ENDURO 1-3kVA Pure Sinewave On-Line UPS User Manual

June 3, 2024
Enduro

ENDURO logo 1-3kVA Pure Sinewave On-Line UPS
User Manual 1-3KVA, 1:1 Phase
Pure Sinewave On-Line UPS
USER MANUAL

1-3kVA Pure Sinewave On-Line UPS

All rights reserved. The information in this document is subject to change without notice.
Publish statement
Thank you for purchasing the Enduro UPS series. This series UPS is an intelligent, single phase in single phase out, high frequency online UPS designed by our R&D team who is with years of designing experienceson UPS. With excellent electrical performance, perfect intelligent monitoring and network functions, smart appearance, complying with EMC and safety standards, The UPS meets the world’s advanced level.
Read this manual carefully before installation
This manual provides technical support to the operator of the equipment. The ENDURO range of UPS systems are intended for installation in a contaminant free environment with a temperature range between 0°C and 40°C.

Important Safety Warning

SAVE THESE INSTRUCTIONS. This manual contains important instruction that should be followed during installation and operation of the UPS and batteries.
Do not operate this unit before reading through all safety information and operating instructions carefully
The UPS contains its own power source (the battery). The power outlets may be energized even if the system is disconnected from the AC power source.
Dangerous voltage levels and high temperature components are present within the system. The UPS and its External Battery Modules should be opened exclusively by suitably trained and qualified personnel.
The batteries supplied within the system are valve regulated lead acid (VRLA) and contains small amounts of toxic materials. The batteries are certified as complying with UN2800 Special Provision A67 of the International Air Transport Association (IATA) Dangerous Goods Regulations.
Safety instructions in this manual act as a supplementary for the local safety instructions. PSS Distributors will not assume the liability that caused by disobeying safety instructions.
1-1 Transportation
Please transport the UPS system only in the original package to protect against shock and impact.
1-2 Preparation
Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment. Do not install the UPS system near water or in moist environments. Do not install the UPS system where it would be exposed to direct sunlight or other heat sources. Do not block ventilation holes in the UPS housing.
1-3 Installation

  • Do not connect appliances or devices with high inrush currents to the UPS system (e.g. laser printers, compressors, fridges and motors).
  • Place cables in such a way that no one can step on or trip over them.
  • Do not connect domestic appliances such as hair dryers to UPS output sockets.
  • The UPS can be operated by any individuals with no previous experience.
  • Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system.
  • Use only Australian approved AC cables to connect the UPS system to the building supply and to connect the loads to the UPS system.
  • When installing the equipment, it should ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3.5mA.

1-4 Operation
Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket outlet) during operations since this would remove the protective earthing of the UPS system and of all connected loads. The UPS system features its own, internal current source (batteries). The UPS output sockets may be energized even if the UPS system is not connected to the building wiring outlet. To fully disconnect the UPS system, first press the OFF/Enter button to disconnect the mains. Isolate the UPS and check for hazardous voltage upstream and downstream during lockout-tagout operation. Prevent fluids or other foreign objects from entering the UPS system.
1-5 Maintenance

  • The UPS system operates with hazardous voltages. Repairs and maintenance must be carried out by qualified UPS maintenance personnel.
  • Caution – risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
  • Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present, and no hazardous voltage exists at within the system.
  • Caution – risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present!
  • Batteries
    • Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
    • The battery supplied with the system contains small amounts of toxic materials.
    • Use appropriate PPE when handling the batteries.
    • If a battery case is damaged there is potential exposure to sulfuric acid and lead.
    • When replacing batteries, replace with the same type, capacity and number of batteries or battery packs.
    • Do not mix old and new batteries and ensure that the batteries have the same state of charge and internal resistance.
    • Read the battery manufacturer’s Safety Data Sheet prior to replacement.
    • Dispose in accordance with federal, state, or local regulations.
    • Recycle wherever possible
  • Maintenance
    • The UPS should be regularly maintained (12 Months, 6 Months etc)
    • Maintenance intervals are dependent on the operating environment and the application.
    • PSS offers a wide range of cost-effective preventative maintenance solutions.

