters and machine input parameters must be considered when interfacing the Banner device OSSD outputs to machine inputs. Design machine control circuitry so that all of the following are true:
The maximum load resistance value is not exceeded.
The maximum specified OSSD OFF-state voltage does not result in an ON condition.

External device monitoring (EDM) is a function used to monitor the state of the external, positively guided (mechanically linked) machine control contacts (FSDs and/or MPCEs). The S4B System does not include the EDM function. As a result, the S4B System should be used with an external safety monitoring device that monitors the status of the two S4B OSSDs and is capable of providing the EDM function. Examples of appropriate external safety monitoring devices include Banner XS/SC26 Safety Controllers, SC10-2roe Safety Controller, Banner UM-FA-9A and UM-FA-11A Universal Input Safety Modules, and Safety PLCs.

Light Curtain
OSSD1 OSSD2

+24 V dc

Light Curtain
OSSD1 OSSD2

Safety Controller
SO1
MPCE1 MPCE2

EDM MPCE 1
MPCE 2

Safety Controller
SO1
MPCE 1 MPCE 2

EDM EDM

MPCE1

MPCE2

+24 V dc

Single-channel EDM used to monitor both MPCE feedback signals. If one or both channels do not close, the system enters a Lockout condition.

Dual-channel EDM used to monitor both MPCE feedback signals. If the channels are not in the same state, the system enters a Lockout condition.

WARNING: · The S4B does not have external device monitoring (EDM). · If EDM is required for the application, it must be implemented in the external control.

6.5.2 Preparing for System Operation
After the initial trip test has been accomplished, and the OSSD safety outputs connections have been made to the external control device, the S4B is ready for testing in combination with the guarded machine.
The operation of the S4B with the guarded machine must be verified before the combined System and machine may be put into service. To do this, a Qualified Person must perform the Commissioning Checkout Procedure. See Commissioning Checkout on page 36.

www.bannerengineering.com – Tel: + 1 888 373 6767

35

S4B Safety Light Curtain

6.5.3 Sensor Interchangeability
The figures and table below illustrate a wiring option that provides sensor interchangeability (or swapability)–the ability to install either sensor at either QD connection.
The resulting installation provides the ability to swap the emitter and receiver position. This wiring option provides advantages during installation, wiring, and troubleshooting.
To use this option, connect all emitter wires in parallel (color-for-color) to the receiver cable via individual wires or the CSB.. splitter cordset.
Model CSB.. splitter cordsets and DEE2R.. double-ended cordsets allow easy interconnection between an S4B receiver and emitter, providing a single homerun cordset.

Figure 17. Individual Cordsets

Figure 18. Splitter Cordsets

Emitter

5-Wire Cordsets

Receiver

Emitter

Splitter Cordsets

Receiver

MQDC1-5… Cordsets

Brown White Black Blue Gray

+24V dc
OSSD2
OSSD1
0V dc Receiver Weak Beam Strength Signal

DEE2R..

DEE2R..

CSB.. Splitter Cordset

6.5.4 Commissioning Checkout
Perform this checkout procedure as part of the System installation after the System has been interfaced to the guarded machine, or whenever changes are made to the System (either a new configuration of the S4B or changes to the machine).

WARNING: · Do not use the system until the checkouts are verified · Attempts to use the guarded/controlled machine before these checks are verified could result in serious injury or death. · If all these checks cannot be verified, do not attempt to use the safety system that includes the Banner device and the guarded/controlled machine until the defect or problem has been corrected.
A Qualified Person must perform the procedure. Checkout results should be recorded and kept on or near the guarded machine as required by applicable standards.
To prepare the System for this checkout:
1. Examine the guarded machine to verify that it is of a type and design compatible with the S4B System. See Examples: Inappropriate Applications on page 10 for a list of misapplications.
2. Verify that the S4B is configured for the intended application.

