Mircom FA-1000 Series Microprocessor Based Fire Alarm System
Introduction
The FA-1000 Series Microprocessor Based Fire Alarm System can be configured to meet virtually any requirements. To facilitate this flexibility, the panel has a number of add-on modules which allow the system to perform certain functions. The following modules have been designed to adapt the system to suit the particular requirements of a building.
RM-1008A Eight Relay Circuit Module
The RM-1008A Eight Relay Circuit Module provides eight programable Form C
relays. Each relay is rated for 28 VDC @ 1 Amp max. Each relay is annunciated
for configuration on the front display board of the MCC-1024-6 or MCC-1024-12
Main Chassis or ECH-1048 Expander Chassis. The RM1008A Relay Adder Module
comes with removeable terminal blocks for easy wiring and servicing. The
module connects via cable to the board on the main or expander chassis. The
RM-1008A also mounts in the FX-2000 main and expander chassis.
PR-300 Polarity Reversal & City Tie Module
The PR-300 Polarity Reversal & City Tie Module allows connection to two
different types of monitoring systems. The City Tie provides an output of 24
VDC at 210 mA max. The module supervises the City Tie connection and will
provide a system trouble if not connected. A terminating resistor is supplied
with the module. The Polarity Reversal provides a 24 VDC output for normal
condition and a polarity reverse 24 VDC output for alarm. The module is also
capable of transmitting a system trouble “Zero Volts.” This option is jumper
selectable. The output current is limited to 8 mA.
UDACT-300A Digital Alarm Communicator Transmitter/Dialer Module
The UDACT-300A Digital Alarm Communicator Transmitter/Dialer Module allows
Mircom’s FA1000 Series Fire Alarm Control Panels to transmit Alarm,
Supervisory and Trouble information on two telephone lines to a monitoring
facility.
The UDACT-300A is powered by the host fi re alarm control panel and
communicates with the fi re alarm control panel via an RS-485 data link. The
Digital Communicator can be programmed for dual line operation and uses the
Security Industry Association (SIA) and Ademco Contact ID reporting protocols.
The UDACT-300A can be configured locally via the on-board keypad and the
CFG-300 Configuration Tool or with a UIMA programming tool and a computer with
an available serial or USB port. In addition the UDACT-300A can be remotely
configured using a personal computer with a modem.
The UDACT-300A can be configured for either DACT or UDACT operation. In DACT
mode the Digital Communicator reports common alarm, trouble and supervisory
information. In UDACT mode the Digital Communicator reports point specific
information.
Ordering Information
Model Description
RM-1008A Eight Relay Circuit Module c/w eight Form C relays (Rated for 28
VDC @ 1 Amp. max. per relay)
PR-300 Polarity Reversal and City Tie Module
UDACT-300A Universal Digital Alarm Communication Transmitter/Dialer
Module
Customer Service
Canada
25 Interchange Way
Vaughan, Ontario L4K 5W3
Telephone: 905-660-4655
Fax: 905-660-4113
Web page: http://www.mircom.com
Email: mail@mircom.com
U.S.A.
4575 Witmer Industrial Estates
Niagara Falls, NY 14305
Toll Free: 888-660-4655
Fax Toll Free: 888-660-4113
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>