Systemair ARFEC4220E24 Recessed Air Curtain Arden User Guide
- June 1, 2024
- systemair
Table of Contents
Systemair ARFEC4220E24 Recessed Air Curtain Arden
Technical Parameters
Installation
|
---|---
Type of installation| Horizontal|
Recommended installation height| 4.2| m
Nominal data| |
Colour casing| Traffic white|
Colour casing, RAL| RAL 9016|
Colour, outlet grilles| Telegrey 2|
Colour outlet grilles, RAL| RAL 7046|
Enclosure class| IP20|
Ambient working temperature (dry conditions)| -20 to 30| °C
Dimensions and weights| |
Length| 2,067| mm
Height| 296| mm
Depth| 851| mm
Weight| 96| kg
Airflow| |
Airflow| 1.3611; 1.1389; 0.6944| m³/s
Sound data| |
Sound level
Sound pressure (LpA)
Sound power (LWA)
Conditions sound level
| 62; 57; 44
Conditions: The distance to the unit is 5 metres. Directional
factor: 2. Equivalent absorption area: 200 m².
77
Measurements according to ISO 27327-2: 2014, Installation type E.
| dB(A)
dB(A)
Motor/control supply|
---|---
Control/motor supply| 230| V|
Phases, motor| 1~| |
Control/motor current, 50 Hz| 6| A|
Input power (P1), motor 50Hz| 1,015| W|
Control/motor current, 60 Hz| 6| A|
Input power (P1), motor 60Hz| 1,015| W|
Enclosure class, motor| IP20| |
Insulation class| B| |
Electric heat| | |
Current heating| 33.8; 23; 11| A|
Voltage heating| 400| V|
Input power, heater| 24; 16; 7.8| kW|
Phases| 3~| |
Temperature rise, maximum heat output, highest airflow| 14| °C|
Temperature rise, maximum heat output, middle airflow| 17| °C|
Temperature rise, maximum heat output, lowest airflow| 28| °C|
| | |
Parameter| | |
Output| | | 24.00 kW
Airflow| | | 1.36 m³/s
Inlet air temperature| | | 20.0 °C
Outlet air temperature| | | 34.7 °C
Inlet air humidity| | | 70 % r.H
Outlet air humidity| | | 30 % r.H
Accessories
- AR42XTT20 Air extension (88062)
- FCDA Control for air curtain (74684)
- FCSA Control for air curtain (74685)
- PA34TR20 Threaded bars (18057)
- FCBA Control for air curtain (74687)
- FCPA Control for air curtain (74686)
- PA34CB20 Ceiling brackets (18060)
- PA34VD20 Vibration damper (18066)
Documents
- Catalogue pages Arden 4200
- manual Arden 4200
- Declaration of Conformity ARFEC4200
- UKCA Declaration ARFEC4200
- Exploded view ARFEC42
FAQ
-
Where can I find the product link for ARFEC4220E24 Air curtain Arden?
You can find the product at Systemair. -
What is the recommended installation height for the ARFEC4220E24 Air curtain Arden?
The recommended installation height is 4.2 meters. -
What are the sound levels for the ARFEC4220E24 Air curtain Arden?
-
The sound levels are 62, 57, and 44 dB(A) under standard conditions.
How can I get in touch with Puravent for more information?
You can call them at 0845 6880112 or email info@adremit.co.uk.
Contact Information
Get In Touch
- Call: 0845 6880112
- Email: info@adremit.co.uk
- Our Address: Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH
Article name: ARFEC4220E24 Air curtain Arden | Product link: https://shop.systemair.com/en-GB/productPermalink?p=543528 | Item Number: 230292 | Document type: Product card | Created at: 19.02.2024 | Generated by: Systemair Online Catalogue | Language: English.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>