Mircom MIX-4010-DUCT Photoelectric Duct Smoke Detector Instruction Manual

October 30, 2023
Mircom

Mircom - logo

25 Interchange way, Vaughan Ontario. L4K 5W3
Phone: 905.660.4655; Fax: 905.660.4113
Web:www.mircomgroup.com
INSTALLATION INSTRUCTIONS
MIX-4010-DUCT

SPECIFICATIONS

Normal Operating Voltage: 15 to 30VDC
Maximum Alarm Current (LED on): 3.2 mA (LED on)
Standby Current: 160 μA (LED flashing)
Nominal sensitivity range: 1.52%/foot – 2.05%/foot
Duct air velocity: 300-4000 feet/minute
Temperature Range: 32 °F to 100 °F (0 °C to 37.8 °C)
Dimensions: 279 mm x 165 mm x 83 mm (11” x 6.5” x 3.3”)
Weight: 0.84 kg (1.85 lb)
Wiring range on all terminals: 24 to 12 AWG

BEFORE INSTALLING THE DUCT DETECTOR

Before installing this device, thoroughly read this manual and refer to the applicable codes including the Standard for Automatic Fire Detectors NFPA 72, the Standard for Installation of Air Conditioning and Ventilating Systems NFPA 90A, CAN/ULC-S524, and the NEMA Guide for Proper Use of Smoke Detectors in Duct Applications for guidance on location, spacing and acceptable use. Also seek guidance from the compatible control panel instructions for the device’s operation modes and the configuration requirements.

WARNING
THIS DETECTOR IS NOT INTENDED AS A SUBSTITUTE FOR OPEN AREA PROTECTION.
MIX-4010-DUCT IS FOR USE WITH MODEL MIX-4010-D DETECTOR HEAD.

ABOUT THIS MANUAL

This manual is a reference for installation. For further information on the use of this device with a FACP, refer to the panel’s manual.
Note: This manual should be left with the owner or operator of this equipment.
Detectors should be tested after installation and during periodic maintenance visits according to NFPA 72 and CAN/ULC-S524. It is recommended each device should be tested at least once per year.

DESCRIPTION

The MIX-4010-DUCT is designed to detect smoke in the air duct system. It is a photoelectric detector that continuously checks air obscuration and reports it to the Fire-Alarm panel using a fully digital communication protocol. It must be used with a MIX-4000 series compatible control panel.
The MIX-4010-DUCT has a remote alarm output for use with auxiliary devices, such as the RA100Z remote LED annunciator.
Note: The RA100Z remote indicator works with SLC loop voltages of 18V or more.

5.1 FEATURES

  • Detector head is compatible with FleX-Net™ FX-4000, FX-400, and FX-401 fire alarm control panels
  • Single sampling tube
  • Easy to install
  • Test hole on cover
  • Address is assigned with the MIX-4090 programmer

PARTS LIST

  1. Detector assembly including base, detector head, enclosure, and cover
  2. 3 metal screws for mounting
  3. 1 sampling tube end plug
  4. 1 cable gland and lock nut
  5. Installation manual (this document)

ACCESSORIES

Table 1: Accessories (sold separately)

Part number Description
DUCT-ST1 Sampling tube 1 foot (0.3m)
DUCT-ST2 Sampling tube 2 feet (0.6m)
DUCT-ST5 Sampling tube 5 feet (1.5m)
DUCT-EXTEND Sampling tube extension 3 ½ feet (1.07m) extension)
DUCT-MB Mounting bracket
DUCT-RG Rubber gasket
MIX-4010-D Replacement detector head
MIX-4090 Programmer
System Sensor RA100Z Remote LED indicator

Note: A DUCT-ST sampling tube (sold separately) is required. The sampling tube should penetrate at least 90% of the width of the duct.
When the diameter of duct is greater than 2 feet (0.6m), the sampling tube should penetrate the whole duct.
If a longer sampling tube is required, add DUCT-EXTEND sampling tube to either DUCT-ST2 or DUCT-ST5.

INSTALLATION

Note: Do not mount MIX-4010-DUCT in locations where it could be affected by condensation, such as attics or outdoors.
Install MIX-4010-DUCT in air duct systems with air velocities of 300 to 4000 feet per minute. Use a velocity meter (anemometer) to measure the air velocity in the duct. MIX-4010-DUCT can be installed in ducts with widths from 6 inches to 9 feet.

8.1 DETERMINE MOUNTING LOCATION
Install MIX-4010-DUCT pointing towards the direction of air flow as shown in figure 1. The MIX-4010-DUCT can be installed on any side of the duct.
Note: In order to gain maximum air sampling coverage in rectangular ducts, install the MIX-4010-DUCT on the shortest side.
MGC recommends that the MIX-4010-DUCT is mounted at a distance of 3 times the duct diameter before a damper, filter or change of the duct direction, and 5 times the diameter after these devices. See figure 2.
FIGURE 1: Install the detector pointing towards the air flow direction

Mircom MIX-4010-DUCT Photoelectric Duct Smoke Detector - air
flow

8.2 MOUNT THE DETECTOR ON THE DUCT

  1. If you are not using a mounting bracket, drill a 1 ½” (38mm) hole where the detector is to be mounted.

  2. If you are using the mounting bracket DUCT-MB, drill a 2” (51mm) hole where the detector is to be mounted.

  3. Measure the diameter of the duct.
    The sampling tube should penetrate approximately 90% of the width of the duct. See table 1.

  4. If needed, shorten the sampling tube and insert the end plug. See figure 3.
    If your duct diameter is greater than 2 feet (0.6m), see section 8.3.
    Mircom MIX-4010-DUCT Photoelectric Duct Smoke Detector -
tube

  5. Insert the sampling tube in the bottom of the MIX-4010-DUCT. See figure 4.

  6. Secure the sampling tube by fastening the locking screw.

  7. Insert the sampling tube in the duct (figure 6 –1) and secure the MIX-4010-DUCT to the duct using the three provided metal screws. (figure 6 -2).

FIGURE 5: For duct diameters smaller than 2 feet (0.6m)

Mircom MIX-4010-DUCT Photoelectric Duct Smoke Detector -
feet

For ducts with ø of less than 2 feet (0.6m) use DUCT-ST2.
For ducts with ø of between 2 feet and 4 (0.6m and 1.4m) use DUCT-ST5.
For ducts which are larger than 4 1.4m) use DUCT-ST5 and DUCT-EXTEND.

FIGURE 6: Secure the duct detector to the ductMircom MIX-4010-DUCT
Photoelectric Duct Smoke Detector - duct

FIGURE 7: Example mounting locations
Mircom MIX-4010-DUCT Photoelectric Duct Smoke Detector -
locations Example of location

Mircom MIX-4010-DUCT Photoelectric Duct Smoke Detector - locations
2

8.3 INSTALLATION OF SAMPLING TUBE LONGER THAN 2 FEET
When the duct diameter is greater than 2 feet (0.6m), the sampling tube should penetrate the whole duct.

  1. Drill a 2” (51mm) hole in the side of the duct opposite the detector.
  2. Place the rubber gasket DUCT-RG (included with DUCT-ST5) in the hole.
  3. Place the plastic end plug (included with DUCT-ST5) on the end of the sampling tube as shown in figure 8.
    The sampling tube must not protrude more than 1 3/16” (30mm) through the duct wall.

FIGURE 8: Installation of sampling tube longer than 2 feetMircom
MIX-4010-DUCT Photoelectric Duct Smoke Detector -
Installation

8.4 MOUNTING BRACKET FOR CIRCULAR OR INSULATED RECTANGULAR DUCTS
The mounting bracket can be used on ducts with diameters as small as 4” (100mm). The mounting bracket is supplied with rubber gasket and sealing sleeve.

