IMPORTANT INFORMATION
Before you proceed… We recommend you engage the services of a registered plumber to install this product. For ease of possible future servicing, we also recommend the fitting of conveniently placed isolating valves. In addition to the guide below it is essential that the written information overleaf is carefully read and understood.

Preparation Check Box for Installer

  • Flush the plumbing system befor
  • Once unpacked remove Backnuts and Side Spray installing the kitchein product. Connector ready for installation.

MOUNT FAUCET

MOUNT FAUCET

Ensure the mixer is orientated correctly, levers -\ should rotate to point forward. After removing backnuts, place complete faucet through 01″ holes at 7. 7/8″ centers (do not remove unions from body) – product is fitted with straight unions, distance must be exact. Secure mixer with a suitable faucet wrench.
The kitchen faucet with side spray is supplied with a brass tube protruding out of the bottom of the shank. Please be careful not to damage the end of this tube during installation.
If your mixer has a side spray please follow steps 2,3 & 4 to install correctly, otherwise please connect Hot & Cold water supplies to shanks.

INSTALL HOSE THROUGH DECK ESCUTCHEON

INSTALLATION

Secure side spray unit socket in a suitable position using a faucet wrench.
Place flexible hose through top of side spray unit socket as shown in diagram.

ROTATE RINSE CONNECTOR ON HOSE BEFORE CONNECTING TO UNION

CONNECTION

Install washer “B” to install hose.
Install washer “A” to connect to the cold water supply.
Rotate side spray connector onto end of flexible hose. Do not twist hose. Loosen, but do not remove the gland nut.

ATTACH CONNECTOR

ATTACH CONNECTOR

Important – Do not cut brass tube.
With washer in place on the captive nut push connector onto cold supply 3/8″ tube as shown. Fully tighten captive nut onto shank, taking care not to twist hose.
Tighten the gland nut to fully compress the seals onto brass tube.
With washer in place hold the side spray, screw the flexible hose onto the end of side spray and place into side spray unit socket. Make sure orientation of side spray is correct.

Please Note: Ceramic disc valves are fitted as standard to this mixer. Flow from FULLY OFF to FULLY ON is achieved by rotating the handles a quarter turn.

BEFORE USE

  • Carefully check the installation for leaks.
  • If further building work is to be carried out in the vicinity, cover the tap with a plastic bag to avoid damaging the finish. Please ensure that the installation complies with local plumbing codes.

CARE & MAINTENANCE

Wipe down after use to avoid water spotting and mineral build up.
Occasional cleaning with warm soapy water, followed by a polish with a soft cloth is all that is required to keep the plated finish in good condition.