systemair 92140 KVK Insulated Duct Fans Owner’s Manual

May 15, 2024
systemair

systemair 92140 KVK Insulated Duct Fans

systemair-92140-KVK-Insulated-Duct-Fans-product

Product Information

Specifications:

  • Article Name: KVK Slim 100
  • Item Number: #92140
  • Operating Mode: 230V 1~ 50Hz
  • Construction: AluZinc 185, corrosion class C4
  • Insulation: Rockwool with surface liner
  • Motor Types: AC or high efficient EC external rotor motors
  • Control Options: Built-in potentiometer for EC motors, 0-10V signal control; 5-step or stepless speed regulator for AC motors

Product Usage Instructions

Flexibility:

The KVK Silent fans are suitable for both supply and extract air applications and can be installed in any position, making them versatile for commercial and domestic use.

Performance:

The high-performance impeller and external rotor motor ensure efficient operation with minimal power consumption and maximum efficiency.

Certifications:

The construction of the casing and thermal insulation allows for both indoor and outdoor use, minimizing maintenance needs and enabling long continuous operation.

Noise Reduction:

The insulated casing design effectively reduces noise levels to ensure quiet operation in various settings.

Ecodesign Compliance:

The product is Ecodesign (ErP) compliant, meeting environmental standards for energy efficiency.

FAQ

Q: Can the KVK Slim/Silent fans be used for outdoor installations?

A: Yes, the construction permits both indoor and outdoor use, with corrosion resistance and reliable casing design.

Q: How can the speed of the fans be controlled?

A: EC motors have a built-in potentiometer for adjustment or can be controlled by an external signal (0-10V). AC motors can be regulated using a 5-step or stepless speed regulator.

Q: Are the fans easy to maintain?

A: Yes, the service cover allows for easy access to clean the fans, minimizing maintenance requirements.

KVK Insulated duct fans

Insulated radial fan for limited spaces

  • Design for limited installation height
  • Very low noise, acoustic and thermal insulation Corrosion resistance of casing C4
  • Indoor and outdoor installation
  • Easy maintenance, service cover

Find more details in our online catalogue

  • Flexibility
    The KVK Silent fans combine a high efficient fan and casing with perfect acoustic and thermal insulation capacity. The KVK Silent fans are intended to use for supply or extract air, designed to be installed in any position. This ensures that the fans can be used in a variety of commercial and domestic applications.

  • Reliability
    Construction of casing and thermal insulation
    permits outdoor and indoor use. The combination of reliable casing and motor construction ensures to minimize the need for maintenance of the fans and allows long continuous operation. Thanks to service lid it is easy to clean.

  • Performance
    High performance impeller together with high efficient external rotor motor are designed to ensure high-level performance to minimize power consumption and maximize efficiency.

  • Noise
    Partly or fully insulated casing (depends on model) is perfectly designed to reduce noise mainly to surrounding and partly to inlet/outlet.

Certifications

Features

  • Construction
    Casing of all KVK fans made of AluZinc 185, corrosion class C4.
    KVK Slim has acoustically/thermally insulated lid. KVK Silent has acoustically/thermally insulated lid and casing. Insulation made of rockwool and has surface liner that prevents the migration of fibers into the airstream. Casing has connection spigot with rubber seals and is equipped with an external terminal box with protection class IP54.

  • Motor protection
    Sizes 100-315 mm with AC motors have integrated thermal protection with manual (electrical) reset.
    Sizes 355-500 mm with AC motors have prewired integral thermal contacts TK with leads to external motor protection device.
    Fans with EC motors have an integrated electronic thermal protection, including locked-rotor protection and soft-start.

  • Impeller
    KVK Slim/Silent fans use backward curved radial impeller. These are from lightweight, hard-wearing fiberglass
    reinforced polyamide (for sizes up to 250) or reinforced polypropylene, dynamically balanced and paired with corresponding external rotor motors.

  • Control
    EC motor with built-in potentiometer to adjust working point can be also controlled by external signal 0-10V.
    AC motor can be controlled by 5-step or stepless speed regulator.
    KVK fans can be demand controlled via additional accessories like sensors and controllers for CO2, temperature, humidity, presence indication and VAV.

  • Motor
    Depending on type, fans are equipped with AC or high efficient EC external rotor motors. All motors are suitable for 50Hz and 60Hz.

  • Installation
    KVK Slim/Silent fans can be installed in any position indoor and outdoor. Circular spigot with rubber seals is perfectly designed to connect to the duct by using fast clamps preventing vibration to the duct. A service cover with screw connection and hinges with pins make cleaning and service easy.

Technical parameters

Nominal data|
---|---
Voltage (nominal)| 230| V
Frequency| 50| Hz
Phases| 1~|
Input power| 78| W
Input power kW| 0.078| kW
Input current| 0.346| A
Impeller speed| 2,438| rpm
Air flow| max 0.0778| m³/s
Capacitance of capacitor| 2| µF
Temperature of transported air| max 60| °C
Max temperature of transported air, when speed controlled| 60| °C

