systemair SPM-250 Measuring Iris Damper with Bulb Instructions

June 2, 2024
systemair

systemair SPM-250 Measuring Iris Damper with Bulb
systemair SPM-250 Measuring Iris Damper with Bulb

Description

Systemair SPM iris damper with more choking ability.

Function

The SPM is an iris damper for measuring and adjusting the air flow, with more choking ability than the SPI. The SPM has the following specifications: low noise level, centrically formed air flow and fixed test points for precise measurements. Accessorie, Access door RLL, is recommended for use with SPM. Available in sizes ø 160-400, but not for size 300.

Design

The damper is manufactured from galvanised sheet steel and is fitted with an airtight rubber seal. Size ø 160-400.

How to use for exhaust air

This device can be used for exhaust air.

Mounting

The SPM adjustment damper must be installed in accordance with the distances required to minimise air-flow deviation. Reducing or enlarging the duct to the next duct size does not require any specified distances for minimising deviation. The SPM enables the taking of precise air-flow measurements at all points including points close to duct deviations such as T junctions and bends, and points in front of other supply-air devices.

Protective distance

before bends 1 x D
after “ 1 x D
before T-pipes 3 x D
after “ 1 x D
before supply-air devices 3 x D

Accessories

Dimensions

  cid C (JD
SPM 160 159 60
SPM 200 199 62
SPM 250 249 62
SPM 300 299 63
SPM 315 314 63
SPM 400 399 70


Dimensions

Diagram

Mid-frequency band, Hz

    63 125 250 500 1K 2K 4K
SPM 160 9 6 1 -5 -11 -18 -27
SPM 200 9 5 1 -5 -12 -17 -24
SPM 250 6 1 -4 -3 -12 -17 -24
SPM 315 3 1 -4 -4 -9 -14 -23
SPM 400 3 1 -4 -4 -9 -13 -19
Tolerance   ±6 ±5 ±2 ±2 ±2 ±2 ±3

Diagram

systemair

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals