Product Information

The GV3 Ppp/Lpp – Ppp6/Lpp6 is a self-protected combination  motor controller UL 60947-4-1 type E. It is a product of Schneider  Electric Limited, with a product code of 1672548 (GV3P). The  product’s rail is 35 mm V EN 50022, NFC 63015 mm in size. It has a  maximum GV3Ppp/Lpp + GV3Gp64 of 9mm or 0.35 inches and a maximum GV3Ppp6/Lpp6 + GV3/L80 of 15mm or 0.6 inches. The product’s configuration is for self-protected combination motor controllers.

Product Usage

Before servicing equipment, it is important to disconnect all power to avoid danger or arc flash. To use the GV3 Ppp/Lpp – Ppp6/Lpp6, follow the steps below:

  1. Ensure that all power is disconnected before servicing equipment.
  2. Mount the GV3Ppp/Lpp or GV3Ppp6/Lpp6 on the rail with the size of 35 mm V EN 50022, NFC 63015 mm in size.
  3. Use three M4 x20 (#8 x 32) screws to secure the product in place, with a torque of 1 N.m or 8.8 Ib-in.
  4. Configure the self-protected combination motor controller by  setting it to type E and turning it off.
  5. Connect the necessary GVANpp, GVADpp, and GVAM11pp wires.
  6. Connect the GVAE11 or AE20 wires for the GV3Ppp/Lpp or GV3Ppp6/Lpp6, respectively.
  7. Connect the GVAED101 or AED011 wires for the GV3Ppp/Lpp or GV3Ppp6/Lpp6, respectively.
  8. Connect the necessary GVAE1 wires for the product.
  9. Connect the necessary GVAUppp and GVASppp wires.
  10. Turn on the GVAM11 and ensure that it is functioning  properly.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Disconnect all power before servicing equipment.
Failure to follow these instructions will result in death or serious injury.

INSTALLATION

  • (1) Ue < 500V: 40 mm (1.57 in)
  • 500V < Ue < 690V: 50 mm (1.97 in)
  • (2) T° < 40°C (102°F): 0 mm (0 in)
  • T° < 60°C (140°F): 9mm (0.35 in)

Schneider-Electric-GV3L65-Motor-Circuit-Breaker-fig-2

Schneider-Electric-GV3L65-Motor-Circuit-Breaker-fig-3

Schneider-Electric-GV3L65-Motor-Circuit-Breaker-fig-4

Schneider-Electric-GV3L65-Motor-Circuit-Breaker-fig-5

Buttons Installation

Schneider-Electric-GV3L65-Motor-Circuit-Breaker-fig-6

Schneider-Electric-GV3L65-Motor-Circuit-Breaker-fig-7

Schneider-Electric-GV3L65-Motor-Circuit-Breaker-fig-8

Recycling

Schneider-Electric-GV3L65-Motor-Circuit-Breaker-fig-9

© 2021 Schneider Electric All rights reserved.

Contacts

Schneider Electric Industries SAS 35, rue Joseph Monier – CS 30323
Telford, TF3 3BL United Kingdom
www.se.com/uk
F – 92506 Rueil Malmaison Cedex
www.se.com/contact
www.se.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals