Mircom MS-700MP U Series Fire Alarm
Description
Mircom’s MS-700MP(U) Series Fire Alarm Manual Stations provide manual fire
alarm activation. These pull stations are available as single or dual-action
devices. They are reset with a key. Each station has a permanently attached MP
(Mircom Protocol) addressable module.
Compatible with FX-400 series and FleX-Net™ MP Fire Alarm Control Panels.
The MS-700MP Manual stations are constructed of high quality, die-cast metal
and finished in red. An abrasion resistant label with large, raised letters
provides clear legible instructions.
The model MS-702MP is the Intelligent Key- Resettable Two Stage Manual
Station.
The model MS-710MP(U) is the Intelligent Key- Resettable Single Stage Dual
Action Manual Station.
The Suffix “U” indicates a USA version.
All manual fire alarm stations shall be installed as per the specific
requirements outlined in the UL/ULC codes, as well as all other applicable
national or local codes.
Addressing is done using the MIX-4090 Device programmer. For setting the
address on this device, disconnect it from the loop, or ensure that the loop
to which is connected is both disconnected from the panel and shorted across
the SCL+ and SLC- inputs at the device. Failing to take either of these steps
may change the address programming of previously configured sensors on the
loop
Features
- High quality, die-cast metal.
- Attractive, Low Profile Design
- Built-in intelligent addressable module with Mircom Protocol.
- Pulling the handle initiates the operation of the intelligent module.
- Address is set by the MIX-4090 hand-held device programmer.
- Two stage and single stage dual action version.
- UL and ULC listed version.
- Standard Single Gang Mount
- Device comes with reset key and plastic rod
Operation
Activating the alarm
- On the MS-702MP, pull down the PULL handle.
- On the MS-710MP(U), push in the PUSH bar, then pull down the PULL handle.
Activating the stage two alarm (MS-702MP only)
- Insert the stage two key into the keyhole above the PULL handle, and then turn the key.
- The stage two alarm activates immediately.
Resetting the manual station
- Open the station with the reset key. The switch is now reset.
- Move the PULL handle back to its upright position.
- Close and lock the station.
Note: Resetting the station does not cancel the alarm at the panel.
Specifications
- MS-702MP/MS-710MP(U)
- Dimensions/4.93” H x 3.56” W x 2.56” D/4.93” H x 3.56” W x 2.9” D
- Nominal Operating Voltage/15–30 VDC
- Maximum Alarm Current/3.3 mA
- Standby current/2 mA
Diagram
Mounting Diagram Wiring Diagram
Ordering Information
- Model/Description
- MS-702MP/Intelligent Key-Resettable Two Stage Manual Station MP- ULC
- MS-710MP/Intelligent Key-Resettable Single Stage Dual Action Manual Station MP- ULC
- MS-710MPU/Intelligent Key-Resettable Single Stage Dual Action Manual Station MP- UL
- MIX-4090/Addressable Device Programming Tool
- BB-700/Electrical Junction Box for Indoor Surface Mount, Red
- BB-700WP/Electrical Junction Box for Outdoor Surface Mount, Red
- GL-007K/Optional Plastic Rod
THIS INFORMATION IS FOR MARKETING PURPOSES ONLY AND NOT INTENDED TO DESCRIBE
THE PRODUCTS TECHNICALLY.
For complete and accurate technical information relating to performance,
installation, testing and certification, refer to technical literature. This
document contains intellectual property of Mircom. The information is subject
to change by Mircom without notice. Mircom does not represent or warrant
correctness or completeness.
Canada
25 Interchange Way Vaughan, Ontario L4K 5W3
Telephone: 905-660-4655
Fax: 905-660-4113
www.mircom.com
U.S.A.
4575 Witmer Industrial Estates Niagara Falls, NY 14305
Toll Free: 888-660-4655
Fax Toll Free: 888-660-4113
NOT TO BE USED FOR INSTALLATION PURPOSES.
THIS INFORMATION IS FOR MARKETING PURPOSES ONLY AND NOT INTENDED TO DESCRIBE
THE PRODUCTS TECHNICALLY.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>