MEAN WELL DDR-480 Series 480W DIN Rail Type DC to DC Converter Instruction Manual

June 9, 2024
MEAN WELL

MEAN WELL DDR-480 Series 480W DIN Rail Type DC to DC Converter

Features

  • Compliance to BS EN/EN50155 and BS EN/EN45545-2 railway standard
  • Width only 85.5mm
  • 2:1 wide input range
  • -40+80C wide operating temperature
  • 150% peak load capability
  • Current sharing up to 1920W(3+1)
  • DC output adjustable
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Protections: Short circuit/ Overload/Over voltage
    • Over temperature / Input reverse polarity/
    • Input under voltage protection
  • 4KVdc O isolation (Reinforced isolation)
  • DC OK relay contact
  • Remote ON-OFF control
  • Operating altitude up to 5000 meters(Note.6)
  • 3 years warranty

Description

DDR-480 series is a 480W DIN Rail type DC-DC converter with main features including DIN rail-type easy installation, ultra-slim width (85.5mm), 2:1 wide input voltage, fanless design, -40-+80C wide operating temperature, 4KVdc l/O isolation, 150% peak load, current sharing, DC OK, adjustable output voltage and full protective functions. This series of models have various input options: 16.8-33.6V/33.6-67.2V/ 67.2-154V and multiple output options: 12V/24V / 48V and can be used for industrial & railway control, security control, communication system, and other fields. Suitable applications include to DC buck/boost regulator, increasing system insulation level and voltage drop compensation along cable…etc.

Model Encoding

Applications

  • Bus, tram, metro, or railway system
  • Industrial control system
  • Semiconductor fabrication equipment
  • Factory automation
  • Electro-mechanical
  • Wireless network
  • Telecom or datacom system

GTIN CODE

MW Search: https://www.meanwell.com/serviceGTIN.aspx.

SPECIFICATION

MODEL| | DDR-480B-12| DDR-480B-24| DDR-480B-48| DDR- 480C-12| DDR-480C-24| DDR-480C-48| DDR-480D-12| DDR- 480D-24| DDR-480D-48
---|---|---|---|---|---|---|---|---|---|---






OUTPUT

| DC VOLTAGE| 12V| 24V| 48V| 12V| 24V| 48V| 12V| 24V| 48V
RATED CURRENT| 33.4A| 20A| 10A| 33.4A| 20A| 10A| 33.4A| 20A| 10A
CURRENT RANGE| 0 ~ 33.4A| 0 ~ 20A| 0 ~ 10A| 0 ~ 33.4A| 0 ~ 20A| 0 ~ 10A| 0 ~ 33.4A| 0 ~ 20A| 0 ~ 10A
RATED POWER| 400.8W| 480W| 480W| 400.8W| 480W| 480W| 400.8W| 480W| 480W
PEAK

Note.5

| CURRENT 5sec.| 50.1A| 30A| 15A| 50.1A| 30A| 15A| 50.1A| 30A| 15A
POWER 5sec.| 12Vo: 601.2W, 24Vo / 48Vo : 720W
RIPPLE & NOISE (max.) **Note.2| 100mVp-p| 120mVp-p| 150mVp-p| 100mVp-p| 120mVp-p| 150mVp-p| 100mVp-p| 120mVp-p| 150mVp-p
VOLTAGE ADJ. RANGE| 12 ~ 14V| 24 ~ 28V| 48~ 56V| 12 ~ 14V| 24 ~ 28V| 48~ 56V| 12 ~ 14V| 24 ~ 28V| 48~ 56V
VOLTAGE TOLERANCE Note.3| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 500ms, 60ms
HOLD UP TIME (Typ.)**| Please refer to page 6 hold up time (Load de-rating curve )



INPUT

| VOLTAGE RANGE

Note.4

| CONTINUOUS| 16.8 ~ 33.6Vdc| 33.6 ~ 67.2Vdc| 67.2 ~ 154Vdc
100ms| 14.4 ~ 16.8Vdc| 28.8 ~ 33.6Vdc| 66 ~ 67.2Vdc
EFFICIENCY (Typ.)| 90%| 91%| 90.5%| 91%| 92%| 92%| 91%| 92%| 93%
DC CURRENT (Typ.)| 23A @24Vdc| 11.2A @48Vdc| 5A @110Vdc
INRUSH CURRENT (Typ.)| 30A
INTERRUPTION OF VOLTAGE SUPPLY| EN50155: 2017-B/C/D type comply with S2 level (10ms)@ full load




PROTECTION

| OVERLOAD **Note.5| Normally works within 150% rated output power for more than 5 seconds and then constant current protection 105~135% rated output power with auto-recovery
OVERVOLTAGE| 14.4 ~ 17.5V| 28.8 ~ 35V| 57.6 ~ 65V| 14.4 ~ 17.5V| 28.8 ~ 35V| 57.6 ~ 65V| 14.4 ~ 17.5V| 28.8 ~ 35V| 57.6 ~ 65V
Protection type: Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down the o/p voltage, and re-power on to recover
REVERSE POLARITY| By internal, MOSFET, no damage, recovers automatically after fault condition is removed
UNDER VOLTAGE LOCKOUT**| 24Vin (B – type): Power ON≥16.8V,

OFF≤16.5V

| 48Vin (C – type) : Power ON≥33.6V,

OFF≤33V

| 110Vin (D – type): Power ON≥67.2V,

OFF≤65V


FUNCTION

| DC OK REALY CONTACT RATINGS (max.)| 30Vdc/1A resistive load
CURRENT SHARING| Up to 1920W (3+1 units). Please refer to the Function Manual
REMOTE ON-OFF CONTROL| Please refer to the Function Manual



ENVIRONMENT

| WORKING TEMP.| -40 ~ +80℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 5 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85, 5 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 55℃)
VIBRATION| Component:10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC61373
OPERATING ALTITUDE Note.6| 5000 meters / OVCⅡ







SAFETY & EMC

(Note 7)

| SAFETY STANDARDS| UL 62368-1, IEC 62368-1, AS/NZS 62368-1, EAC TP TC 004 approved
WITHSTAND VOLTAGE| I/P-O/P:4KVdc  I/P-FG:2.5KVdc  O/P-FG:0.71KVdc
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500Vdc / 25℃/ 70% RH



EMC EMISSION

| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032 (CISRP32)| Class A
Radiated| BS EN/EN55032 (CISRP32)| Class B
Voltage Flicker| BS EN/EN61000-3-3| —–
Harmonic Current| —–| —–




EMC IMMUNITY

| BS EN/EN55035
Parameter| Standard| Test Level / Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 3, 6KV contact; criteria A
Radiated| BS EN/EN61000-4-3| Level 3, 10V/m ; criteria A
EFT / Burst| BS EN/EN61000-4-4| Level 3, 2KV ; criteria A
Surge| BS EN/EN61000-4-5| Level 3, 1KV/Line-Line ;Level 3, 2KV/Line-Line-FG ;criteria A
Conducted| BS EN/EN61000-4-6| Level 3, 10V ; criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, 30A/m ; criteria A
RAILWAY STANDARD| Compliance to BS EN/EN45545-2 for fire protection ; Meet BS EN/EN50155 / IEC60571 including IEC61373 for shock & vibration, BS EN/EN50121-3-2 for EMC


OTHERS

| MTBF| 750.3K hrs min.        Telcordia SR-332 (Bellcore);  101.7K hrs min.         MIL-HDBK-217F (25℃)
DIMENSION| 85.5125.2129.2mm  (WHD)
PACKING| 1.375Kg;8pcs/12Kg/0.95CUFT
**NOTE**| 1. All parameters NOT specially mentioned are measured at normal input (B:24Vdc, C:48Vdc, D:110Vdc ), rated load, and 25C of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance: includes set up tolerance, line regulation, and load regulation.
4. Derating may be needed under low input voltage. Please check the derating curve for more details.
5. 150% 5 seconds, please refer to peak loading curves.
6. The ambient temperature derating of 3.5 C/1000m with fanless models and of 5 C/100Om with fan models for operating altitude higher than2000m(6500ft).
7. The power supply is considered an independent unit, but the final equipment still needs to re-confirm that the whole system complies with
the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com.
Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx.

Block Diagram

Derating Curve

Output derating VS Input Voltage

Peak Loading

DC OK Relay Contact

Contact Close PSU turns on/DC OK.
Contact Open PSU turns off/DC Fail.
Contact Ratings (max.) 30V/1A resistive load.

Function Manual

Current sharing

  1. Parallel operation is available by connecting the units shown below (P+, and P- are connected mutually in parallel) :
  2. The voltage difference among each output should be minimized so that less than 0.2V is required.
  3. The total output current must not exceed the value determined by the following equation (Output current at parallel operation) =(The rated current per unit) x (Number of units) x 0.9.
  4. In parallel operation 4 units are the maximum, please consult the manufacturer for other applications.
  5. When in parallel operation, the minimum output load should be greater than 3% of the total output load. (Min. load > 3% rated current per unit x number of unit).

Remote ON-OFF Control

  • The power supply can be turned ON-OFF by using the “Remote ON-OFF” function.
Remote ON-OFF (TB1 PIN2,4) Output Status
Open or 5.5 ~ 10VDC power supply ON
Short or 0 ~ 0.8VDC power supply OFF

Input Fuse

There is one fuse connected in series to the positive input line, which is used to protect against the abnormal surge. The fuse specifications of each model are shown below.

Type Fuse Type Reference and Rating
B Time-Lag Conquer MST, 10A, 250V *5
C Time-Lag Conquer MST, 8A, 250V *3
D Time-Lag Conquer MST, 6.3A, 250V *2

Input Under-Voltage Protection
If the input voltage drops below Vimin, the internal control IC shuts down and there is no output voltage. It recovers automatically when the input voltage reaches above Vimin, please refer to the curve below.

Input Reverse Polarity Protection
There are two MOSFETs connected in series to the negative input line. If the input polarity is connected reversely, the MOSFETs open and there will be no output to protect the unit.

Inrush Current
Inrush current is suppressed by a resistor during the initial start-up, and then the resistor is bypassed by MOSFETs to reduce power consumption after accomplishing the start-up.

Hold-up Time

EN50155:2017 version- B/C/D type complies with S2 level (10ms) @ full load, please refer to the table and curves shown below for the hold-up time specification.

Load

Model

| 100% load| 70% load| another load
---|---|---|---
B type (24Vin)| 10ms min.| 16ms min.| figure 1,2,3
C type (48Vin)| 11ms min.| 17ms min.| figure 4,5,6
D type (110Vin)| 16ms min.| 24ms min.| figure 7,8,9

Efficiency vs Load & Vin Curve

The efficiency vs load & Vin curves of each model are shown as below.

Immunity to Environmental Conditions

Test method Standard Test conditions Status
Cooling Test EN 50155 section 12.2.3 (Column 2, Class TX)

EN 60068-2-1

| Temperature: -40℃ Dwell Time: 2 hrs/cycle| No damage

Dry Heat Test

| EN 50155 section 12.2.4 (Column 2, Class TX)

EN 50155 section 12.2.4 (Column 3, Class TX & Column 4, Class TX)

EN 60068-2-2

| Temperature: 70℃ / 85℃ Duration: 6 hrs / 10min|

PASS

Damp Heat Test, Cyclic

| EN 50155 section 12.2.5

EN 60068-2-30

| Temperature: 25℃~55℃ Humidity: 90%~100% RH Duration: 48 hrs|

PASS

Vibration Test

| EN 50155 section 12.2.11

EN 61373

| Temperature: 19℃ Humidity: 65%

Duration: 10 mins

|

PASS

Increased Vibration Test

|

EN 50155 section 12.2.11

EN 61373

| Temperature: 19℃ Humidity: 65%

Duration: 5 hrs

|

PASS

Shock Test

|

EN 50155 section 12.2.11

EN 61373

| Temperature: 21± 3℃

Humidity: 65 ± 5% Duration: 30ms*18

|

PASS

Low-Temperature Storage Test

|

EN 50155 section 12.2.3 (Column 2, Class TX)

EN 60068-2-1

|

Temperature: -40℃ Dwell Time: 16 hrs

|

PASS

Salt Mist Test

|

EN 50155 section 12.2.10 (Class ST4)

|

Temperature: 35℃±2℃ Duration: 48 hrs

|

PASS

EN45545-2 Fire Test Conditions

Test Items Hazard Level
Items Standard HL1 HL2

R22

|

Oxygen index test

| EN 45545-2:2013

EN ISO 4589-2:1996

|

PASS

|

PASS

|

PASS

Smoke density test

| EN 45545-2:2013

EN ISO 5659-2:2006

|

PASS

|

PASS

|

PASS

Smoke toxicity test

| EN 45545-2:2013 NF X70-100:2006|

PASS

|

PASS

|

PASS

R24

|

Oxygen index test

| EN 45545-2:2013

EN ISO 4589-2:1996

|

PASS

|

PASS

|

PASS

R25

|

Glow-wire test

| EN 45545-2:2013

EN 60695-2-11:2000

|

PASS

|

PASS

|

PASS

R26

|

Vertical flame test

| EN 45545-2:2013

EN 60695-11:2003

|

PASS

|

PASS

|

PASS

Mechanical Specification

Installation Instruction

This series fits DIN rail TS35/7.5 or TS35/15. For installation details, please refer to the Instruction manual.