|
---|---
Non Contract – ONE-OFF Service| | X| X| X| X
BASIC CONTRACT| | | X| X| X
COMPREHENSIVE CONTRACT| | | | | X
COMPREHENSIVE PLUS| | | | |

Installation and setup

NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package has been damaged. Please keep the shipping cartons and packing materials in a safe place for future use.
2-1 Unpack checking

  • When removing the UPS or EBM from the packaging:
    • Do not lift the UPS from the front panel.
    • Do not lean the UPS when moving it out from the packaging.
    • The UPS is heavy. Removing it from the carton requires a minimum of two people.
  • Check to see if the UPS is visibly damaged during the transportation, do not switch on the UPS if any damage found. Please contact the supplier right away.
  • Verify that the following additional items are included with the UPS:
    • User manual
    • Software Suite CD
    • USB cable
    • Input AC Power cord
    • base brackets kit (tower installation)
    • Rack brackets (rack installation)

2-2 Real panel view
EN1000 – 1KVA

  1. Output receptacles (10A)
  2. External Battery Connector
  3. SNMP intelligent slot (optional SW006 SNMP card)
  4. Network /Fax/Modem Surge Protection
  5. RS-232 communication port
  6. AC input receptacle
  7. Input resettable fuse
  8. Connector for EPO (Emergency Power Off)
  9. USB communication port
  10. Output receptacle (16A)

2-3 Installing the UPS
Rackmount installation
If installing optional external battery module(s) EBM(S), make sure to install the EBM(S) directly below the UPS module and the connector(s) are securely plugged in as detailed below.
FRONT VIEW Optional adjustable rack mounting kits, part number RK1000 are available from your Enduro supplier.  Tower Installation Connect the base brackets together for a single unit installation. Utilize the 1U base extender(s) to add
2-4 UPS startup and turn off
Startup operation

  1. Turn on the UPS ONLINE mode
    NOTE Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm.
    a) Once mains power is plugged in, the UPS will startup in bypass mode (Bypass LED lit)
    b) Press and hold the ON key for more than half a second to start the UPS.
    c) The inverter will start, and the UPS will perform a self-test.
    d) On completion of the self-test, the green LED will be lit, indicating the UPS is working ONLINE mode.

  2. Turn on the UPS by DC without mains power
    a) Ensure that the earth is connected via the AC supply cord.
    b) Press and hold the ON key for more than half a second to start the UPS.
    c) The inverter will start, and the UPS will perform a self-test.
    d) On completion of the self-test, the amber battery LED will be lit, indicating the UPS is working ONLINE mode but drawing power from the batteries. An audible alarm will be heard. the self-test, the corresponding LED lights andthe UPS is working in battery mode.

Turn off operation

  1. Bypass the UPS
    a) Press and hold the OFF key for more than half a second to turn off the inverter.
    b) The Green ONLINE LED will extinguish, and the Bypass LED will be lit.

  2. Turning off the UPS
    c) Switch off the AC power supplying the UPS.
    d) The UPS will shut down.

2-5 Configuring Battery Settings

  • Set the UPS for the number of EBMs installed.
  • To ensure maximum battery runtime, configure the UPS for the correct number of EBMs, refer to the table below for the appropriate setting.
  • Refer to UPS Settings, section 3.3 screen number 4.
All UPS and EBM Cabinets Battery Capacity
UPS only (internal batteries) 9Ah(default)
UPS+1EBM 27Ah
UPS+2EBMs 45Ah
UPS+3EBMs 63Ah
UPS+4EBMs 81Ah

NOTE The UPS contains 1 battery string; each EBM contains 2 battery strings.
2-6 LCD control panel
2-7 Setup the UPS

Step 1: UPS input connection

  • Using the AC power cord supplied, plug the UPS into the AC supply socket.
  • Avoid the use of multiplugs and extension leads.

Step 2: UPS output connection

  • Plug the load devices into the UPS.

Step 3: Communication connection
To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication cable one end to the USB port and the other to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or Relay card. When installing either SNMP (part number SW006) or Relay card (part number SW011), it will provide advanced communication and monitoring options.
Communication ports:
Step 4: Turn on the UPS

Refer to section 2.4 Note: The battery charges fully during the first five hours of normal operation.
Step 5: Install software
For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown. You may insert provided CD into CD-ROM to install the monitoring software. The software can be download at http://www.megatec.com.tw/Download.htm

Operations

3-1 Button Operation

Button Function
Turn on the UPS: Press and hold ON button for at least 2  seconds to turn

on the UPS.
Switch the UPS from bypass mode to ONLINE mode.
UPS Setting Mode
Choosing different value: When the UPS enters the setting mode, press this button to select the required value.
| Turn off the UPS: Press and hold button at least 2 seconds to turn off the UPS in battery mode.
Switch the UPS from ONLINE mode to bypass mode.
UPS Setting Mode
Down key: Press button to display the next selection.
| Switch LCD message: Press button to change the LCD message for input voltage, input frequency, battery  voltage, output voltage and output frequency etc.
Rotate Key: Hold for 10 seconds to rotate the LCD screen.
Mute the mains failure alarm: Hold button for at least 5 seconds  to disable or enable the alarm system.
UPS Setting Mode
Up key: Press button to display previous selection.
Switch to UPS self‐test mode: Press button for 2 seconds.
| Access UPS Setting Mode
Press buttons simultaneously for 5 seconds.

3-2 LCD display
Part one: Rack display
There are 8 interfaces available in the LCD display.
3-3 UPS settings
The UPS should come preset and not require any adjustments. The setting function is controlled by the three buttons as detailed below. To access the setup, press the After the UPS turn ON, press buttons +  for 5 seconds.

Item Settings Content display
01 MODE

Press Enter button to change the setting (NOA or ECO or CF).
Press UP button ▲ to select  the previous setting.
Press DOWN ▼ button to select the next setting.|
02| OUTPUT VOLTAGE
Press Enter button to change the setting (200V – 240V).
Press UP button ▲ to select the previous setting.
Press DOWN ▼ button to select the next setting.|
03| FREQUENCY
Press Enter button to change the setting (50Hz /60Hz).
Press UP button ▲ to select the previous setting.
Press DOWN ▼ button to select the next setting.|
04| BATTERY CAPACITY
Press Enter button to  change the setting.
Default is 9Ah refer to section 2.5.
Press UP button ▲ to select the previous setting.
Press DOWN ▼ button to select the next setting.|
05| LOW VOLTAGE ALARM
Press Enter button to change the setting.
Default setting: 185V / Cell
Press UP button ▲ to select the previous setting.
Press DOWN ▼ button to select the next setting.|
06| EOD
Press Enter button to  change the setting.
Default setting: 185V / Cell
Press UP button ▲ to select the  previous setting.
Press DOWN button ▼ to  select theprevious setting.|
07| Bypass Voltage Upper limit
Press Enter button to  change the setting. (230‐264Vac)
Press UP button ▲ to selectthe  previous setting.
Press DOWN button ▼ to select the  previous setting.|
08| Bypass Voltage Lower limit
Press Enter button to  change the setting. (170‐ 220Vac)
Press UP button▲to select the  previous setting.
Press DOWN button▼to select the  previous setting.|

3-4 Operating Mode Description

Mode Description Indicator
Line Mode The green LED is on.
o Input AC mains is within limits, the UPS will function in ONLINE mode.
Battery Mode The battery amber LED is on.

o The alarm  beeps once every 4 seconds.
o Input AC mains is out of limits.
The battery amber LED flashes.
o The battery voltage has reached the limit setin section 3.3 (05)
UPS power off
o The battery voltage has reached the limit set in section 3.3 (06)
UPS will auto‐restart when  the mains recover.|
Bypass Mode| The bypass amber LED is on.
The UPS is in bypass.|
ECO Mode| The bypass amber LED is on.
When ECO enabled and the AC mains is in range, the UPS will work on ECO Mode.
If the AC mains is out of range the UPS will transfer to ONLINE mode.|
Fault Mode| The warning red LED is on and the alarm beeps.The UPS is in fault mode.
• NOTE: please refer to alarm or fault reference code.|

