ION SF6 P2 Instrument User Manual
- June 3, 2024
- ION
Table of Contents
SF6 P2
Instrument User Manual V1.2
Register your instrument online to receive your extended Warranty.
Unrivalled Gas Detection.
ionscience.com
SF6 P2 Instrument
Register your instrument online for extended warranty
Thank you for purchasing your Ion Science instrument.
The standard warranty of your instrument can be extended to up to two years.
To receive your extended warranty, you must register your instrument online
within one month of purchase (terms and conditions apply.)
Visit www.ionscience.com/instrument-registration
Declaration of conformity
Manufacture´s name and address ISM Deutschland GmbH, Laubach 30,
Die ISM Deutschland GmbH the product / ISM Deutschland GmbH
Product name : SF6-Raumluftmonitor / SF6-Roommonitor
Type: SF6 AREACHECK P2
with applicable regulations
Low-Voltage Equipment Directive 73/23/EEC amended by 93/68/EEC
Harmonized standards applied
Safety
EN 61010-1 : 1993 / IEC (CEI) 1010-
Overvoltage category II
Degree of pollution
Electromagnetic compatibility
EN 50082-2: 1995 / VDE 0839 T82-2
ENV 50140 : 1993 / IEC (CEI) 1001-4
ENV 50141 : 1993 / IEC (CEI) 1000-4
ENV 61000-4,2 : 1995 / IEC (CEI) 1000
Level = 2
EN 61000-4-4: 1995 / IEC (CEI) 1000
Level = 3
EN 50081-1 : 1992 / EN 55011 : 1991 / CISPR11
group = 1, Class = B
Date
01.08.2005
Signature
Hr. Becker – Technical Director
Installation
Location
SF6 AREACHECK P2 is designed for indoor wall mounting. Since SF6 tends to sink towards the ground in undisturbed air, we suggest to place it approx. 50 … 60 cm above ground level.
Wiring
Mains power connects to the orange clamp block, according to the designation
printed on the PCB near each clamp.
For an optional audible and/or visible alarm device, a voltage free switchover
relay output is supplied. It is available on the blue 3 position clamp block
in the middle. Contacts are, from left to right: N.O. / COM / N.C.
During normal operation, COM connects to N.O. During an alarm or error
condition, COM disconnects from N.O. and switches over to N.C. The same
applies in case of power failure, and whenever the instrument is taken into
setup mode via the host computer interface via the RS232 connector.
The leftmost 6 position clamp block is provided for network operation.
Physically, the network follows RS485 standards and hence has three wires
named A, B, and GND. Their positions are marked on the PCB next to the clamps.
They must be wired to the corresponding pins on the SF6 NETWORKCONTROLLER
P2NC. Double clamps are provided for each wire for easy “daisy chaining” of
several instrument.
Network diagram
Wiring details
Operation
Auto-zero at startup
To precisely determine SF6 concentration, SF6 AREACHECK P2 requires a
reference value representing clean air. This reference value is taken and
stored whenever the instrument is powered up or reset. You should therefore
make sure that power up takes place under clean air conditions.
A fresh reference value is also taken after manual reset via the key switch.
Therefore, after each manual reset, the instrument will temporarily only
respond to SF6 concentrations exceeding the level that was present at the time
of manual reset. This will avoid the next measuring cycle to trigger an
undesired, new alarm. The reference value will auto-adapt to falling SF6
concentrations, so after once meeting a clean air condition, SF6 AREACHECK P2
will automatically return to full sensitivity.
Since a reset is also performed when the instrument is taken into setup mode
via the host computer interface, the above also applies in this case.
After Power up or reset, the first measuring cycle starts immediately,
beginning with the fan run time.
Measuring interval
Since SF6 AREACHECK P2 is designed to determine slowly changing
concentrations, it samples the air at a fixed time interval rather than
measuring continuously. This feature minimizes the amount of air per time that
passes the instrument’s intake system, thus extending its service life.
Via the measuring time interval, it is possible to perfectly adapt the
instrument to the actual application. For monitoring generally unattended
spaces, a long time interval should be selected, while in the working area a
shorter interval is suggested.
SF6 AREACHECK P2 comes with a factory set measuring interval of 30 minutes,
which is the suggested starting point for most applications.
Indicator lights
6 LEDs on the instrument’s front panel represent its state as follows:
Placement of LEDs:
RUN
This light acts as a life sign to confirm the SF6 AREACHECK P2 is in
operation. As long as no internal error condition is met, it will blink at all
times. During the actual SF6 measurement (normally, this phase is very short),
it will blink at a faster rate.
Should this lamp stop blinking, an internal error has occurred.
ALARM
This light will be permanently on if the last measuring cycle has determined a
SF6 concentration above the selected alarm threshold.
In case of an internal error state, it will blink quickly.
