inELs Converter EBM DALI/DMX Instructions

June 9, 2024
inELS

logo-inels

inELs Converter EBM DALI/DMX

inELs-Converter-EBM-DALI-DMX-PRODUCT

Lighting control

  • The unit EMDC-64M is designed to control DALI electronic ballasts and DMX receivers from the iNELS system.
  • EMDC-64M enables control of up to 64 independent electronic bal-lasts DALI (Digital Addressable Lighting Interface) for fl uorescent lamps, LEDs and other light sources.
  • EMDC-64M also enables connection of up to 64 DMX receivers (Digi-tal MultipleX).
  • Control from iNELS BUS System via EBM BUS.
  • DIP switches on the front panel to select the control interface (DALI/DMX).
  • Addressing of DALI ballast units can be done via the central unit and iDM3 software or via MINI USB on the front panel of the EMDC-64M and DALI Confi gurator software.
  • The required functionality is set in user project in iDM3 software.
  • The unit EMDC-64M is powered from the mains voltage 230 V AC.
  • DALI BUS power supply is 16 V/250 mA via an EMDC-64M unit.
  • The system BUS EBM is galvanically separated from the BUSes DALI/DMX. Terminals for connecting the DALI BUS are equipped with short circuit and surge protection.
  • It is possible to connect up to 8 EMDC-64M units to one EBM BUS.
  • If this concerns the last unit on a system BUS EBM, it is necessary to ter-minate the wire with a resistor with nominal resistance of 120 Ω. The resistor is inside the unit, termination is made by shorting neighboring terminals TERM and EBM+.
  • The BUS DMX must be terminated at its end by a resistor with nominal resistive value 120 Ω. The resistor for DMX BUS termination is on the side of the EMDC- 64M inside the unit, termination is performed by shorting adjacent terminals TERM and A.
  • Updating the fi rmware of the EMDC-64M can be done through the central unit adn software iDM3 or via MINI USB on the front panel and EMDC-64M Flasher software. Updating through MINI USB must be done while system BUS EBM is disconnected.
  • When confi guring DALI addresses two types are necessary to distin-guished:
    • MASTER – this group includes sensors and detectors and one DALI branch can connect up to 4 DALI MASTER units
  • lighting intensity sensor DLS3-1
  • motion detector DMD3-1
    • SLAVE – electronic lighting ballast
  • EMDC-64M in 3-MODULE design is designed for mounting in a control panel on a DIN rail EN60715.

Connection

inELs-Converter-EBM-DALI-DMX-FIG-1

Technical parameters

  • EMDC-64M

Power supply

Supply voltage/tolerance/

Rated current:

| AC 230 V (50 – 60 Hz)/

-15/+10 %/max. 100 mA

---|---
DALI power supply:| 16 V, 250 mA
Dissipated power:| max. 3 W

Communication

Input interface: EBM BUS (RS485 communication)
Output interface: DALI (max. 64 ballasts)

DMX (max. 32 receivers, with repeater up to 64)

Indication
Power supply:| green LED Un
Error surge or short DALI:|

illuminated red LED ERR

Indication of unit status:| LED DALI/DMX (see iNELS installation handbook)
Operating conditions
Relative humidity:| max. 80 %
Operating temperature:| -20 °C to +55 °C
Storage temperature:| -30 °C to +70 °C
Protection degree:| IP20 device, IP40 mounting in the switchboard
Control device purpose:| operating control device
Control device construction:| individual control device
Characteristic of automatic action:| 2.5 kV
Overvoltage category:| II.
Pollution degree:| 2
Operating position:| vertical
Installation:| into switchboard on DIN rail EN60715
Implementation:| 3-MODULE

Dimension and weight

Dimension: 90 x 52 x 65 mm
Weight: 140 g