systemair-92140-KVK-Insulated-Duct-Fans-fig-2

Performance

Performance curve

systemair-92140-KVK-Insulated-Duct-Fans-fig-3

Hydraulic data|
---|---
Required air flow| 0.04 m³/s
Required static pressure| 208 Pa
Working air flow| 0.04 m³/s
Working static pressure| 208 Pa
Air density| 1.204 kg/m³
Power| 73.2 W
Fan control – RPM| 2,551 rpm
Current| 0.30 A
SFP| 1.710 kW/m³/s
Control voltage| 230.0 V
Supply voltage| 230 V
Sound power level| | 63| 125| 250| 500| 1k| 2k| 4k| 8k| Total
---|---|---|---|---|---|---|---|---|---|---
Inlet| dB(A)| 49| 62| 58| 55| 52| 47| 43| 38| 64
Outlet| dB(A)| 57| 62| 59| 61| 63| 57| 50| 45| 68
Surrounding| dB(A)| 21| 36| 41| 39| 42| 37| 28| 23| 47
Sound pressure level at 3m (20m² Sabine)| dB(A)| –| –| –| –| –| –| –| –| 40
Sound pressure level at 3m free field| dB(A)| –| –| –| –| –| –| –| –| 26

systemair-92140-KVK-Insulated-Duct-Fans-fig-4

Basic unit|
---|---
ErP compliance| 2016|
SEC Average| -10| kWh/(m².a)
SEC Cold| -26.4| kWh/(m².a)
SEC Warm| -0.6| kWh/(m².a)
SEC Class| E|
Unit category| RVU|
Unit type| UVU|
Drive| External MSD or VSD|
Heat recovery type| None|
Temperature ratio (UVU)| Not applicable|
qv max| 223| m³/h
P max| 75| W
Sound power (LWA)| 39| dB(A)
qv ref| 0.044| m³/s
Ps ref| 50| Pa
SPI| 0.228| W/(m³/h)
CTRL| 1|
MISC| 1.1|
x-value| 1.5|
External Leakage| 5| %
AEC average| 285.1| kWh
AHS Cold| 285.1| kWh
AEC warm| 285.1| kWh
AHS Average| 1,715.2| kWh/a
AHS Cold| 3,355.3| kWh/a
AHS Warm| 775.6| kWh/a
Units with local demand control| |
---|---|---
ErP compliance| 2018|
SEC Average| -24.6| kWh/(m².a)
SEC Cold| -51.6| kWh/(m².a)
SEC Warm| -9.1| kWh/(m².a)
SEC Class| C|
Unit category| RVU|
Unit type| UVU|
Drive| External MSD or VSD|
Heat recovery type| None|
Temperature ratio (UVU)| Not applicable|
qv max| 224| m³/h
P max| 75| W
Sound power (LWA)| 39| dB(A)
qv ref| 0.0436| m³/s
Ps ref| 50| Pa
SPI| 0.228| W/(m³/h)
CTRL| 0.65|
MISC| 1.1|
x-value| 1.5|
External Leakage| 5| %
AEC average| 149.4| kWh
AEC cold| 149.4| kWh
AEC warm| 149.4| kWh
AHS Average| 2,830| kWh/a
AHS Cold| 5,536.2| kWh/a
AHS Warm| 1,279.7| kWh/a

Dimension

systemair-92140-KVK-Insulated-Duct-Fans-fig-5

 | A| B| C| D| E| øF| G| H| I| J| K
---|---|---|---|---|---|---|---|---|---|---|---
KVK Slim 100| 400| 150| 392| 325| 278| 98| 348| 300| 69| 76| 300
KVK Slim 125| 400| 150| 392| 325| 278| 123| 348| 300| 84| 72| 300
KVK Slim 160| 400| 185| 392| 325| 278| 158| 348| 300| 99| 90| 370
KVK Slim100 EC| 400| 150| 392| 325| 278| 98| 348| 300| 69| 76| 300
KVK Slim120 EC| 400| 150| 392| 325| 278| 123| 348| 300| 84| 72| 300
KVK Slim160 EC| 400| 185| 392| 325| 278| 158| 348| 300| 99| 90| 370

Wiring

Energy class label

systemair-92140-KVK-Insulated-Duct-Fans-fig-7

Accessories

  • Frequency converter FRQ5SE-6A (37421)
  • REE 1 Speed control (5314)
  • REV-3POL/03-7,5kW R/Y (33978)
  • VKK-100 Back draft damper (1623)
  • Frequency converter FRQSE-6A (37419)
  • VBC 125-3 Water heating batt (9839)
  • CB 100-0,6 230V/1 Duct heater (5376)
  • CBMF 100-0,6 230V/1 Duct heate (12241)
  • FFR 100 Filter cassette (1766)
  • FK 100 Fast clamp (1607)
  • LDC 100-600 Silencer (5188)
  • RSK-100 Back draft damper (5597)
  • VBF 100 Water heating battery (1724)
  • IGC-100 Intake grille (76874)
  • RE 1,5 Speed control (5000)
  • REU 1.5 Speed control (5004)
  • SG 100 Protection guard (5606)
  • DTV500A (96807)
  • IGK-100 Wall Grid (1630)
  • CB 100-0,4 230V/1 Duct heater (5288)
  • CBM 100-0,6 230V/1 Duct heater (5479)
  • CWK 100-3-2,5 Duct cooler,circ (30019)
  • FGR 100 Filter cassette (1802)
  • LDC 100-300 Silencer (8180)
  • LDC 100-900 Silencer (5189)
  • VBC 100-2 Water heating batt (5456)
  • VK-10 Louvre shutter (87682)

Documents

INSTALLATIONOPERATION_AND_MAINTENANCE_INSTRUCTION_KV_DUO__KVK_DUOKVK_003EN.PDF COMMISSIONING_RECORD_FANSEN.PDF

Article name: KVK Slim 100 | Product link: https://shop.systemair.com/en- GB/productPermalink?p=400493 | Item Number: 92140 | Variant: 230V 1~ 50Hz | Document type: Product card | Created at: 26.02.2024 | Generated by: Systemair Online Catalogue | Language: English

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

systemair User Manuals

Related Manuals