3-5 Operational Status and Mode(s)

item Content Displayed
2 Standby Mode
3 No Output
4 Bypass Mode
5 Utility Mode
6 Battery Mode
7 Battery Self‐diagnostics
8 Inverter is starting up
9 ECO Mode
10 EPO Mode
11 Maintenance Bypass Mode
12 Fault Mode

3-6 Alarm or Fault reference codes

Event log UPS Alarm Warning Buzzer LED
2 Inverter fault (Including Inverter bridg is shorted) Beep continuously

Fault LED lit
9| Fan fault| Beep continuously| Fault LED lit
12| Self‐test fault| Beep continuously| Fault LED lit
13| Battery Charger fault| Beep continuously| Fault LED lit
15| DC Bus over voltage| Beep continuously| Fault LED lit
16| DC Bus below voltage| Beep continuously| Fault LED lit
17| DC bus unbalance| Beep continuously| Fault LED lit
18| Soft start failed| Beep continuously| Fault LED lit
19| UPS Inside Over Temperature| Twice per second| Fault LED lit
20| Heat sink Over Temperature| Twice per second| Fault LED lit
26| Battery over voltage| Once per second| Fault LED blinking
29| Output Short‐circuit| Once per second| Fault LED blinking
30| Input current limit| Once per second| Fault LED blinking
31| Bypass over current| Once per second| BPS LED blinking
32| Overload| Once per second| INV or BPS LED blinking
33| No battery| Once per second| Battery LED blinking
34| Battery under voltage| Once per second| Battery LED blinking
35| Battery low pre‐warning| Once per second| Battery LED blinking
36| Overload time out| Once per 2 seconds| Fault LED blinking
37| DC component over limit.| Once per 2 seconds| INV LED blinking
39| Main’s volt. Abnormal| Once per 2 seconds| Battery LED lit
40| Mains freq. abnormal| Once per 2 seconds| Battery LED lit
41| Bypass Not Available| | BPS LED blinking

Troubleshooting

If the UPS system does not operate correctly, please solve the problem by using the table below.

Symptom Possible cause Remedy
No indication and alarm even though the mains is normal. The AC input power
isnot connected well. Check if input power cord firmly connected to the

mains.
The AC input is connected to the UPS output.| Plug AC input power cordto AC input correctly.
Alarm code is shown as”33″and battery led blinking.| The external or internal batten/ is
incorrectly connected.| Check if all batteries are connected well.
Alarm code is shown as “26”and battery led blinking.| voltage Is too Battery high or the charger is fault.| Contact your dealer.
Alarm code is shown as “34”and  battery led blinking| Battery voltage is toolow or the charger is fault.| Contact your dealer.
Alarm code is shown as “3 2″and INV or BYPASS led blinking.| UPS is overload| Remove excess loads fromUPS output.
Alarm code is shown as ” 29″and FAULT led light.| The UPS shut down automatically because short circuit occurs on
the UPS output.| Check output wiring and if connected devices are in short circuit status.
Alarm code is shown as “9”and FAULT led light.| Fan fault.| Contact your dealer.
Alarm code is shown as 01,02, 15,16,17,18″| A UPS internal faulthas occurred.| Contact your dealer.
Battery backup time is shorterthan nominal value| Batteries are not fully charged| Charge the batteries for atleast 5 hours and then check capacity. If the problem still persists, consult with your dealer.
Batteries defect| Contact your dealer to replace the battery.

