Mircom i3 SERIES 2-Wire Loop Test-Maintenance Module Owner’s Manual

June 9, 2024
Mircom

Mircom i3 SERIES 2-Wire Loop Test-Maintenance Module

Description

The 2W-MOD2 two-wire loop test/maintenance module maximizes the benefits of the i3™ series smoke detectors, by offering detector remote maintenance signaling and EZ Walk loop testing capabilities.

Installation Ease
The 2W-MOD2 mounts to a 4”-square back box for quick and easy installation. Terminal blocks with durable SEMS screws assure a reliable connection.

Intelligence
The 2W-MOD2 allows communication to 2-wire i3 detectors with any listed fi re alarm control panel. This in turn enables i3 detectors to initiate a remote maintenance signal when they are in need of cleaning, and to provide a visual indication of this condition at the module and at the panel. The 2W-MOD2 also features the EZ Walk loop test for 2-wire i3 series detectors. This function verifi es the entire initiating loop wiring with just the press of a button.

Instant Inspection
The 2W-MOD2 includes three LEDs — green, red, and yellow — that provide status indication for the loop. These LEDs indicate the following:

  • Loop communication status
  • Maintenance alert
  • Alarm
  • Freeze trouble
  • EZ Walk test enabled
  • Wiring fault

Features

  • Allows all 2-wire i3™ detectors to be used on any compatible 2 or 4-wire fi re alarm control panel
  • Interprets the i3 remote maintenance signal
  • Provides visual indication and an output relay when a detector on the loop requires cleaning
  • Initiates the EZ Walk loop test
  • Provides Style D wiring on IDC loops
  • Green, red, and yellow LEDs indicate
    • Loop communication status
    • Maintenance alert
    • Freeze trouble
    •  Alarm
    • EZ Walk test enabled
    • Wiring fault
  • Mounts to 4”-square back box
  • Durable terminal blocks with SEMS screws

Engineering Specifications

Loop test/maintenance module shall be an i3 series model number 2W-MOD2, listed to Underwriters Laboratories UL 864 for Control Units for Fire Protection Signaling Systems. The module shall include provisions for mounting to 4-inch square back boxes. Wiring connections shall be made by means of SEMS screws. The module shall provide three LED indicators which will blink or illuminate to indicate communication status, maintenance alert, alarm or freeze trouble conditions, and EZ Walk loop test mode. The module shall allow communication to 2-wire i3 detectors with any UL listed fi re alarm control panel. The 2W-MOD2 shall offer provisions for Style D wiring on IDC loops, and shall provide a loop testing capability to verify the initiating loop wiring.

Mounting

Electrical Specifications

Operating Voltage

  • Nominal: 12/24 V
  • Min.: 8.5 V power limited
  • Max.: 35 V power limited

Maximum Ripple Voltage

  • 30% of nominal (peak to peak)

Alarm Contact Ratings

  • 0.5 A @ 36VDC, Resistive

Maintenance Contact Ratings

  • 2 A @ 30VDC, Resistive

Maximum Standby Current

  • 30 mA

Maximum Alarm Current

  • 90 mA

Max. Maintenance Current

  • 53 mA

LED Modes

LED Color Status Condition


Green LED

| On| Power on. Detectors on loop do not have communication capability.
Blinking 1 sec. on / 1 sec. off| Power on. Detectors on loop are communicating normally.
Off| Power not applied or module not in operation.


Red LED

| On| Detector on loop in alarm.
Blinking 1 sec. on / 1 sec. off| One or more detector on loop is in need of maintenance or is in freeze trouble.
Yellow LED| On| Loop wiring fault exists.
Blinking 0.5 sec. on / 0.5 sec. off| EZ Walk test mode.

Power Up Sequence for LED Indication

Condition Duration
Initial LED status indication 2 minutes
EZ Walk test available 6 minutes after reset

Physical Specifications

Operating Temperature Range

  • 14°F–122°F (–10°C to 50°C)

Operating Humidity Range

  • 0 to 95%

RH non-condensing Input Terminals

  • 14–22 AWG

Dimensions

  • Height: 4.5 inches (114 mm)
  • Width: 4.0 inches (101 mm)
  • Depth: 1.25 inches (32 mm)

Weight

  • 8 oz. (225 grams)

Mounting

  • 4-inch square back box

Ordering Information

Model Description
2-wire loop test/maintenance module for 2-wire i3 Series standard, sounder and Form C relay smoke detectors

Canada
25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone: 905-660-4655 Fax: 905-660-4113
Web page: http://www.mircom.com

U.S.A.
4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free: 888-660-4655 Fax Toll Free: 888-660-4113

Email: mail@mircom.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Mircom User Manuals

Related Manuals