The instrument’s internal audible alarm works in parallel with this lamp.
500 / 1000 / 1500 / 2000 [ppm]
These 4 yellow lamps reflect the last sampling period’s result in terms of
alarm levels as designated.
On instruments equipped with the optional oxygen sensor, these lights have the
following additional functions:
- The two leftmost LEDs (500+1000ppm) will blink when an oxygen concentration below the lower alarm threshold of 16% is present.
- The two rightmost LEDs (1500+2000ppm) will blink when an oxygen concentration above the upper alarm threshold of 25% is present.
Lamp test and manual reset
When the key switch is turned to the spring return “TEST” position, all lamps,
the internal audible alarm and the optional external alarm device will turn on
until the key switch is released.
When released, a pending alarm condition is cleared.
NOTE: An error condition will NOT be cleared!
When the key switch is turned and released twice within 2 seconds, a system
reset is performed which also clears any pending alarm and error conditions,
and logs a fresh reference value.
Configuration via the PC interface
Connecting to the host computer
Parameter modification in stand-alone operation is done exclusively through
the host computer interface. This has the clear advantage that any unintended
or unauthorised fiddling is discouraged.
The user parameters described in the following are relevant for stand alone
operation only. In network operation, parameters received from the network
base unit will take precedence.
The host computer interface follows RS232 standards. A special interface cable
connects to the 3 position plug, which is found between the two blue clamp
blocks.
The lamp next to the plug indicates the presence of valid RS232 levels from
the host. It will be lit when the host is on and correctly connected.
On the host computer, a standard terminal program is used to talk to the SF6
AREACHECK P2. A suitable program called “Hyper Terminal” is a standard
Microsoft Windows component and by default present in most installations.
Optionally, any other terminal software will work.
Set up the terminal program for the following parameters: 9600 baud, 8 data
bits, no parity, 1 stop bit. This is a standard configuration also known as
“9600-8-N-1”. Further, select “none” for the handshake protocol, and “TTY” as
emulation if available. The option “append CR” for received lines should be
checked for a more readable screen output. For your convenience, we will be
pleased to send you a predefined configuration file for “Hyper Terminal” which
will perform all relevant settings for you.
NOTE: While the PC interface is connected, the instrument will talk to
the host computer only and no longer communicate over the network. When
present, an SF6 NETWORK CONTROLLER P2NC will see this station as “OFFLINE” and
issue an alarm accordingly.
User parameters
User adjustable parameters are the time interval between each two samples (“Scan period”) and the alarm level. To activate the setup, from the terminal first send a line feed, then the instruction “TtS”, followed by another carriage return. A choice menu with the following options will then be presented:
<1> Scan period <2> Alarm level <3> Exit and resume operationJust type the corresponding number to invoke the desired option. Any other
inputs will be discarded.
After selecting “<1> Scan period”, enter the desired time interval in minutes,
followed by a carriage return. The allowed range is 1-99 minutes.
Upon selecting “<2> Alarm level”, enter the number corresponding to the
desired alarm level.
Option <3> will finish the setup and return the instrument to normal
operation. Since it will now perform a restart.
Changing the sensor unit
For changing the sensor unit, carry out the following Steps:
- Power down the P2 (remove the fuse, observing the hints below)
- Remove screws
- Take off Smart Sensor as indicated below
- Pull the connector off the Smart Sensor
- Fit the replacement Smart Sensor
- Power up the P2 (insert fuse observing the hints below)
NOTE: To precisely determine SF6 concentration, SF6 AREACHECK P2 requires
a reference value representing clean air. This reference value is taken and
stored whenever the instrument is powered up or reset. You should therefore
make sure that power up takes place under clean air conditions.
ATTENTION: The fuse (T1A) is at mains voltage. All works on it are to be
carried out by qualified personnel only, observing appropriate precautions!
O2 sensor
Functionality
The optionally available O2 sensor continuously measures the O2 content in the
ambient air, and reports it to the network controller if present.
An alarm condition on both the measuring station and network controller is
raised whenever the oxygen level is outside the allowed range of 16…25%.
Physical location
The O2 sensor is part of the SmartSensor, it is found protruding downwards from it.
Sensor Type
The O2 sensor is of galvanic cell type. It exhibits low cross sensitivity to CO2 and other gases, good stability and linearity over its range.
Sensor Lifetime
With a reasonable safety margin, sensor life is fixed at one year, no matter if shelfed or used this is due to the nature of galvanic cells, in which the chemical reaction goes on at all times as long as oxygen is present. When lifetime is over, the SmartSensor must be replaced against a fresh, readily calibrated one.
User Interface
When a low oxygen condition is encountered, the measuring station will issue an alarm, involving the built in alarm buzzer, the red alarm lamp, and the alarm relay. The low oxygen condition will be reflected by the yellow “500” and “1000” ppm lamps flashing. In case of a high oxygen condition, the same applies, except that the “1500” and “2000” ppm lamps will flash. On the SF6 NETWORK CONTROLLER P2NC, the O2 status will be marked as “OK”, “HI”, or “LO”, respectively, for each measuring station.
Safety
Should the O2 sensor fail, be missing or spent, a low oxygen alarm will be issued.
Technical data
Detection principle | SF6: NIC’ ‘ |
---|---|
Range | 0 … 2000 ppmv SF6 |
0 … 30% 02
Resolution| SR: 500 ppm 02: 1%
Mains power| 100-240VAC, 50/60Hz
Power consumption| 18 VA
Operating temperature range| – 5°C … 45°C
Storage temperature range| – 20°C … 60°C
Operating humidity range| 10 … 90% non-condensing
Max load, relay output| 2,5 A / 230 VAC
Size| H 280 x B 165 x T 125 mm
Protection class| IP 52
Noise level of audible alarm| > 75 dbA, lm
Weight| 1,5 kg (w/o wall mounting bracket)
Fuse| T 1A (Slow Blow)
Instrument warranty and service
Warranty
Standard Warranty can be extended to up to 2 years on the SF6 P1 & P1:p when
registering your instrument via our website: www.ionscience.com/instrument-
registration
To receive your Extended Warranty, you need to register within one month of
purchase (Terms and Conditions apply). You will then receive a confirmation
email that your Extended Warranty Period has been activated and processed.
Full details, along with a copy of our Warranty Statement can be found by
visiting: www.ionscience.com/instrument-
registration
Service
Ion Science is pleased to offer a number of service options on our SF6 P1 &
P1:p product range that allow you to choose the instrument cover that best
suits your needs.
At Ion Science we recommend that all of our gas detection instruments be
returned for service and factory calibration once every 12 months.
Contact Ion Science or your local distributor for service options in your
area.
Find your local distributor by visiting:
www.ionscience.com
Contact details
UK and Head Office
ION Science Ltd The Way, Fowlmere Cambridge SG8 7UJ UK Tel: +44 (0)1763 208503
Fax: +44 (0) 1763 208814 Web: www.ionscience.com
Email: info@ionscience.com
German Office
ISM ION Science Messtechnik Laubach 30 Metmann-Neandertal D-40822 GERMANY Tel:
+49 2104 14480 Fax: +49 2104 144825 Web: www.ism-d.de
Email: info@ism-d.de
French Office
ION Science France 41 Rue de Etoiles, 83240 Cavalaire-sur-Mer, FRANCE Tel: +33
6 13 50 55 35 Email: info@ionscience.fr
India Office
ION Science India #1-90/B/B/3/1, Charmy Vittal Rao Nagar Image Hospital Lane,
Madhapur, Hyderabad 500 081 Telangana State – India Tel: +91 40 4853 6129
Web: www.ionscience-india.com
USA Office
ION Science Inc 4153 Bluebonnet Drive Stafford TX 77477 USA Tel: +1 877 864
7710 Web: www.ionscience-usa.com Email:
info@ionscienceusa.com
Italian Office
ION Science Italia Via Emilia 51/c 40011 Anzola Emilia Bologna ITALY Tel: +39
051 0561850 Fax: +39 051 0561851 Web:
www.ionscience.it Email:
info@ionscience.it
Chinese Office
ION Science China Ltd 1101 Bldg B, Far East International Plaza No. 317,
Xianxia Road, Shanghai P.R. CHINA Tel: +86 21 52545988 Fax: +86 21 52545986
Web: www.ionscience.cn Email:
info@ionscience.cn
Manual log
Manual Version| Amendment| Date updated| Instrument
Firmware| PC Software
---|---|---|---|---
SF6 P2 V1.1| Layout and font update| 28/01/13| |
SF6 P2 V1.1R| Logo only| 1-8-2017| |
SF6 P2 V1.2| Design update| 5-5-2020| |
Disclaimer: Information in this [manual, document…] is subject to change without notice and does not represent a commitment on the part of Ion Science. No claims, promises or guarantees are made about the accuracy, completeness, or adequacy of the information contained herein.
Unrivalled Gas Detection.
ionscience.com
References
- Pioneering Gas Sensing Technology - ION Science Inc
- Coming Soon
- Coming Soon
- Coming Soon
- Coming Soon
- 离科科技 | 英国离科中国公司
- 离科科技 | 英国离科中国公司
- Pioneering Gas Sensing Technology - ION Science Inc
- Pioneering Gas Sensing Technology - ION Science Inc
- Pioneering Gas Sensing Technology - ION Science Ltd
- Pioneering Gas Sensing Technology - ION Science Ltd
- Gasdetektion und Dichtheitsmessung von ISM - Messbar Besser
- Gasdetektion und Dichtheitsmessung von ISM - Messbar Besser
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>