Storage and Maintenance

Operation
The UPS system contains no user‐serviceable parts. If the battery service life (3~5 years at 25°C  mbient temperature) has been  exceeded, the batteries must be replaced. In this case, please contact your dealer.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table:

Storage Temperature Recharge Frequency Charging Duration
‐25°C ‐ 40°C Every 3 months 1‐2 hours
40°C ‐ 45°C Every 2 months 1‐2  hours

ENDURO 1-3kVA Pure Sinewave On-Line UPS fig 27

  • Loosen the 2 torque screws (on each side of the card).
  • Carefully insert the SNMP / Relay card into the slot and lock the screws

SW006 SNMP

SW011 Relay Card

1 Common
2 UPS Active
3 Mains Fail
4 Close when Mains Fails
5 Battery Low
6 Close when Battery Low
7 General Alarm
8 Close when UPS Alarm
9 Bypass Active
10 Close when Bypass Active
11 UPS Fault
12 Close when UPS Fault

7-1 Warranty Registration
Please register your warranty with the serial number provided on the below link.
http://www.pssdistributors.com.au/ups‐warranty‐registration/
7-2 PSS Repair/RMA Form
 https://pssdistributors.com.au/repair‐rma/
7-3 Service Enquiries
Email: Service@pssdistributors.com.au
Contact: 1300 882 447

Specification

Model EN 1000 EN 2000 EN 3000
Capacity 1kVA/900W 2kVA/1800W 3kVAl2700W
Input
Voltage range 230V +/- 20%
Frequency range 45Hz – 65Hz
Phase Single phase
Power factor .?- 0.98
Breaker 6A 10A 15A
Input socket IEC C14 10A IEC C14 10A IEC C20 16A

Output
Voltage range| 230VAC+/-2%
Frequency ( battery mode)| 50Hz +/- 0.1Hz
Power factor| 0.9
Current crest ratio| 3:01
THD| c3%(linear Load); -05% (non-linear oad)
Waveform| Pure Sinewave
Output sockets| 2x AU 3 Pin sockets
( 1 critical I 1 non-critical)| 3x AU 3 Pin sockets
( 2 critical / 1 non-critical)| 3x AU 3 Pin sockets
( 2 critical! 1 non-critical)
Efficiency| ?.. 89% normal mode, up to 97% ECO mode
Overload capacity| 30s at 100-150%: 300ms at >150%
Battery
Type| Seated lead acid, maintenance free
Configuration (standard run)| 3x 12V / 9Ah| 6x 12V /9Ah| 6x 12V / 9Ah
Rated battery voltage| 36V| 72V| 72V
Charge current (Max)| 12A
Recharge time to 90%| 5 Hrs
Charge mode| Intelligent 3-stage charging
Comma & Management
Software| Windows 95198/NT/2000/XPNistaf7, Windows Server 2003/2008
Linux Deblan, Redhat, Fedora, Suss, Ubuntu, Cent0S. Novell. Mac, FreeBSD
Ports| USB and RS-232 standard
Optional| SNMP & relay (trigger voltage free contacts)
LED/LCO display| Load, battery, input, output, operating
Audible alarm| Battery mode, low battery, overload, fault
Protection
Surge protection| 2200 Joules/ 60,000 Amps
Input protection| Compliance with IEEE 587
Short circuit| Resettable circuit breaker
EPO| Shuts down UPS immediately
EMC| EN50091-2, C Tick/RCM
Network| RJ45, fulltime network protection
Characteristics
Temperature| 0-40  °C
Humidity| 0 – 95% (non-condensing)
Noise level| <50dB at 1m
Dimensions (WxDxH) /weight| 440x430x86.5 (2RUy15.1kg| 440x600x86.5mm (2RU)126.3kg| 440x600x86.5mm (2RU)/26.8kg
Shipping dimensions (WxDxli)/weight| 560x560x210mm/17.9kg| 560x730x210mrs129.6kg| 560x730x210mm129.9kg
EBM dimensions (WxOxH) 1 weight| 440x430x86.5mm(2RU)120kg| 440x710x86.5mm(2RU)/33kg| 440x710x86.5mm(2RU)133kg
EOM shipping dimensions(VhdixH)fweigN| 560x560x210mm124.1kg| 560440x210mm./42.6kg| 560x810x210mm142.6kg

ENDURO logowww.pssdistributors.com.au
Email: sales@pssdistributors.com.au
Phone: 1300 882 447

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals