DELTA PDU-275-kVA Power Distribution Cabinet User Manual

June 3, 2024
Delta

DELTA PDU-275-kVA Power Distribution Cabinet User Manual
DELTA PDU-275-kVA Power Distribution Cabinet

Overview

This document provides the product introduction, component introduction and system maintenance of the DC power system. The pictures in this article are for reference only, and the actual structure shall prevail.

Suitable for

This document (this guide) is primarily intended for the following engineers:

  • Sales Engineer
  • Technical Support Engineer
  • Maintenance Engineer

Safety rules
Before starting the operation, please read the operation instructions and precautions carefully to reduce the occurrence of accidents. The “CAUTION, NOTICE, WARNING, DANGER” items in the product and product manual do not represent all the safety precautions to be followed, but only serve as a supplement to various operational safety precautions. Therefore, the personnel responsible for the installation and operation of this product must be strictly trained and master the correct operation method of the system and various safety precautions before operating the equipment.

When operating the company’s products and equipment, user must abide by the safety regulations of the relevant industry, and strictly abide by the relevant equipment precautions and special safety instructions provided by the company.

Notation convention

High Voltage

| The AC input line is a high-voltage working line. During the operation, it must be ensured that the AC input is powered off. During the operation, a temporary prohibition sign should be added to the switch that is not allowed to be used.
---|---

Danger

| Indicates an imminently hazardous situation which, if not avoided, will result in death or serious personal injury.

Caution

| Indicates a potentially hazardous situation which, if not avoided, could result in moderate or minor personal injury.

Notice

| Used to convey equipment or environmental safety warnings, which, if not avoided, may result in equipment damage, data loss, reduced equipment performance, or other unpredictable results.

“NOTICE” does not refer to personal injury.

Instruction

| Used to highlight important/critical information, best practices, tips, etc.

“Instructions” are not safety warning information, and do not involve personal, equipment and environmental damage information.

Revision history
Document version 1.0[2022-03-25] The first official release

General Safety Considerations

  • This product should be used in an environment that meets the design specifications, otherwise it may cause product failure, resulting in abnormal product function or component damage, which is not within the scope of product quality assurance.
  • The personnel responsible for installing and maintaining the equipment must first undergo strict training, understand various safety precautions, and master the correct operation methods before installing, operating and maintaining the equipment.
  • Operators should follow local regulations and codes. The safety precautions in the manual are intended only as a supplement to local safety regulations.
  • Operation of equipment and cables during thunderstorms is prohibited.
  • It is strictly forbidden to wear watches, bracelets, bracelets, rings and other conductive objects on the wrist during operation.
  • Special insulated tools must be used during operation.
  • Installation or maintenance operations must follow the sequence of steps in the task.
  • Before touching any conductor surface or terminal, measure the voltage at the point of contact with an electricity meter to confirm that the point of contact is free or within a predicted range.
  • If the battery is not connected to the power system or the battery capacity is insufficient, the load (electric equipment) may be powered off during maintenance or fault location.
  • More than 24 hours before the laying operation.
  • After the installation of the equipment is completed, the user should carry out routine inspection and maintenance of the equipment in accordance with the requirements of the user manual, and replace the faulty parts in time to ensure the safe operation of the equipment.

Electrical Safety

Ground safety
  • When installing the device, the protective ground wire must be installed first; when removing the device, the protective ground wire must be removed last.
  • Before operating the equipment, make sure that the equipment is properly grounded.

AC and DC operation requirements

  Danger

The supply voltage of the power supply system is dangerous, and direct contact or indirect contact through wet objects with these parts will bring fatal danger.
Irregular and incorrect operation may cause accidents such as fire or electric shock.

  • The installation of AC power equipment must comply with the safety regulations of the relevant industry, and the personnel who install the AC equipment must be qualified for high-voltage and AC power operations.
  • Before the equipment is electrically connected, the pre-protection switch of the equipment must be disconnected.
  • Before connecting to AC power, you must ensure that the electrical connections to the equipment are complete.
  • Before connecting the load (power equipment) cable or battery cable, you must confirm the polarities of the cables and terminals to prevent reverse connection.
  • It is strictly forbidden to wear watches, bracelets, bracelets, rings and other conductive objects on the wrist during operation.
  • Prohibition signs must be hung on switches and buttons that cannot be operated during installation.

Anti-static requirements

  • In order to prevent human body static electricity from damaging sensitive components, you must wear anti-static gloves or ESD gloves before touching the circuit board.
  • An anti-static wrist strap, and the other end of the anti-static wrist strap is well grounded.
  • When holding a veneer, you must hold the edge of the veneer that does not contain components, and it is forbidden to touch the chip with your hands.
  • The disassembled veneer must be packed with anti-static packaging material before storage or transportation.

Liquid resistance requirements

  • This product should be placed in an area away from liquids, and it is forbidden to install it below the air-conditioning vents, vents, outlet windows of the equipment room and other places prone to water leakage, to prevent liquid from entering the equipment and cause a short circuit, and to ensure that there is no condensation in the equipment room and equipment.
  • When you find that liquid has entered the inside of the device, please turn off the power immediately and notify the administrator.
Mechanical safety

Lifting safety

  • Personnel who carry out hoisting operations need to undergo relevant training and can only take up their posts after being qualified.
  • Lifting tools need to be inspected and the tools are complete before they can be used.
  • Before hoisting work, make sure that the hoisting tool is securely fastened to a load-bearing fixture or wall.
  • During the hoisting process, ensure that the angle between the two cables is not greater than 90°.

Safe use of ladders

  • Before using the ladder, make sure that the ladder is in good condition. And confirm the size of the loadbearing weight specified by the ladder, and prohibit the use of excessive weight.

  • Figure 1-1, the inclination of the ladder is preferably 75°, which can be measured with a square or arm.
    Ladders should be used with the wide feet facing down or with protection at the bottom of the ladder to prevent falls. Ladders should be placed in a stable place.
    Figure 1-1 Schematic diagram of the inclination of the ladder

  • When carrying heavy objects, be prepared to bear the weight to avoid being crushed or sprained by heavy objects.

  • When handling the device by hand, wear protective gloves to avoid cutting your hands from sharp corners.

Drilling Safety

Notice

Do not drill holes in the cabinet by yourself. Drilling holes that do not meet the requirements will destroy the electromagnetic shielding performance of the cabinet and damage the internal cables. Metal chips generated by the drilling will.

  • Before drilling holes in the cabinet, remove the cables inside the cabinet.
  • Goggles and protective gloves should be worn when drilling.
  • Strictly prevent metal shavings from falling into the cabinet, and clean up the metal shavings in time after drilling.

Chapter 2 Product Introduction

Product description

Power distribution cabinet system, is to give 220V AC or 380V AC series equipment is used for power supply, the maximum output current is 400A, and it is divided into 51 outputs. The appearance of the product is shown in Figure 2-1.
Product description

Working principle

Schematic diagram of the working principle of the power distribution cabinet system is shown in Figure 2-2.
The AC power passes through the main molded case circuit breaker, passes through the main transformer, the 51 way sub-transformer, and then reaches the 51 -way miniature circuit breaker to supply power to multiple loads.
Working principle
Figure 2-2 Schematic diagram of the working principle of the system

System Configuration

The system configuration is shown in Table 2-1.

Project System configuration
Monitoring unit YD-DEMS-BD2-N YM- DEMS-BD11Q24YM- DEMS-BD11Q30 YDE-DD150-1212
Molded case circuit breaker NDM2-400L/4300B400
Magnetic circuit breaker SPEC(CVP-FR-1BA4-32-AB2L2Y-T)*41 SPEC(CVP-FR-

1BA4-63-AB2L2Y-T)*10
Lightning protection circuit breaker| NDB1-63C32/4
AC lightning protection| In(8/20us): 20KA; Imax(8/20us): 40KA , Class C

Table 2-1 System configuration

Structure function
System structure and functions are shown in Figure 2-3.
Structure function
Figure 2-3 System structure and function

  1. Input molded case circuit breaker
  2. Output magnetic circuit breaker
  3. Lightning protection circuit breaker
  4. Lightning protection
  5. Monitoring unit
Monitoring function

For the function description of the system, see YD-DEMS-VD2-DC – The user manual of touch screen
operation.

Technical indicators

Environmental indicators

Table 2-2 Environmental indicators

parameter name Parameter Description
Operating temperature -40℃~+65℃
transport temperature -40℃~+70℃
Storage temperature -40℃~+70℃
Working humidity 5%RH~95%RH, no condensation
Storage humidity 5%RH~95%RH, no condensation
Altitude requirements 0 ~ 4000m ( in the environment of 3000m ~ 4000m high

temperature derating, every 200m rise , the working temperature temperature decreased by 1°C)

Electrical Specifications

Table 2-3 Electrical Specification

parameter name Parameter Description
AC input input format
input frequency 50Hz (45Hz~65Hz); nominal frequency: 50Hz/60Hz
input capacity 400A
AC output The output voltage
output capacity 32A*41

63A*10

other Safety design Meet the standard IEC/EN60950-1/GB 4943
Insulation resistance After removing the monitoring module, rectifier module,

and lightning protection module, the connection between the DC part, the AC part and the chassis is

Insulation resistance >10MΩ ( Test voltage 500Vdc)

Dielectric strength| To the AC input and DC output parts; apply 1500VAC to the AC part and the case; apply 500VAC to the DC output and the case. No breakdown arcing and leakage in one minute flow ≤ 10mA.

Mechanical index
Table 2-4 Electrical Specifications

parameter name Parameter Description
structure Power System

(H×W×D)

| 2000±2mm×600±2mm×1200±2mm
weight| ≤ 50kg
Protection class| IP20
Installation method| Floor installation
In and out way| top-in, top-out
Maintenance method| Pre-support maintenance method
Cooling method| Natural heat dissipation

Chapter 3 System Installation

This chapter describes the installation requirements, installation, wiring, and installation inspection of the power system.

Installation requirements

Construction personnel requirements
Construction personnel must have basic knowledge of safe operation, undergo professional training, master correct operation methods, and have corresponding operating qualifications.

Notice

The company does not assume any responsibility for the damage to individuals and equipment caused by the construction personnel not operating in accordance with the requirements of this article

Customers should pay attention to the following points when organizing construction personnel:

  • The technical personnel of the client side should undergo relevant training and master certain installation and construction methods.
  • The number of construction personnel should be determined according to the specific project schedule and installation environment, generally 2 to 4 people are appropriate.

Installation tool requirements

Notice

Use tools with insulated handles!
Introduce the tools and instruments that need to be prepared before installation (including but not limited to the tools in the table below).

Table 3-1 Preparation tools and instruments

List of tools and meters

List of tools and meters
List of tools and meters

Cable laying requirements

  • Cables should be kept 20mm away from heat sources to prevent insulation damage (melting) or functional degradation (aging or breakage).
  • The bend radius of the cable should be at least five times the diameter of the cable.
  • Cables of the same type should be connected together, with a minimum distance of 30mm between cables of different types to avoid entanglement.
  • The cables connected together should be close to each other, neat and undamaged.
  • The ground wire should not be connected or tangled with the signal cable, and there should be an appropriate distance between them to minimize interference.
  • AC power cords, DC power cords, signal cables, and communication cables must be connected separately.
  • No soldering or soldering should be done on the power cord, use longer cables if necessary
Install the power distribution cabinet

Planning the installation space
Installation Instruction
Figure 3-1 Dimensions

Unpacking and acceptance

  • Step 1, check if the box is intact.
    If the box is badly damaged or wet, please find out the reason and give us feedback.

  • Step 2, open the box.

  • Step 3, check the number of parts on the packing list.
    If the quantity is different from the quantity on the packing list, please confirm the reason and give us feedback.

Install the power distribution cabinet

Install the power distribution cabinet on the ground or a concrete base, as shown in Figure 3-2.

  • Step 1. Remove the power distribution cabinet from its packaging.
  • Step 2, align the installation holes of the power distribution cabinet and put them into the ground studs.
  • Step 3, install the fixing screws.
    Installation Instruction
Install the cable

Install the protective ground wire

Caution

Make sure the ground wire is connected reliably. Equipment damage or personal injury may result if equipment is not properly grounded.

  • Step 1. Connect one end of the protective ground wire to the PE terminal block of the AC input.

  • Step 2. Connect the other end of the protective ground wire to the main grounding bar screw in  the equipment room, as shown in Figure 3-3. No. 1 is the grounding bar.
    Installation Instruction

    1. Ground bar
      Figure 3-3 Installing the protective ground wire

Install communication cables

  • Step 1. Connect one end of the cable to the RS485 port of the monitoring module.

  • Step 2. Connect the other end of the cable to the network port of the host computer, as shown in Figure 3-10.
    Install communication cables

    1. RS485 interface of the system
    2. Host computer
      Figure 3-4 Schematic diagram of communication cable connection

Install the output cable

Danger

  1. Please make sure that the AC output air switch of the front stage is in the OFF state, and place a prominent sign of “prohibited operation”.
  2. Turn off all air switches before installing cables.
  • Step 1, place 220 The AC single-phase three-wire AC output cables are routed through the top or bottom of the power distribution cabinet.
  • Step 2 , according to the actual load capacity, fasten the output L cable to the output air switch copper bar of the corresponding specification.
  • Step 3. Fasten the output N cables to the screws corresponding to the specifications of the zero row.
    Install the output cable
1. AC load  

Figure 3-4 Output cable wiring diagram

Installing the AC Input Cable

Danger

  1. Please ensure that the front-end AC input air switch is in the OFF state, and place a prominent sign of “prohibited operation”.
  2. Turn off all air switches before installing cables.
  • Step 1, put the 220/380V Pass the AC three-phase four-wire AC input cable from the rear side of the sub-rack and remove the front top cover for wiring.
  • Step 2. Fasten the AC input cable to the corresponding AC input terminal, as shown in Figure 3-13.
    Wiring diagram of AC input cable
1. AC input  

Figure 3-5 Wiring diagram of AC input cable

Installation check

Check hardware installation

  • Check that all screws are tight (especially those used for electrical connections), and check that flat washers and spring washers are installed correctly.
  • Check that the rectifier module is fully inserted into each slot and locked correctly.

Check electrical connections

  • Check that all air switches are OFF.
  • Check that flat washers and spring washers are securely installed on all terminals and that all OT terminals are intact and properly connected together.
  • Check that the input and output power cables and ground cables are properly connected.

Check cable installation

  • Check that all cables are securely connected.
  • Check that all cables are neatly lined up and connected tightly to their nearest cables without twisting or over-bending.
  • Check that the cable labels are correct, firm, and oriented in the same direction.

Chapter 4 System Commissioning

Notice

  • The following commissioning steps may cause power failure or generate alarms. You need to notify the alarm center before and after the operation is completed.
  • Commissioning personnel must undergo corresponding technical training, and be sure to refer to the commissioning instructions.
  • The commissioning process is a live operation. Please stand on a dry insulating material during operation. Do not wear metal objects such as watches and necklaces. Tools should be insulated.
  • During equipment commissioning, be sure to check whether the status of related units or components meets the requirements before any “closing operation”.
  • During the operation, if other people are not allowed to operate, a prohibition sign should be hung on the power distribution equipment: “It is forbidden to close the switch, and someone will operate it”.
  • In the process of commissioning, you should observe while commissioning, and immediately shut down if any abnormality is found, and continue after the cause is identified.
AC power-on debugging
  1. Step 1. Measure the input voltage of the AC input circuit breaker, which should be between 380V ± 10 % AC.
  2. Step 2, turn the AC input circuit breaker ON, and measure the output voltage of the AC input circuit breaker, which should be between 220V± 10% AC.
  3. Step 3, check the running indicator (yellow, green, red) , it should be always on.
  4. Step 4, the monitoring display is normal, and the voltage parameters are correct
View system parameters

Instruction

For the function description of the system, see YD-DEMS-VD2-DC – The user manual of touch screen operation

  1. Step 1. Click “System Diagram” on the main screen to enter the system diagram screen, and check the SPD status, the status of the main circuit switch and the status of each branch switch.
  2. Step 2, click “Data View” to enter the incoming line data screen, click “Basic Electrical Parameters” on the incoming line data screen to check the incoming line voltage.
  3. Step 3, click “Data View” to enter the incoming line data screen, click “Power Data Record” on the incoming line data screen.
  4. Step 4: On the incoming line data screen, click the “Feeder” bar box on the left side of the screen to enter the feeder data screen and click the data item to view the parameters.
  5. Step 5. Click “Alarm/Event” to enter the alarm record screen, and click the bar box of “Real-time Alarm”, “Historical Alarm”, “Operation Record”, “Power Record”, “Incoming Line Record”, and “Feeder Record”. Switch the screen.
Other processing
  1. Put the removed panel or cover back in place.
  2. The exterior paint should be kept intact. If the paint is peeled off, the paint should be repainted immediately to prevent corrosion.
  3. Clean up the site, exit the site.

System Maintenance

Routine maintenance

Table 5-1 Daily maintenance list

maintenance item Maintenance content
Check items Inspection Method
Electric Is the voltage output normal?
branch voltage exceeds the set range See 5.2 Alarm Troubleshooting
Troubleshooting Is the indicator light normal?

fault alarm
Exterior| No peeling or scratching of the system coating| Visual inspection| Damaged or deformed appearance of the system| Repaint, repair the shell
Ground detection| Is the grounding point of the power distribution cabinet connected to the grounding bar of the equipment room?| Visual inspection, screwdriver, wrench and other tools| Check that the cable connection between the grounding point of the power distribution cabinet and the grounding row of the equipment room is unreliable| Re-tighten the grounding point or replace the grounding cable

Alarm Troubleshooting

SPD failure

Possible Causes:

  1. Damaged SPD.
  2. The SPD detects that the signal cable is disconnected.

Approach:

  1. 1. Check the SPD trip window, if it is red, the SPD needs to be replaced.
  2. Check whether the signal detection cable is loose, and if so, fix the cable.

Main circuit switch status display open

Possible Causes:

  1. The main molded case circuit breaker is not closed.
  2. The SPD detects that the signal cable is disconnected.

Approach:

  1. Check if the molded case switch is open, if so, close the molded case switch.
  2. Check whether the signal detection cable is loose, and if so, fix the cable.

Shunt switch status display open

Possible Causes:

  1. Each branch MCB is not closed.
  2. The state collection line of each shunt switch falls off.

Approach:

  1. Check whether the corresponding miniature circuit breaker is open, if so, close the corresponding miniature circuit breaker.
  2. Check whether the corresponding branch signal detection cable is loose, and if so, fix the cable.

Shunt switch status display open

Possible Causes:

  1. The setting of the AC overvoltage alarm point is unreasonable.
  2. Grid failure.

Approach:

  1. Check if the AC input cable is loose, if so, fix the input cable. Check whether the AC overvoltage alarm setting value is reasonable. If not, adjust it according to the actual situation.
  2. Check whether the AC input voltage of the power system exceeds the “AC overvoltage alarm point”, and if so, handle the AC input fault.

AC under-voltage

Possible Causes:

  1.  The AC under-voltage alarm point setting is unreasonable.
  2. Grid failure.

Approach:

  1. Check whether the AC under-voltage alarm setting value is reasonable. If not, adjust it according to the actual situation.
  2. Check whether the AC input voltage of the power system is lower than the “AC under voltage alarm point”, and if so, handle the AC input fault.

HMI and host

Possible Causes:

  1. The communication cable is disconnected.
  2. Device address dialing error.

Approach:

  1. Check if the communication cable is loose, if so, fix the cable.
  2. Check whether the device dialing code is correct, if so, redial the dialing code.
Component fault location

Air switch fault location

Air switch failures mainly include the following phenomena:

  • After dealing with the short circuit fault of the rear end of the air circuit breaker, the ON/OFF adjustment of the air circuit breaker cannot be performed.
  • The voltage at the input terminal of the air switch is normal and in the ON state, the voltage across the air switch is greater than 1V.
  • The voltage at the input terminal of the air switch is normal and in the OFF state, the resistance value at both ends of the air switch is less than 1kΩ.

Monitoring module fault location

The faults of the monitoring module mainly include the following phenomena:

  • The monitoring module has obvious faults, such as: crash, no response when booting, LCD display problems, buttons cannot be operated, etc.
  • When the alarm is enabled, the monitoring module does not generate an alarm when the power system fails.
  • After the monitoring module generates an alarm, it is detected that the power system does not have the fault indicated by the alarm.
  • When the communication line is normal, all subordinate devices displayed in the monitoring module are interrupted in communication.
  • When the rectifier module and the communication line are normal, the communication between the monitoring module and all rectifier modules is interrupted.
  • The monitoring module cannot set parameters or view running information.
    Logo

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Delta User Manuals

Related Manuals