Mircom MPS-800U Fire Alarm Manual Station Instruction Manual
- June 4, 2024
- Mircom
Table of Contents
Mircom MPS-800U Fire Alarm Manual Station Instruction Manual
Mircom’s MPS-800(U) Series Fire Alarm Manual Stations provide manual fire alarm activation.
This guide covers these models:
MPS-810 Single Stage, Dual Action, Conventional Manual Station
MPS-810U Single Stage, Dual Action Conventional Manual Station (US)
MPS-802 Two Stage, Dual Action, Conventional Manual Station
Specifications & Dimensions
Compatible with Mircom Fire Alarm Control Panels
Electrical Rating: 1 A at 30 VDC
Dimensions:
139 mm H x 104 mm W x 34 mm D
(5 1/2” H x 4 1/8” W x 1 3/8” D)
Notes
- Environment: Outdoor, wet
- Do not change factory applied finishes.
- Wire as shown so that supervision of connections is maintained.
- Maximum wire size: 14 AWG
- ADA compliant.
- To be installed per ADA 4.27.1 to 4.27.4 inclusive.
- Wiring must be in accordance with CSA C22.1, Canadian Electrical Code, Part I, Safety Standard for Electrical Installations, Section 32 and CAN/ULC-S524, Standard for Installation of Fire Alarm Systems.
- All manual fire alarm stations shall be installed as per the specific requirements outlined in the UL/ULC codes, as well as all other applicable national or local codes. Final acceptance is subject to the local authority having jurisdiction.
Install the manual station
Contents of kit
MPS-810(U): 2 mounting screws, 2 reset keys (black)
MPS-802: 2 mounting screws, 2 reset keys (black), 2 stage two keys
A. Open
1. Insert the reset key into the reset keyhole and turn it.
2. Pull the cover open.
Figure 1: Front of manual station
Figure 2: Opening the station
Canada:
25 Interchange Way
Vaughan, ON L4K 5W3
Tel: 1-888-647-2665
U.S.A
4575 Witmer Industrial Estates
Niagara Falls, NY 14305
Tel: 1-888-647-2665
B. Wire
Note: The maximum wire size is 14 AWG.
1. Strip wires to 10 mm (25/64”) maximum.
2. Push the wire into the terminal.
Note: The terminals have a push-in lock. To remove the wire, push the terminal in with the screwdriver and pull out the wire at the same time. see Figure 3.
Figure 3 Removing the wire
3. Wire as shown in Figure 4.
Figure 4 Wiring
C. Mount
Flush mount indoor: Single-gang electrical box.
Flush mount outdoor: Single-gang electrical box with STI-1250 (Shallow Cover
with Gasket)
Surface mount indoor: BB-800 backbox with or without STI-1230 (Deep Cover
without Gasket)
Surface mount outdoor: BB-800 backbox with STI-3150 (Deep Cover with Gasket)
Note: Mount the manual station with the Mircom logo on the bottom.
Figure 5 Back of manual station
Using the manual station
Activate the alarm
1. Push in the push bar.
2. Pull down the pull handle.
A qualified person must reset the station by opening it with the reset key.
See Resetting the manual station below.
Activate the stage two alarm (MPS-802)
• Insert the stage two key into the stage two keyhole, and then turn the key.
The stage two alarm activates immediately.
Note: The stage two alarm will activate automatically a certain amount of time after the handle has been pulled if no action is taken. This time is set in the Fire Alarm Control Panel.
Reset the manual station
Note: Resetting the station does not cancel the alarm at the panel.
- Insert the reset key into the reset keyhole and turn it.
- Pull the cover open. The switch is now reset.
- Close and lock the station with the reset key.
- Reset the Fire Alarm Control Panel to reset the alarm.