36

www.bannerengineering.com – Tel: + 1 888 373 6767

S4B Safety Light Curtain
3. Verify that the safety distance (minimum distance) from the closest danger point of the guarded machine to the defined area is not less than the calculated distance, per Calculating the Safety Distance (Minimum Distance) on page 15.
4. Verify that: a) Access to any dangerous parts of the guarded machine is not possible from any direction not protected by the S4B System, hard (fixed) guarding, or supplemental safeguarding, and b) It is not possible for a person to stand between the defined area and the dangerous parts of the machine, or c) Supplemental safeguarding and hard (fixed) guarding, as described by the appropriate safety standards, are in place and functioning properly in any space (between the defined area and any hazard) which is large enough to allow a person to stand undetected by the S4B.
5. If used, verify that all reset switches are mounted outside and in full view of the guarded area, out of reach of anyone inside the guarded area, and that means of preventing inadvertent use is in place.
6. Examine the electrical wiring connections between the S4B OSSD outputs and the guarded machine’s control elements to verify that the wiring meets the requirements stated in Electrical Connections to the Guarded Machine on page 34.
7. Inspect the area near the defined area (including work pieces and the guarded machine) for reflective surfaces (see Adjacent Reflective Surfaces on page 20). Remove the reflective surfaces, if possible, by relocating them, painting, masking or roughening them. Remaining problem reflections will become apparent during the Trip Test.
8. Verify that power to the guarded machine is off. Remove all obstructions from the defined area. Apply power to the S4B System.
9. Observe the Status indicators and Diagnostic Display: · Lockout: Red Status flashing; all others off · Blocked: Red Status on; one or more red Zone indicators on · Clear: Green Status on; all green Zone indicators on
10. A Blocked condition indicates that one or more of the beams is misaligned or interrupted. See Optically Align the System Components on page 31 to correct this situation.
11. After the green Status indicator is on, perform the trip test (Conduct a Trip Test on page 32) on each sensing field to verify proper System operation and to detect possible optical short circuits or reflection problems. Do not continue until the S4B passes the trip test.
Important: Do not expose any individual to any hazard during the following checks.
WARNING: · Clear the guarded area before applying power or resetting the system · Failure to clear the guarded area before applying power could result in serious injury or death. · Verify that the guarded area is clear of personnel and any unwanted materials before applying power to the guarded machine or before resetting the system.
12. Apply power to the guarded machine and verify that the machine does not start up. 13. Interrupt (block) the defined area with the test piece and verify it is not possible for the guarded machine to be put into
motion while the beam(s) is blocked. 14. Initiate machine motion of the guarded machine and, while it is moving, use the test piece to block the defined area.
Do not attempt to insert the test piece into the dangerous parts of the machine. Upon blocking any beam, the dangerous parts of the machine must come to a stop with no apparent delay. 15. Remove the test piece from the beam; verify that the machine does not automatically restart, and that the initiation devices must be engaged to restart the machine. 16. Remove electrical power to the S4B. Both OSSD outputs should immediately turn Off, and the machine must not be capable of starting until power is re-applied to the S4B. 17. Test the machine stopping response time, using an instrument designed for that purpose, to verify that it is the same or less than the overall system response time specified by the machine manufacturer.
Do not continue operation until the entire checkout procedure is complete and all problems are corrected.

www.bannerengineering.com – Tel: + 1 888 373 6767

37

S4B Safety Light Curtain

6.6 Wiring Diagrams
6.6.1 Generic Emitter Wiring Diagram
Figure 19. Generic Emitter Wiring Diagram

5-pin male Euro-Style

+24 V dc 0 V dc Pin #1 Pin #4
n.c. Pin #3 Pin #2
n.c.

  • All pins shown as no connection (n.c.) are either not connected or are paralleled to same color wire from the receiver cable.

Pin

Color

Mating MQDC1-5.. Cordset Pinout Emitter Function

M12 Connector (female face view)

1

Brown

2

White

3

Blue

4

Black

+ 24 V DC no connection 0 V DC no connection

2 1

3

4

5

5

Gray

no connection

38

www.bannerengineering.com – Tel: + 1 888 373 6767

S4B Safety Light Curtain

6.6.2 Generic Receiver Wiring Diagram–Self-checking Safety Module, Safety Controller, Safety PLC
Generic wiring for a self-checking Safety module, Safety Controller, or Safety PLC (no monitoring, automatic reset).
Figure 20. Generic Receiver Wiring Diagram–Self-checking Safety Module, Safety Controller, Safety PLC

Pin #1

+24Vdc 0Vdc

5-pin male Euro-Style

Pin #5 *
Pin #3 Pin #4 Pin #2

XS/SC26-2xx
+24Vdc 0Vdc

SO1a (SO1 not split)
SO1b

IN1

IN2

EDM

Single-Channel Safety Stop Circuit

Dual-Channel Safety Stop Circuit

Pin

Color

1

Brown

2

White

3

Blue

4

Black

5

Gray

Mating MQDC1-5.. Cordset Pinout Receiver Function + 24 V DC OSSD2 0 V DC OSSD1
Weak beam strength

FSD1 FSD2

M12 Connector (female face view)

2 1

3

4

5

www.bannerengineering.com – Tel: + 1 888 373 6767

39

S4B Safety Light Curtain
7 System Operation
7.1 Security Protocol
Certain procedures for installing, maintaining, and operating the S4B must be performed by either Designated Persons or Qualified Persons. A Designated Person is identified and designated in writing, by the employer, as being appropriately trained and qualified to perform system resets and the specified checkout procedures on the S4B. The Designated Person is empowered to:
· Perform manual resets and hold possession of the reset key · Perform the Daily Checkout Procedure A Qualified Person, by possession of a recognized degree or certificate of professional training, or by extensive knowledge, training, and experience, has successfully demonstrated the ability to solve problems relating to the installation of the S4B System and its integration with the guarded machine. In addition to everything for which the Designated Person is empowered, the Qualified Person is empowered to: · Install the S4B System · Perform all checkout procedures · Make changes to the internal configuration settings · Reset the System following a Lockout condition
7.2 Normal Operation

7.2.1 System Power-Up
When power is applied, each sensor conducts self-tests to detect critical internal faults, determine configuration settings, and prepare the S4B for operation. If either sensor detects a critical fault, scanning ceases, the receiver outputs remain Off and diagnostic information displays. If no faults are detected, the S4B automatically enters Alignment mode, and the receiver looks for an optical sync pattern from the emitter. If the receiver is aligned and receives the proper sync pattern, it enters Run mode and begins scanning to determine the blocked or clear status of each beam. No manual reset operation is required.
7.2.2 Run Mode
If any beams become blocked while the S4B is running, the receiver outputs turn Off within the stated S4B response time (see Specifications on page 13). If all the beams then become clear, the receiver outputs come back On. No resets are needed. All required machine control resets are provided by the machine control circuit. Internal Faults (Lockouts): If either sensor detects a critical fault, scanning ceases, the receiver outputs turn Off and diagnostic information displays. See Troubleshooting on page 42 for resolution of error/fault conditions.
7.2.3 Emitter Indicators
A single Status indicator shows whether power is applied, and whether the emitter is in Run mode or a Lockout condition. Two Scan Code indicators show the scan code assigned to the emitter.

Emitter Operating Status Power-up
Run Mode Lockout

Status Indicator Red on for several seconds
Green Flashing Red

Scan Code Indicator
Two LEDs red on, then flash green, then yellow on for 10 seconds to indicate scan code:
· One yellow LED = Scan Code 1 · Two yellow LEDs = Scan Code 2
Off
Off

40

www.bannerengineering.com – Tel: + 1 888 373 6767

S4B Safety Light Curtain

7.2.4 Receiver Indicators

A single Status indicator shows when the OSSD outputs are on (green) or off (red), or the System is in a Lockout condition (flashing red).
Zone indicators show whether a section of the defined area is aligned and clear, is blocked and/or misaligned, or is a section that has a channel with a weak beam strength. All models have three Zone indicators, each of which indicates Blocked/Clear/ Weak Beam Strength conditions for approximately 1/3 of the total light screen.