FIGURE 9: Mounting Bracket

Mircom MIX-4010-DUCT Photoelectric Duct Smoke Detector -
MOUNTING

The mounting bracket can easily be bent or shaped to fit a circular or rectangular duct

Mircom MIX-4010-DUCT Photoelectric Duct Smoke Detector - MOUNTING
2

FIELD WIRING

See section 1 for the wiring gauge. Seek guidance from the compatible control panel instructions for wiring requirements for the SLC (signaling linecircuit).
9.1 CONDUIT ENTRIES AND WIRING

  1. Disconnect the loop power.

  2. Remove the four screws and the enclosure cover. See figure 10-1.
    FIGURE 10: Screws securing the cover and cable openings The MIX-4010-DUCT has one cable opening and provision for 3 more. See figure 10-2.

  3. Remove one of the three round knockouts and insert a cable gland if you need more than one opening.
    If you do not use a cable opening, close it properly.

  4. Connect the cables according to the wiring shown in figure 11 and figure 12.

  5. Secure the cover on the enclosure with the four screws.

FIGURE 11: Detector wiring

FIGURE 12: Loop wiring

Mircom MIX-4010-DUCT Photoelectric Duct Smoke Detector - WIRING
3

9.2 SET THE ADDRESS

  1. Disconnect the loop power.

  2. Remove the four screws and the enclosure cover.

  3. Remove the detector head from the base by turning it counterclockwise and lifting it.

  4. Program the detector address with the MIX-4090 programming device. See manual LT-6146 for programming.
    Addresses 1 to 240 can be used for any device on a SLC loop. Each device on a loop must have a unique address.

  5. Position the detector head centrally on its adapter base ensuring it is level.

  6. Rotate clockwise applying gentle pressure. The detector head will drop into its keyed location.

  7. Continue to rotate clockwise a few degrees until the detector head is fully engaged in the base.

  8. When the detector head is firmly engaged, check the alignment of the raised reference marks on the detector head and on the base (figure 13).

  9. Install the diverter as shown in section 11.

  10. Secure the cover on the enclosure with the four screws.

FIGURE 13: Alignment marks

Mircom MIX-4010-DUCT Photoelectric Duct Smoke Detector - WIRING
4

MEASUREMENT TESTS

10.1 METHOD 1: LOW VELOCITY 300-500 FEET PER MINUTE
This test is intended for low-flow systems (300-500 feet per minute). With the air handler on, measure the air velocity with an anemometer. The air speed must be 300 feet per minute or greater. Then use the Dwyer Transmitter (series 607-1) by following the details provided in figure 14.
The pressure differential across the inlet port and outlet ports of the sampling tube shall be verified to be more than 0.01 inches of water.
Measure the pressure difference between the inlet port and outlet ports on the sampling tube with a Dwyer Series 607-1 Differential Pressure Transmitter. To verify sufficient sampling of ducted air, turn the air handler on. Connect the leads of the meter to either side of the 1 kΩ resistor.
Allow unit to warm up for 15 seconds. With both HIGH and LOW pressure ports open to ambient air, measure and record the voltage drop across the 1 kΩ resistor (measurement A), typical reading is approximately 4V.
Use flexible tubing to connect the HIGH side of the transmitter to the inlet port of the sampling tube and the LOW side of the transmitter to the outlet ports of the sampling tube. Measure and record the voltage drop across the 1 kΩ  resistor (measurement B). Subtract the voltage recorded in measurement A from the voltage recorded in measurement B. The results should be greater than 0.15 volts, and then this indicates that there is enough air flow through the duct  smoke detector for proper operation.

FIGURE 14: Measure the pressure differentialMircom MIX-4010-DUCT
Photoelectric Duct Smoke Detector - differential

10.2 METHOD 2: AIR VELOCITY GREATER THAN 500 FEET PER MINUTE
First, verify the air speed is greater than 500 feet per minute by using the measurement method described in section 10.1. With the air handler turned on, use a manometer to measure the differential pressure across the inlet port and outlet ports of the sampling tube, this measurement shall be verified to be between 0.0028 to 1.49 inches of water. Please ensure that the end of the tube is completely sealed by use of a plug, or a duct tape in order to obtain proper measurements.

Install the Diverter

The plastic diverter is always required. Install it so that it directs smoke from the sampling tube into the detector head. See figure 15. The diverter is included with the sampling tube.
FIGURE 15: Install the diverter

Mircom MIX-4010-DUCT Photoelectric Duct Smoke Detector -
Diverter

DETECTOR HEAD REPLACEMENT

  1. Remove the old detector head from the base by turning it counterclockwise and lifting it.

  2. Position the new detector head centrally on its adapter base ensuring it is level.

  3. Rotate the head clockwise applying gentle pressure. The detector head will drop into its keyed location.
    Continue to rotate clockwise a few degrees until the detector head is fully engaged in the base.

  4. When the detector head is firmly engaged, check the alignment of the raised reference marks on the detector head and on the base (figure 13).

  5. Install the diverter as shown in section 11.

TESTING THE DETECTOR

Detectors should be tested after installation and during periodic maintenance visits; it is recommended to test each device at least once per year.
After each test reset the system and allow at least one minute for power stabilization.

13.1 MAGNET TEST
Position the test magnet next to raised mark on the detector, then move it 45 degrees counter-clockwise (figure 16).
The magnet test simulates smoke in the optical chamber and verifies the function of all electronic circuits of the detector and its communication with the control panel. The detector should trigger an alarm message to the control panel,  and, successively, the detector’s red LED should be activated by the control panel it self.
FIGURE 16: Mark for magnet test

13.2 AEROSOL TEST (SIMULATED SMOKE TEST)
For this test only use test aerosols from an approved manufacturer, in accordance with their application instructions, in order to prevent contamination or possible damage to the detector. Spray the aerosol into the detector by using a  recommended applicator.

  1. Open the test hole plug (figure 17).
  2. Spray aerosol smoke into the hole. Follow the instructions provided by the manufacturer.
  3. Wait for the detector to trigger an alarm message on the control panel.
    The detector’s red LED should be activated. If the detector does not respond to the tests correctly it may be necessary to clean it; in this case follow the instructions indicated in section 14. If testing fails again after maintenance then  replace the detector with a new one and return the faulty one for servicing. After testing, close the test hole plug.
    FIGURE 17: Hole for aerosol test

MAINTENANCE

  1. Disconnect the power.
  2. Remove the four screws and the enclosure cover.
  3. Remove the detector head from the base: turn it counter-clockwise and lift it.
  4. Inspect the detector head in good light at ground level. Inspect the smoke entry ports around the detector and use a small, soft bristle brush to dislodge any evident contaminants.
  5. Use a small vacuum tube or clean, dry and compressed air to suck up or blow away any remaining small particles from the smoke entry screen area.
  6. Wipe the exterior housing of the detector with a clean, damp, lint free cloth to remove any surface film that can later attract airborne contaminants.
  7. Use the hand-held programming unit to read the pollution percentage of the chamber; refer to LT-6146 the programming unit instruction manual.
  8. Replace the detector head: position the detector head centrally on its adapter base ensuring it is level.
  9. Rotate the head clockwise applying gentle pressure. The detector head will drop into its keyed location.
  10. Continue to rotate clockwise a few degrees until the detector head is fully engaged in the base.
  11. When the detector head is firmly engaged, check the alignment of the raised reference marks on the detector head and on the base (figure 13).
  12. Install the diverter as shown in section 11.
  13. Secure the enclosure cover with the four screws.
  14. Power on the system.
  15. Verify that the smoke detector is working.

DETECTOR HEAD LEDS

Table 2: Detector Head LED Colors

Alarm Red (Steady on)
Air Sampling Green (Flash)
Fault Yellow (Steady on)

WARRANTY

Purchase of all MGC products is governed by:
https://www.mircom.com/product-warranty
https://www.mircom.com/purchase-terms-and-conditions
https://www.mircom.com/software-license-terms-and-conditions

LT-6744 rev 0 4/12/23 HFE749

Documents / Resources

| Mircom MIX-4010-DUCT Photoelectric Duct Smoke Detector [pdf] Instruction Manual
MIX-4010-DUCT Photoelectric Duct Smoke Detector, MIX-4010-DUCT, Photoelectric Duct Smoke Detector, Duct Smoke Detector, Smoke Detector, Detector
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Mircom User Manuals

Related Manuals