Beghelli 31172 Infinita LED X5 CabLECom Emergency Luminaires
INSTRUCTION
DIMENSION
WIRING
Basic setting (1h-3h) without using App and Central
Wiring with Infinity mode deactivated
Wiring with Infinity mode activated
- Wiring 2.1 The appliance goes into emergency conditions for:
- absence of a general emergency electricity (CableCom);
- absence of a local lighting
- Wiring 2.2 The appliance goes into emergency conditions for:
- absence of a general emergency electricity (CableCom).
Caution: SA luminaires can be set SE only through the App (with smartphone flash on the lamp or with wi-fi with Central CableCom Connect). With Infinity mode on N2 L2 must be connected like wiring 2.1 or 2.2.
Emergency line and local line
For the functioning please refer to the instruction manuals either of the Central CableCom and CableCom Wi-Fi (cod. 20150 – 20151). For the Central configuration the batteries must be sufficiently charged. Be careful NOT to invert the phase and neutral polarity. Maximum connectable lamps 32. Do not connect other types of devices on the power cable / BUS L + N-.
Aailable option
Setting by App CableCom
- A- Open App CableCom (available for download on the App Store and Google Play).
- B- Program the lamp with the “lamp. emerg. ”if used without a control panel or with a cablecom code 20150 control unit. N.B. With central cablecom wifi cod 20151 all configurations and commands can be sent with wifi.
On each device there is a QR code that uniquely identifies the lamp.
POSITION LAMP FOR COVER ENSURE THE PROGRAM
FEATURE
AUTOMATIC TESTS PERIODICITY
- FUNCTIONAL TEST (30 sec) = every 28 days
- AUTONOMY TEST (1h) = every 26 weeks
- Even lamps carry out the autonomy test 1 week after the odd lamps. (0,2,…,8,A,C,E) = even; (1,3,…,9,B,D,F)= odd
LED SIGNALS
- FIXED GREEN BATTERY CHARGED
- FLASHING GREEN BATTERY CHARGING
- ONE RED FLASH BATTERY ERROR DURATION
- TWO RED FLASHES LIGHTING LED ERROR
- THREE RED FLASHES BATTERY DISCONNECTED
OPENING OF THE CABLECOM COMMUNICATION:
Remove and reset the network for less than 3 seconds. The communication remains possible for 2 hours and for 1 min the LED flashes orange to signal the communication opening. The Functional Test, the Functional STOP Test and Rest Mode are controlled by the CableCom App at any time without having to open communication with the device.
WARNINGS – GUARANTEE
- This device shall be used exclusively for the purpose for which it has been designed. Any other use is considered improper and therefore dangerous.
- Rechargeable battery and LED source are non-replaceable type. Contact an authorised technical service centre for any repairs possibly required use only original spare parts. The lacked respect of the above conditions may compromise the safety of the device.
- RG0 risk group at 300cm