Operating Mode

Status Indicator

Zone Indicators 5

OSSD Outputs

Power up

Three LEDs red on, then flash

green, then yellow for 10 seconds to

Red on for several seconds, then green on for 1 second

indicate scan code. · Zone 2 only = Scan Code 1

Off

· Zone 2 and Zone 3 = Scan

Code 2

Alignment mode – beam 1 blocked

Red

Zone 1 red, others off

Off

Alignment mode – beam 1 clear

Red

Red or green

Off

Run mode – clear

Green

All on green

On

Run Mode – clear with weak beam strength

Green

Green or yellow

On

Run mode – blocked

Red

Red or green

Off

Lockout

· Zone 1 = Output Error

OR

Flashing red

· Zone 3 = Receiver Error

Off

See Receiver Error Codes on page 42 for more information.

7.3 Periodic Checkout Requirements
To ensure continued reliable operation, the System must be checked out periodically. Banner Engineering highly recommends performing the System checkouts as described below. However, a Qualified Person should evaluate these recommendations, based on the specific application and the results of a machine risk assessment, to determine the appropriate content and frequency of checkouts.
At every shift change, power-up, and machine setup change, the Daily Checkout should be performed; this checkout may be performed by a Designated or Qualified Person.
Semi-annually, the System and its interface to the guarded machine should be thoroughly checked out; this checkout must be performed by a Qualified Person (see Schedule of Checkouts on page 44). A copy of these test results should be posted on or near the machine.
Whenever changes are made to the System (either a new configuration of the S4B System or changes to the machine), perform the Commissioning Checkout (see Commissioning Checkout on page 36).
Note: Verify Proper Operation
The S4B can operate as it is designed only if it and the guarded machine are operating properly, both separately and together. It is the user’s responsibility to verify this, on a regular basis, as instructed in Schedule of Checkouts on page 44. Failure to correct such problems can result in an increased risk of harm.
Before the System is put back into service, verify that the S4B System and the guarded machine perform exactly as outlined in the checkout procedures and any problem(s) are found and corrected.

5 If beam 1 is blocked, Zone indicators 2­3 will be Off, because beam 1 provides the synchronization signal for all the beams.

www.bannerengineering.com – Tel: + 1 888 373 6767

41

S4B Safety Light Curtain
8 Troubleshooting

8.1 Lockout Conditions

A Lockout condition causes both S4B OSSD outputs to turn off or remain off, sending a stop signal to the guarded machine. Each sensor provides diagnostic error codes to identify the cause(s) of lockouts (see Troubleshooting on page 42). The following tables indicate a sensor lockout condition:

Emitter Lockout Conditions

Status indicator

Flashing Red

Receiver Lockout Conditions Status indicator Zone indicators

Flashing Red See Receiver Error Codes on page 42

To recover from a Lockout condition, correct all errors and cycle power to the device.

8.2 Receiver Error Codes

Indicators
Flashing

Error Description
Output Error caused by: · one or both outputs being shorted to a power supply (high or low) · by shorting OSSD 1 to OSSD 2 · by an overload (greater than 0.5 A)

Appropriate Action
· Disconnect the OSSD loads and reset the receiver. · If the error clears, the problem is in the OSSD load(s) or in the
load wiring. · If the error continues with no load connected, replace the
receiver.

Flashing

Receiver Error occurs because of excessive electrical noise or an internal failure

· Perform a reset per Checkout Procedures: Shift and Daily Checkout Procedure.
· If the error clears, perform a Daily Checkout procedure (per Checkout Procedures: Shift and Daily Checkout Procedure; Daily Checkout Card) and if the System checks out, resume operation. If the System fails the Daily Checkout procedure, replace the receiver.
· If the error clears, check the external connections and configuration settings.
· If the error continues, replace the receiver.

8.3 Electrical and Optical Noise
The S4B is designed and manufactured to be highly resistant to electrical and optical noise and to operate reliably in industrial settings. However, serious electrical and/or optical noise may cause a random nuisance trip. In extreme electrical noise cases, a Lockout is possible. To minimize the effects of transitory noise, the S4B responds to noise only if the noise is detected on multiple consecutive scans. If random nuisance trips occur, check the following:
· Optical interference from adjacent light screens or other photoelectrics · Sensor input or output wires routed too close to noisy wiring
8.3.1 Checking for Sources of Electrical Noise
All S4B wiring is low voltage; running these wires alongside power wires, motor/servo wires, or other high-voltage wiring can inject noise into the S4B System. It is good wiring practice (and may be required by code) to isolate S4B wires from highvoltage wires.
1. Use the Banner model BT-1 Beam Tracker Alignment Aid (see Accessories on page 47) to detect electrical transient spikes and surges.
2. Cover the lens of the BT-1 with electrical tape to block optical light from entering the receiver lens.

42

www.bannerengineering.com – Tel: + 1 888 373 6767

S4B Safety Light Curtain
3. Press the RCV button on the BT-1 and position the Beam Tracker on the wires going to the S4B or any other nearby wires.
4. If the BT-1’s indicator lights, check for sources of electrical noise and separate the S4B cordset from any high-voltage wiring, if applicable.
5. Install proper transient suppression across the load to reduce the noise.
8.3.2 Check for Sources of Optical Noise
1. Turn off the emitter or completely block the emitter. 2. Press the RCV button on the Banner BT-1 Beam Tracker Alignment Aid and move it across the full length of the
receiver’s sensing window to check for light at the receiver. 3. If the BT-1’s indicator lights, check for emitted light from other sources (other safety light screens, grids or points, or
standard photoelectric sensors).

www.bannerengineering.com – Tel: + 1 888 373 6767

43

S4B Safety Light Curtain

9 Checkout Procedures
This section lists the schedule of checkout procedures and describes where each procedure is documented. Checkouts must be performed as described. Results should be recorded and kept in the appropriate place (for example, near the machine, and/or in a technical file).
Banner Engineering highly recommends performing the System checkouts as described. However, a Qualified Person (or team) should evaluate these generic recommendations considering their specific application and determine the appropriate frequency of checkouts. This will generally be determined by a risk assessment, such as the one contained in ANSI B11.0. The result of the risk assessment will drive the frequency and content of the periodic checkout procedures and must be followed.

9.1 Schedule of Checkouts

Checkout cards and this manual can be downloaded at www.bannerengineering.com.

Checkout Procedure Trip Test Commissioning Checkout
Shift/Daily Checkout
Semi-Annual Checkout

When to Perform

Where to Find the Procedure

Who Must Perform the Procedure

At Installation
Any time the System, the guarded machine, or any Conduct a Trip Test on page 32 part of the application is altered.

Qualified Person

At Installation
Whenever changes are made to the System (for example, either a new configuration of the S4B or changes to the guarded machine).

Commissioning Checkout on page 36

Qualified Person

At each shift change
Machine setup change
Whenever the System is powered up
During continuous machine run periods, this checkout should be performed at intervals not to exceed 24 hours.

Daily Checkout Card (Banner p/n 230288)
A copy of the checkout results should be recorded and kept in the appropriate place (for example, near or on the machine, in the machine’s technical file).

Designated Person or Qualified Person

Every six months following System installation, or whenever changes are made to the System (either a new configuration of the S4B or changes to the machine).

Semi-Annual Checkout Card (Banner p/n 230289)
A copy of the checkout results should be recorded and kept in the appropriate place (for example, near or on the machine, in the machine’s technical file).

Qualified Person

44

www.bannerengineering.com – Tel: + 1 888 373 6767

10 Product Support and Maintenance

S4B Safety Light Curtain

10.1 Cleaning
Clean components with mild detergent or window cleaner and a soft cloth. Avoid cleaners containing alcohol, as they may damage the polycarbonate housing.

10.2 Warranty Service
Contact Banner Engineering for troubleshooting of this device. Do not attempt any repairs to this Banner device; it contains no field-replaceable parts or components. If the device, device part, or device component is determined to be defective by a Banner Applications Engineer, they will advise you of Banner’s RMA (Return Merchandise Authorization) procedure.
Important: If instructed to return the device, pack it with care. Damage that occurs in return shipping is not covered by warranty.

