ggm gastro GC95 Refrigerated Serve Over Counter User Manual

June 9, 2024
ggm gastro

ggm gastro -logo Refrigerated Serve over counter GC95

 SM 1,0-1|
---|---
SM 1,2-1|
SM 1,5-1|
SM 1,8-1|
SM 2,0-1|
SV 1,0-1|
SV 1,2-1|
SV 1,5-1|
SV 1,8-1|
SV 2,0-1|
SL 1,0-1|
SL 1,2-1|
SL 1,5-1|
SL 1,8-1|
SL 2,0-1|
SM 1,0-2|
SM 1,2-2|
SM 1,5-2|
SM 1,8-2|
SM 2,0-2|
VM 5|
VM 6|

**OPERATION MANUAL**

INTRODUCTION

This Operation Manual is intended to get acquainted with the device, installation and operation regulations for the refrigerated display.
Installation, precommissioning, and maintenance of the display case must be performed only by the service centers of suppliers or retailers of refrigeration equipment working on behalf of the manufacturer.
This Operation Manual includes nameplate data.
Warning! Before putting the product into operation, study the Operation Manual. The Manual must be accessible for the user during the whole lifetime of the product.

  1. GENERAL INFORMATION
    1.1. PRODUCT PURPOSE
    Refrigerated displays (hereinafter display cases) are intended for short-term storage and selling of food products precooled down to the temperature of the refrigerated enclosure at retail and food service facilities.
    Display cases are intended for operation in the self-ventilated closed space at ambient temperature of 12°С to 25°С and relative humidity of up to 60%.
    1.2. SPECIFICATIONS
    Main specifications of display cases are presented in Table 1.
    Table 1. Specifications of refrigerated displays.

Display case brand| Net volumm3| Refrigerate d area, sq. m| Net volume temperature °C| Set total capacity, kW| Energy consumptio n  per 24hour day,
kW/h, not more| Overall dimensions, mm, without protruding parts| Net weight, kg, not more
---|---|---|---|---|---|---|---
length| width| height (with legs)
GC95 SM 1,0-1| 0.09| 0.6| 0 ÷ +7| 0.4| 4| 1020| 970| 1200(1235| 115
GC95 SM 1,2-1| 0.11| 0.7| 0 ÷ +7| 0.4| 5.0| 1180| 970| 1200 (1235)| 140
GC95 SM 1,5-1| 0.13| 0.9| 0 ÷ +7| 0.4| 5.0| 1480| 970| 1200 (1235)| 150
GC95 SM 1,8-1| 0.16| 1.09| 0 ÷ +7| 0.4| 6.0| 1780| 970| 1200 (1235)| 170
GC95 SM 2,0-1| 0.18| 1.2| 0 ÷ +7| 0.4| 6.0| 1955| 970| 1200 (1235)| 180
GC95 SV 1,0-1| 0.09| 0.6| -5 ÷ +5| 1.1| 5.6| 1020| 970| 1200 (1235)| 115
GC95 SV 1,2-1| 0.11| 0.7| -5 ÷ +5| 1.1| 5.8| 1180| 970| 1200 (1235)| 145
GC95 SV 1,5-1| 0.13| 0.9| -5 ÷ +5| 1.1| 6.6| 1480| 970| 1200 (1235)| 155
GC95 SV 1,8-1| 0.16| 1.09b| -1| 1.4| 7.2| 1780| 970| 1200 (1235)| 175
GC95 SV 2,0-1| 0.18| 1.2| -5 ÷ +5| 1.4| 8.2| 1955| 970| 1200 (1235)| 185
GC95 SL 1,0-1| 0.08| 0.56| до -18| 2.0| 6.6| 1020| 970| 1200 (1235)| 140
GC95 SL 1,2-1| 0.1| 0.66| до -18| 2.1| 6.8| 1180| 970| 1200 (1235)| 150
GC95 SL 1,5-1| 0.13| 0.84| до -18| 2.2| 7.2| 1480| 970| 1200(1235| 162
GC95 SL 1,8-1| 0.15| 1.03| до -18| 2.4| 9.2| 1780| 970| 1200 (1235)| 185
GC95 SL 2,0-1| 0.17| 1.14| до -18| 2.4| 11.2| 1955| 970| 1200 (1235)| 192
GC95 SM 1,0-2| 0.09| 0.6| до -18| 1.1| 5.6| 1020| 970| 870 (905)| 110
GC95 SM 1,2-2| 0.11| 0.7| до -18| 1.1| 5.8| 1180| 970| 870 (905)| 120
GC95 SM 1,5-2| 0.13| 0.9| +2 ÷ +6| 1.1| 6.6| 1480| 970| 870 (905)| 130
GC95 SM 1,8-2| 0.16| 1.09| +2 ÷ +6| 1.4| 7.2| 1780| 970| 870 (905)| 145
GC95 SM 2,0-2| 0.18| 1.2| +2 ÷ +6| 1.4| 8.2| 1955| 970| 870 (905)| 160
GC95 VM-5| 0.11| 0.7| 0 ÷ +7| 0.4| 5.0| 1550| 1045| 1200 (1235)| 140
GC95 VM-6| 0.11| 0.7| 0 ÷ +7| 0.4| 5| 1860| 1130| 1200 (1235)| 140

Notes:

  1. Refrigerant type: R134a, R452А, its quantity is specified on the data plate
  2. Power Supply System: 1/N/PE 230V 50 Hz.

Electrical schematic
Electric schematic diagram is shown in Fig. 1-6.
ATTENTION! The manufacturer reserves the right to make minor changes to the electric schematic diagram of the unit which do not impair its operation, without any notice.

LEGEND OF THE ELECTRICAL SCHEMATIC DIAGRAM:
А1 – controller
SA1 – key switch
SA2 – lighting key switch
MC – compressor electric motor
MVC – condenser fan motor
MVE – air cooler fan motor
S1 – temperature sensor of refrigerated enclosure
S2 – temperature sensor of evaporator
ХР – power cord plug
ХТ – grounding terminal
QF – automatic switch
KM – magnetic starter
LA – lamp
ES – heating element
ESС – flexible heater of a condensate drainage tray
Fig. 1. Electric schematic diagram of the refrigerated display GC95 SM 1,0-1; GC95 SM 1,2-1; GC95 SM 1,5-1; GC95 SM 1,8-1; GC95 SM 2,0-1.
ggm gastro GC95 Refrigerated Serve Over Counter-

Fig. 2. Electric schematic diagram of the refrigerated display GC95 SV 1,0-1; GC95 SV 1,2-1; GC95 SV 1,5-1; GC95 SV 1,8-1; GC95 SV 2,0-1.ggm gastro GC95
Refrigerated Serve Over Counter-fig1

Fig. 3. Electric schematic diagram of the refrigerated display GC95 SL 1,0-1; GC95 SL 1,2-1; GC95 SL 1,5-1.ggm gastro GC95 Refrigerated Serve Over
Counter-fig2

Fig. 4. Electric schematic diagram of the refrigerated display GC95 SL 1,8-1; GC95 SL 2,0. ggm gastro GC95 Refrigerated Serve Over Counter-
fig3

Fig. 5. Electric schematic diagram of the refrigerated display GC95 SM 1,0-2; GC95 SM 1,2-2; GC95 SM 1,5-2; GC95 SM 1,8-2; GC95 SM 2,0-2. ggm gastro GC95
Refrigerated Serve Over Counter-fig4

Fig. 6. Electric schematic diagram of the refrigerated display GC95 VM-5, GC95 VM-6.ggm gastro GC95 Refrigerated Serve Over Counter-
fig5

NAMEPLATE DATA

2.1. SCOPE OF DELIVERY
The Scope of Delivery is presented in the assembly diagram.
2.2. ACCEPTANCE CERTIFICATE

Seal
2.3. WARRANTY OBLIGATIONS

The manufacturer guarantees conformance of the display case to specification requirements 5151-002-80055133-2007 “Refrigerated displays. Specifications”, provided that  transportation, storage, installation, and operation conditions and regulations specified in the Operation Manual are observed. Warrantied service life of the refrigerated  display is 12 months from the date of putting into operation, but not more than 18 months from the date of manufacture. Warrantied storage life is 6 months from the date  of manufacture.
Total average service life of the display case is at least 12 years, provided that the installation and operation regulations are complied with.
The warranty is only valid if the following documentation is available:
– Operation Manual;
– Certificate of Putting into Operation (form in Appendix A);
– Technical Evaluation Report (form in Appendix B);
– Maintenance Contract with a specialized company authorized by the equipment supplier (vendor).
The warranty obligations are performed by the authorized organization (the Supplier or Vendor) and their service centers.
The warranty obligations are not performed if:
– the transportation, storage and operation regulations and safety measures specified in the Operation Manual are not complied with;
– precommissioning, routine maintenance of the product is performed by a company which does not have the required authorization to perform such work;
– structural changes to the display case (installation or replacement of parts or installation of additional parts not manufactured or not approved by Company were made  without the manufacturer’s written approval;
– display case serial number is removed, unreadable or changed;
– there is a defect as a result of outside impacts and the reasons beyond the manufacturer’s control, such as:
– deviation from standard power supply parameters (deviation of current frequency from the rated one – more than 0.5%; voltage beyond the range of 230V;
– natural disasters, fire, external objects, liquids, animals or insects getting into the working units and devices;
– mechanical damage to the frame, glass, and adjustable supporting legs.
The warranty obligations not cover the consumables (light lamps, starters, and chokes) and the installation, adjustment and maintenance work specified in this Operation  Manual.
The manufacturer reserves the right to make modifications to the structure or manufacturing process which do not imply the obligations to change or improve any devices  manufactured earlier.
These warranty obligations do not limit the statutory consumer rights.
Please contact the authorized companies (Suppliers or Vendors) or their service centers regarding any matters related to maintenance and spare parts purchase.

INTENDED USE

3.1. GENERAL INSTRUCTIONS
This Operation Manual contains the information required for proper operation and maintenance of the display case during its direct use.
The service life of the product and its operational safety depends on compliance with the operation regulations.

3.2. SAFETY PRECAUTIONS
The product meets the safety requirements according to Customs Union Technical Regulations TR CU 004/2011 “On Safety of Low Voltage Equipment” (Decision of Commission of the Customs Union No. 768 dated August 16, 2011), Customs Union Technical Regulations TR CU 010/2011 “On Safety of Machinery and Equipment” (Decision of Commission of the Customs Union No. 823 dated October 18, 2011), and Customs Union Technical Regulations TR CU 020/2011 “Electromagnetic Compatibility of Technical Equipment” (Decision of Commission of the Customs Union No. 789 dated December 09, 2011).
In terms of protection against electric shock, the product belongs to protection class I according to GOST IEC 60335-1.
Protection degree of equipment provided by enclosures is IP20.
This appliance is not intended for use by persons (including children) with impaired physical, sensory or mental capabilities, or lack of experience or knowledge, unless they  are supervised or have been given instruction concerning the use of the appliance by the person responsible for their safety. Keep children away from playing with the  product.
DO NOT STORE EXPLOSIVE SUBSTANCES AND OBJECTS SUCH AS AEROSOL SPRAY-CANS WITH FLAMMABLE MIXTURES INSIDE THE PRODUCT.
WARNING! The device must be connected to the supply network via the dual protection automatic switch.
Display case power cord must be plugged into the socket with grounding contact which is connected with supply mains earth wire.
DO NOT CONNECT THE DISPLAY CASE VIA THE EXTENSION CORDS WITHOUT EARTH WIRE OR IF WIRE CROSS-SECTION IS LESS THAN 1.5 SQ.  MM.
WARNING! Damaged power cord ПВС-ВП can be replaced only by the maintenance (repair) service or similar qualified person.
DO NOT OPERATE THE DISPLAY CASE WITH CRACKED OR BROKEN GLASS.
Failure to comply with the above requirements waives the manufacturer’s responsibility for electrical safety.
In case of any malfunctions in the electrical part (wire insulation fault, broken grounding wire etc.), the operating personnel must immediately shut the product down pulling  the power cord plug out of the socket and call for a mechanical engineer.
IT IS ABSOLUTELY FORBIDDEN FOR THE OPERATING PERSONNEL TO REPAIR AND ADJUST THE REFRIGERATING UNIT.
WARNING! When dismantling and repairing the refrigeration system elements, do not allow the refrigerant to leak into atmosphere.

3.3. PRODUCT INSTALLATION
Unpack the product, check the scope of delivery.
Assemble the display case according to the diagram, place it horizontally using jack bases.
Normal operation requires installation of the display case at least 2 m away from the heaters.
Do not operate the display case under direct sunlight, air flow from air conditioners, fans and heaters.
SOME PARTS HAVE PROTECTIVE COVERING (FILM) WHICH CAN BE REMOVED IF NEEDED.
Wash internal and external surfaces of the display case with a neutral detergent and dry with a soft cloth.

3.4. OPERATION PROCEDURE
WARNING! After the display case was transported or stored at freezing temperatures, keep it at room temperature (not less than 12°С) for 24h. The connection of the cold  device to the net may lead to compressor locking and device failure.
Plug the power cord into the socket.
Install the key switches located on display case control panel into position ‘1’. After this, the indicator lamps of the switches should light up, the display case lighting turn on  and the luminous signs on the controller display flash. In 5 seconds, the display shall show the current temperature in the interior volume. The user can set the required  temperature in the interior volume on the controller display. Other controller parameters are set at the manufacturing plant. To change them, it is necessary to call for the refrigerating equipment operation and repair serviceman.
After starting the unit, and upon reaching the desired temperature, load the display case with the products precooled down to the internal enclosure temperature distributing  them evenly on the trays. The height of product display for demonstration must not be more than 150 mm and the distance to the display case wall along the perimeter must  not be less than 40 mm.
ATTENTION! The glass shelf must be used for displaying the products which do not require cooling. Use the additional storage space for short-term storage of goods  which do not require cooling down to the refrigerated enclosure temperature.
Shelf load must not exceed 3 kg per a meter of the distributed load.
Do not block the air conduits.
If the above requirements are not met, the air circulation is blocked, the performance of the product deteriorates, which may lead to the damage of food products.
The product compressor works in cycles turning off when the preset temperature is reached and turning on when it increases by 3-4 ºС.
Thus, air temperature in certain spots of the refrigerated enclosure may rise briefly and differ from controller readings, which does not constitute a defect.
During its operation, the compressor regularly stops for the evaporator to thaw. At the time of thawing, the temperature in the refrigerated enclosure may rise, which does not  constitute a defect.
Rainy or humid weather may cause condensation in the display case. This is not a malfunction. In this case, wipe the display case with a soft cloth from time to time.
The main signs of refrigerated display normal operation are the following:
– the temperature in the internal enclosure matches the preset one;
– the refrigerating unit is operating in cycles.

TROUBLESHOOTING

If there is any malfunction, immediately disconnect the display case from the supply mains by pulling the power cord plug out of the socket and call for a mechanical engineer from the specialized service company authorized by the equipment supplier (vendor).
For troubleshooting, refer to Table 2.
WARNING! All work must only be performed after disconnecting the display case from the power supply net by pulling the power cord plug from the socket.
Table 2. List of potential malfunctions and their repair

Malfunction, symptoms and additional signs Probable reason Repair

1.Refrigerated display does not work, no network key- operated switch indication.| No power supply to the key- operated switch terminals.| Check power cord condition and repair, if necessary.
Check voltage in the supply mains.
2.Refrigerated display is operating continuously or for a long time.| Warm products loading.| Avoid loading with hot and warm products. Decrease product loading frequency.
3. The preset temperature is not maintained in  display case internal enclosure.| Evaporator is covered with thick ice layer.| Defreeze the evaporator by disconnecting the display case from the  supply mains (if there is a heating element – by forced defrosting)  and having removed the products beforehand.
Very high ambient temperature.| Display case shall be operated at ambient temperature of not more  than +25°С.
Air circulating is blocked because of the  condenser soiling.|  Check air access into the fans. Clean the condenser.

3.6. STORAGE REGULATIONS
The product must be stored packed in the room or under shelter at air temperature not lower than minus 35°С.
Guaranteed storage period is up to 6 months.

3.7. TRANSPORTATION
The packed device may be transported by any kind of transport except for the air transport.
When transporting, provide the protection against mechanical damage. Avoid making sudden jerks and stops.
Placement and fixing of the packed box in transport must provide its stable positioning and exclude the possibility of displacement during transportation.
DO NOT TURN OVER THE BOXES! HANDLE ONLY UPRIGHT!

3.8. GUIDELINES ON REMOVAL AND DISPOSAL OF WASTE AND ENVIRONMENTAL PROTECTION
The local environmental protection regulations shall be taken into consideration and complied with. Avoid ingress of water polluting substances into water bodies, soil, or  sewage system.
Please promptly resolve the problem of waste collection and disposal without any damage to the environment (ground water and soil). The waste must be disposed of in  accordance with existing local waste recycling regulations.
When preparing and shipping the device for disposal, display case components must be disassembled and sorted by material they are made from.

MAINTENANCE

4.1. GENERAL INSTRUCTIONS
The equipment must have two types of maintenance: daily in the course of operation and regular maintenance performed by the specialized company authorized by the  equipment supplier (vendor).
Daily maintenance of equipment includes the monitoring of:
– internal enclosure temperature;
– condensate discharge system (water absence inside the product).
During the operation, the equipment must be kept clean. When cleaning, avoid the use of abrasive and corroding detergents.
WARNING! Before cleaning, turn the product off by pulling the power cord plug from the socket and remove the food from the internal enclosure!
Regular maintenance is performed according to the annual schedule made by the center which provides technical service before the planned year begins.
Regular maintenance includes a range of operations performed at least once every three months regardless of the device technical state at the beginning of maintenance.
List of work types for the regular maintenance:
– check if the device is placed and installed properly;
– clean the assemblies from contamination, clean the condenser (if required);
– check if the components and assemblies are properly secured, re-tighten the fasteners;
– brazed piping joints leak test;
– check the reliability of electrical connections, re-tighten contacts on screwed connections;
– test mains voltage, check the earthing availability and status, wires and power cable isolation integrity;
– check display case earth circuit integrity – the resistance between power cord plug earth terminal and any accessible display case metal part shall not exceed 0.1 Ohm;
– check the internal enclosure cooling;
– check the refrigeration system cyclic operation, condenser blower speed, absence of frost deposit on the evaporator;
– check the controller program and readjust the parameters (if required).
Failure to perform scheduled maintenance will cancel the warranty obligations!
Please contact the authorized companies (Supplier or Vendor) or their service centers regarding any questions arising during the devices’ start-up, operation, and maintenance.

Appendix С.

PYEZ1R05J4 (Carl) controller programming parameters

Code| Description| Type| Min| Max| Fact| unit of meas.
PS| Password| F| 0| 99| 22|
-Cl| Calibration of probe I| F| -20| 20| 0.0| °C
St| Temperature set point| F| -50| 90| 2| °C
rd| Controller differential| F| 0| 19| 4| °C
c0| Compressor start delay| C| 0| 99| 0| Min
c2| Min. compressor OFF time| C| 0| 99| 3| \Int
dl| Interval between defrosts| C| 0| 24| 6| hour
dP| Maximum defrost duration| C| 1| 99| 45| Mtn
dd| Dripping time| C| 0| 15| 3| Min
AO| Alarm and fan differential| C| -20| 20| 2.0| °C
AL| Low temperature alarm| C| -50| 90| 0| °C
AH| High temperature alarm| C| -50| 90| 0| °C
Ad| Low and high temperature alarm delay| C| 0| 99| 0| Min
rl| Minimum set point| C| -50| r2| 0| °C
r2| Maximum set point| C| r 1| 90| 10| °C
PYEZ1R05J5 (Carol) controller programming parameters

Code| Description| Typc| Min| Max| Fact| Unit of meas.
PS| Password| 1| 0| 99| 22|
-Cl| Calibration of probe I| 1| -20| 20| 0.0| °C
-C2| Calibration of probe 2| 1| -20| 20| 0.0| °C
St| Temperature set point| F| -50| 90| -3*| °C
rd| Controller differential| F| 0| 19| 3| °C
c0| Compressor start delay| C| 0| 99| 0| Min
c2| Min. compressor OFF time| C| 0| 99| 3| Min
(10| Defrost type (0-heater (temperature), I -gas (temperature), 2- heater (time), 3-gas (time), 4-heater (time+temperature))| C| 0| 4| 0|
dl| Interval between defrosts| C| 0| 24| 5| hour
dt| End defrost temperature| C| -50| 90| 8| °C
dP| Maximum defrost duration| C| 1| 99| 30| Min
dd| Dripping time| C| 0| 15| 3| Min
AO| Alarm and fan differential L| C| -20| 20| 2.0| °C
| Low temperature alarm| C| -50| 90| 0| °C
Al i| High temperature alarm| C| -50| 90| 0| °C
Ad| Low and high temperature alarm delay| C| 0| 99| |
A4| Door in relation to management of fan and lighting: 0-door not in use, I-door open-fan off, 2-door open-lighting on, 3door open-refrigerator shows dO, lighting on/off using push buttons, 4-door open-refrigerator shows EA: compressor off, lighting on/off using push buttons| C| 0| 4| c|
A7| External alarm delay| C| 0| 199| 0| \ Iii:
FO| Fan regulation launch| C| ()| I| 1|
Fl| Fan stop temperature| F| -51)| 90| I0| °c’
F2| Fan stop at compressor stop| C| 0| 2| 0|
F3| Fan delay during defrost| C| ( )| I| 1|
Fd| Delay time after dripping| C| 0| 15| 0| Min
F4| Fan delay| C| I| 99| 3| Sec
F5| Fan-uninterrupted cycle (if F2=2) time on| C| I| 99| 5| Min
F6| Fan-uninterrupted cycle (if F2=2) time off| C| I| 99| 5| Min
rl| Minimum set point| C| -50| r2| -18| °C
r2| Maximum set point| C| r I| 90| 10| °C
HO| IP address setup| C| 0| 207| 1|

  • -3 is the set temperature for GC95 SV;
    -18 – for GC95 SL; +2 – for GC95 SM X.X-2.

ggm gastro -logo

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

ggm gastro User Manuals

Related Manuals