Mircom MPS-800MP Fire Alarm Manual Station Instruction Manual
- June 4, 2024
- Mircom
Table of Contents
- Mircom MPS-800MP Fire Alarm Manual Station Instruction Manual
- Mircom
- This guide covers these models:
- Station
- Specifications & Dimensions
- Electrical Rating for MPS-822MP maglock terminal:
- Dimensions:
- Notes
- Install the manual station
- B. Wire
- Figure 4 Wiring
- Fire Alarm Manual Station
- Using the manual station
- Reset the manual station
- Read More About This Manual & Download PDF:
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Mircom MPS-800MP Fire Alarm Manual Station Instruction Manual
Mircom
Mircom’s MPS-800MP(U) Series Fire Alarm Manual Stations provide manual fire alarm activation.
This guide covers these models:
MPS-810MP Single Stage, Dual Action, MP Addressable Manual Station
MPS-810MPU Single Stage, Dual Action, MP Addressable
Manual Station (US)
MPS-802MP Two Stage, Dual Action, MP Addressable Manual
Station
MPS-822MP Two Stage, Dual Action, MP Addressable Manual Station with additional door contacts.
Specifications & Dimensions
Compatible with FX-400 series and FleX-Net™ FX-4000 Fire
Alarm Control Panels
Electrical Rating:
Nominal Operating Voltage: 15-30 VDC
Maximum alarm current: 3.3 mA
Standby current: 2 mA
Electrical Rating for MPS-822MP maglock terminal:
1A at 30VDC
Dimensions:
139 mm H x 104 mm W x 34 mm D (5 1/2” H x 4 1/8” W x 1 3/8” D)
Notes
-
Environment: Indoor, dry
-
Do not change factory applied finishes.
-
Wire as shown so that supervision of connections is maintained.
-
Maximum wire size: 14 AWG
-
ADA compliant.
-
To be installed per ADA 4.27.1 to 4.27.4 inclusive.
-
Wiring must be in accordance with CSA C22.1, Canadian
Electrical Code, Part I, Safety Standard for Electrical Installations, Section 32 and CAN/ULC-S524, Standard for Installation of Fire Alarm Systems. -
All manual fire alarm stations shall be installed as per the specific requirements outlined in the UL/ULC codes, as well as all other applicable national or local codes. Final acceptance is subject to the local authority having jurisdiction.
Install the manual station
Contents of kit
MPS-810MP(U): 2 mounting screws, 2 reset keys (black)
MPS-802MP and MPS-822MP: 2 mounting screws, 2 reset keys (black), 2 stage two
keys
A. Open
- Insert the reset key into the reset keyhole and turn it.
- Pull the cover open.
Figure 1 Front of manual station
Figure 2 Opening the station
Canada
25 Interchange Way
Vaughan, ON L4K 5W3
Tel: 1-888-647-2665
B. Wire
Note: The maximum wire size is 14 AWG.
- Strip wires to 10 mm (25/64”) maximum.
- Push the wire into the terminal.
Note: The terminals have a push-in lock. To remove the wire, push the terminal in with the screwdriver and pull out the wire at the same time. see Figure 3.
Figure 3 Removing the wire 3. Wire as shown in Figure 4.
Figure 4 Wiring
C. Mount
Flush mount indoor: Single-gang electrical box.
Surface mount indoor: BB-800 backbox with or without STI-1230
(Deep Cover without Gasket)
Note: Mount the manual station with the Mircom logo on the bottom.
]
Figure 5 Back of manual station
Fire Alarm Manual Station
D. Set the addressable module
Follow the instructions in LT-6146, the MIX-4090 Device
Programmer Installation Manual, available on http://www.mircom.com.
The factory default address is 255.
The connector for the device programmer is inside the unit above the
addressable module, as shown in Figure 6.
Figure 6 Connector for device programmer
Using the manual station
Activate the alarm
- Push in the push bar.
- Pull down the pull handle.
A qualified person must reset the station by opening it with the
reset key. See Resetting the manual station below.
Activate the stage two alarm (MPS-802MP and
MPS-822MP)
- Insert the stage two key into the stage two keyhole, and then turn the key.
The stage two alarm activates immediately.
Note: The stage two alarm will activate automatically a certain amount of time after the handle has been pulled if no action is taken. This time is set in the Fire Alarm Control Panel.
Reset the manual station
Note: Resetting the station does not cancel the alarm at the panel.
- Insert the reset key into the reset keyhole and turn it.
- Pull the cover open. The switch is now reset.
- Close and lock the station with the reset key.
- Reset the Fire Alarm Control Panel to reset the alarm.