10.3 Manufacturing Date
Every S4B produced is marked with a code that defines the week and year of manufacture and manufacturing location. The code format (U.S. Standard format) is: YYWWL
· YY = Year of manufacture, 2 digits · WW = Week of manufacture, 2 digits · L = Banner-specific code, 1 digit Example: 2309H = 2023, Week 9.
10.4 Disposal
Devices that are no longer in use should be disposed of according to the applicable national and local regulations.
10.5 Banner Engineering Corp Limited Warranty
Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty does not cover damage or liability for misuse, abuse, or the improper application or installation of the Banner product. THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE USAGE. This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE. Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously manufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection applications when the product is identified as not intended for such purposes will void the product warranty. Any modifications to this product without prior express approval by Banner Engineering Corp will void the product warranties. All specifications published in this document are subject to change; Banner reserves the right to modify product specifications or update documentation at any time. Specifications and product information in English supersede that which is provided in any other language. For the most recent version of any documentation, refer to: www.bannerengineering.com. For patent information, see www.bannerengineering.com/patents.

www.bannerengineering.com – Tel: + 1 888 373 6767

45

S4B Safety Light Curtain
10.6 Contact Us
Banner Engineering Corp. headquarters is located at: 9714 Tenth Avenue North Minneapolis, MN 55441, USA Phone: + 1 888 373 6767 For worldwide locations and local representatives, visit www.bannerengineering.com.

46

www.bannerengineering.com – Tel: + 1 888 373 6767

11 Accessories

S4B Safety Light Curtain

11.1 Safety Controllers

Safety Controllers provide a fully configurable, software-based safety logic solution for monitoring safety and non-safety devices.
For additional models and XS26 expansion modules, see instruction manual p/n 174868.
Table 4: Safety controller models

Non-Expandable Models Expandable Models

Description

SC26-2

XS26-2

26 convertible I/O and 2 redundant solid state safety outputs

SC26-2d

XS26-2d

26 convertible I/O and 2 redundant solid state safety outputs with display

SC26-2e

XS26-2e

26 convertible I/O and 2 redundant solid state safety outputs with Ethernet

SC26-2de

XS26-2de

26 convertible I/O and 2 redundant solid state safety outputs with display and Ethernet

SC10-2roe

10 inputs, 2 redundant relay safety outputs (3 contacts each) (ISD and Ethernet compatible)

XS26-ISDd

26 inputs, 2 redundant solid state safety outputs with display, Ethernet, and 8 ISD channels

11.2 In-Line Sensor Status Indicator
The S15LRGPQ provides in-line sensor status indication of the output status of the S4B receiver. See datasheet p/n 212217 for more information.
· Connects in line with receiver cable · Translucent white PUR body · Fully encapsulated IP66, IP67, and IP68 body

11.3 Literature

The following documentation are available at no charge. Contact Banner Engineering or visit www.bannerengineering.com.

Part Number

Description

230287

S4B Safety Light Curtain Instruction Manual

230288

Daily Checkout Procedure Card

230289

Semi-Annual Checkout Procedure Card

11.4 Brackets
S4BA-MBK-16 · Side mount bracket · ±15° rotation · Glass-filled polycarbonate · Includes two brackets

*mounting hole

spacing 25 mm

38

4 x Ø4.5*

42 68

www.bannerengineering.com – Tel: + 1 888 373 6767

47

S4B Safety Light Curtain

11.5 Cordsets

Machine interface cordsets provide power to the first emitter/receiver pair.
Table 5: 5-Pin Threaded M12 Cordset–Double Ended

Model

Length

Style

Dimensions

DES4E-51D

315 40

0.3 m (1 ft)

Male Straight

M12 x 1

27 39

Pinout (Male)

1

2 4

3

5

1 = Brown 2 = White 3 = Blue 4 = Black 5 = Green/Yellow

Table 6: MQDC1-5.. 5-pin M12 Quick-disconnect to flying lead cordsets
These cordsets have a M12 quick-disconnect connector on one end and are unterminated (cut to length) on the other end to interface with guarded machine. PVC cable jacket and PUR overmolded strain relief.

5-Pin Threaded M12 Cordsets–Single Ended

Model

Length

MQDC1-501.5

0.5 m (1.5 ft)

MQDC1-503

0.9 m (2.9 ft)

MQDC1-506

2 m (6.5 ft)

MQDC1-515

5 m (16.4 ft)

MQDC1-530

9 m (29.5 ft)

MQDC1-560

18 m (59 ft)

MQDC1-5100

31 m (101.7 ft)

Style Straight

Dimensions
44 Typ. M12 x 1 ø 14.5

Pinout (Female)

2 1

3

4

5

1 = Brown 2 = White 3 = Blue 4 = Black 5 = Gray

Pin

Color

1

Brown

Emitter Function +24 V DC

Receiver Function +24 V DC

2

White

3

Blue

no connection 0 V DC

OSSD2 0 V DC

4

Black

no connection

OSSD1

5

Gray

no connection

Weak Beam Strength Output

Splitter cordsets are used for easy interconnection between an S4B receiver and its emitter, providing a single “homerun” cable. Model DEE2R-.. double- ended cordsets may be used to extend the QD trunk or either branch. (Branch #1 and branch #2 cable sections are 300 mm/1 ft long.)
Model MQDC1-5.. single-ended corsets may be used to extend the QD trunk for cut-to-length applications.
The 5-pin splitter cordsets allow for an easy interconnection between the receiver and emitter, and provide a single trunk cable for the optional interchangeable (“swapable”) connection.

5-Pin Threaded M12 Splitter Cordsets with Flat Junction–Double Ended

Model

Trunk (Male)

Branches (Female)

Pinout (Male)

Pinout (Female)

CSB-M1251M1251 CSB-M1258M1251 CSB-M12515M1251 CSB-M12525M1251

0.3 m (0.98 ft) 2.44 m (8 ft) 4.57 m (15 ft) 7.62 m (25 ft)

2 x 0.3 m (0.98 ft)

1

2 4

3

5

2 1

3

4

5

48

www.bannerengineering.com – Tel: + 1 888 373 6767

S4B Safety Light Curtain

5-Pin Threaded M12 Splitter Cordsets with Flat Junction–Double Ended

Model

Trunk (Male)

Branches (Female)

CSB-UNT525M1251

7.62 m (25 ft) Unterminated

Ø14.5 [0.57″] M12 x 1

40 Typ. [1.58″]

Ø4.5 [0.18″]

18.0 [0.71″]

35 [1.38″]

43.0 [1.69″]

44 Typ. [1.73″]

Ø14.5 [0.57″] M12 x 1

Pinout (Male)
1 = Brown 2 = White 3 = Blue

Pinout (Female)
4 = Black 5 = Green/Yellow

Table 7: DEE2R-5..D 5-pin M12 Quick-Disconnect to M12 Quick-Disconnect (female-male) cordsets
Use the DEE2R-5… cordsets to extend the length of cordsets and directly connect to other devices with a 5-pin M12 quickdisconnect connector. Other lengths are available.

Model DEE2R-51D DEE2R-53D

Length 0.3 m (1 ft) 0.9 m (3 ft)

Banner Cordset Pinout/Color Code

M12 Connector (female face view)
40 Typ.

DEE2R-58D DEE2R-515D DEE2R-525D DEE2R-550D DEE2R-575D DEE2R-5100D

2.5 m (8 ft) 4.6 m (15 ft) 7.6 m (25 ft) 15.2 m (50 ft) 22.9 m (75 ft) 30.5 m (100 ft)

See the table below

M12 x 1 ø 14.5
44 Typ.

M12 x 1 ø 14.5

2 1

3

4

5

Pin

Color

1

Brown

2

White

3

Blue

4

Black

5

Gn/Ye

Emitter Function +24 V DC
no connection 0 V DC
no connection no connection

Receiver Function +24 V DC OSSD2 0 V DC OSSD1
Weak Beam Strength Output

11.6 Test Piece

Use a test piece during a trip test to verify the detection capability of the sensor.

Model

Description

STP-14

30 mm test piece (30 mm resolution systems)

11.7 Universal (Input) Safety Modules
UM-FA-xA Safety Modules are safety monitoring devices that provide forced- guided, mechanically-linked relay (safety) outputs for the S4B system. See datasheet p/n 141249 for more information.

www.bannerengineering.com – Tel: + 1 888 373 6767

49

S4B Safety Light Curtain
Model UM-FA-9A UM-FA-11A

Description 3 normally open (N.O.) redundant-output 6 amp contacts 2 normally open (N.O.) redundant-output 6 amp contacts, plus 1 normally closed (N.C.) auxiliary contact

11.8 Alignment Aids

Model LAT-1-S4B S4B-LAT-2 S4B-LAT-SS BRT-THG-2-100

Description Self-contained visible-beam laser tool for aligning any S4B emitter/receiver pair. Includes retroreflective target material and mounting clip. Clip-on retroreflective LAT target Replacement LAT-1 Clip 2 inch retroreflective tape, 100 ft

BT-1

Beam Tracker

11.9 MSM Series Corner Mirrors
· Compact for light-duty applications · Rear-surface glass mirrors are rated at 85% efficiency. The total sensing range decreases by approximately 8% per
mirror. See the MSM Series Corner Mirror datasheet (p/n 43685) or http://www.bannerengineering.com for further information. · Mounting brackets may be inverted from the positions shown (flanges pointing “inward” instead of “outward,” as shown). When this is done, dimension L1 decreases by 57 mm. · MSAMB adapter bracket kit included with each MSA stand.

Mirror Model MSM4A

Part Number 43162

Reflective Area Length (Y)
165 mm (6.5 in)

Mounting Length (L1) 221 mm (8.7 in)

Mirror Height Overall (L2)
191 mm (7.5 in)

MSM8A MSM12A

43163 43164

267 mm (10.5 in) 356 mm (14 in)

323 mm (12.7 in) 411 mm (16.2 in)

292 mm (11.5 in) 381 mm (15 in)

M4 x 10 mm Screw (8 supplied)

MSM16A MSM20A

43165 43166

457 mm (18 in) 559 mm (22 in)

513 mm (20.2 in) 615 mm (24.2 in)

483 mm (19 in) 584 mm (23 in)

53.8 mm (2.12″)

MSM24A

43167

660 mm (26 in)

716 mm (28.2 in)

686 mm (27 in)

Y

MSM28A MSM32A

43168 43169

762 mm (30 in) 864 mm (34 in)

818 mm (32.2 in) 919 mm (36.2 in)

787 mm (31 in) 889 mm (35 in)

L1 L2

MSM36A MSM40A MSM44A

43170 43171 43172

965 mm (38 in) 1067 mm (42 in) 1168 mm (46 in)

1021 mm (40.2 in) 1123 mm (44.2 in) 1224 mm (48.2 in)

991 mm (39 in) 1092 mm (43 in) 1194 mm (47 in)

72.9 mm (2.87″)

50.8 mm (2.00″)

MSM48A

43173

1270 mm (50 in)

1326 mm (52.2 in)

1295 mm (51 in)

MSM Model
MSM4A MSM8A MSM12A

SLS Defined Area

S4B Defined Area

Light Curtain Series LP Defined Area

LS Defined Area

Type 2 Defined Area

150

150

300

300

270

280

300

50

www.bannerengineering.com – Tel: + 1 888 373 6767

MSM Model
MSM16A MSM20A MSM24A MSM28A MSM32A MSM36A MSM40A MSM44A MSM48A

S4B Safety Light Curtain

SLS Defined Area
450 600
750 900
1050 1200

S4B Defined Area
450 600
750 900
1050 1200

Light Curtain Series LP Defined Area 410
550 690
830 970 1110

LS Defined Area 350 490 560
630/700 770
840/910 980
1050/1120 1190

Type 2 Defined Ar

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals