PAX Technology 9302539 Calima Fan for Ventilation All Indoor Spaces User Manual
- June 4, 2024
- Pax Technology
Table of Contents
**PAX Technology 9302539 Calima Fan for Ventilation All Indoor Spaces User Manual
**
IMPORTANT!
Read these instructions carefully before use. The fan is designed for fixed
installation.
Electrical installation must be carried out by a registered electrical
installation company. Standard EN 60335 provides the following guidance:
This appliance can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience
and knowlede if they have been given supervision or instruction concerning use
of the appliance in safe way and understand the hazards involved.
Children shall not play with the appliance. Cleaning and user maintenance shall notbe made by children without supervision.
Thank you for choosing a Pax fan – the original!
The Pax Calima fan is designed to boost the basic ventilation of your home*
and provide forced ventilation of humidity and odours from wet rooms
(WC/bathroom/shower room/laundry room) or to function as a heat distributor.
The fan can be fitted in ducts with natural draught ventilation (ceiling,
Figure 1) and/or without natural draught ventilation (wall, Figure 2)**.
Calima fits ducts with a diameter of 100 – 140 mm. For larger ducts (up to 160
mm diameter), the Pax cover plate (accessory) must be used.
To ensure that it neither disturbs nor is disturbed by other ventilation, the
fan must always be installed in its own duct. Make sure that the duct is clear
of obstructions. Avoid insect mesh, filters and other objects that may
obstruct the flow of air. To prevent condensation in natural draught ducts (in
the winter), the ducts must be insulated where they pass through unheated
areas such as cold attics.
The fan is designed for use in a temperature range of 5 to 50 °C. If the fan
is installed in a cold area or if it has been stored in a cold place before
installation, it may run slowly when started for the first time. The fan will
work normally when it reaches its working temperature.
Make sure that air can enter the room, for example through a large gap under the door or by using the Pax transfer air unit (accessory). We recommend the use of genuine Pax accessories to ensure that the fan works properly and delivers the correct capacity.
- Primarily detached houses and holiday homes, but can also be used in multi-dwelling buildings with separate, airtight, well insulated ventilation ducts.
** With natural draught ventilation, air is carried upwards through ventilation ducts and out of the building (see Figure 1). For natural draught ventilation to work, the air inside the building must be warmer (and therefore lighter) than the air outside. Natural draught ventilation therefore works best during the winter. Natural draught ventilation will be reduced or absent if the temperature differential (inside/outside) is small or non-existent in the summer.
For this reason, buildings are often poorly ventilated when the weather is warm. This can be remedied with a Pax fan that works continuously at low speed
Accessories
-
Backdraught shutter Calima 8127-1:
-
Cover plate white 8143-6, for duct dimensions Ø140-160
Installation
Installation preparation
Detach the motor unit by grasping it as shown in Figure (A). Pry off the motor
unit by leveraging against the cover with your knuckles. Ensure that you have
the motor unit in a secure grip so you do not drop it when it is detached.
Then detach the wall frame by using a screwdriver to press the lock button as
shown in Figure (B). Then remove the top of the cover from the wall frame as
shown in Figure (C)
Fit the enclosed wall gasket as shown in the figure (C_1).
New Installations
New installations require holes using a Ø110 mm hole saw (Figure D).
Pax wall pipes and external louvres are available as accessories (Figure E).
The fan’s wall seal has a short spigot which fits inside the Ø100 mm pipe.
Make sure when mounting to adapt the length of the wall pipe so it does not
push back the wall seal so the fan impeller cannot rotate. Always customise a
wall pipe, existing or new, so it ends about 5 mm inside the wall surface
where Calima is to be installed. The wall frame with its seal is prepared with
5 cable entry points (Figure F) for concealed electrical connection or
surface-mounted cable using the dimension shown in Figure G.
Use ageing-resistant sealant to seal around cables that are laid through the
wall seal.
Use ageing-resistant sealant to seal around cables that are laid through the wall seal.
Make sure that the seal is properly installed on the wall frame; place it in
the appropriate place and centre it in the wall pipe. The wall frame can be
levelled horizontally by placing a spirit level on its support points (Figures
H and I).
Mark the three attachment points for the appropriate screws to the substrate
(Figure J).
Pax follows industry regulations for Safe Water installation, drilling and
sealing with silicone according to the instructions for wooden walls and
concrete.
These must be followed. (See page 25).
Tighten the screws so that the seal forms a seal against the wall.
Always use a qualified electrician
All 100-240 V electrical connections must be performed by a qualified
electrician. The power must be cut during all electrical work on the product.
The wall frame contains an electronics component with terminal blocks for
100-240 V AC and 12 V DC.
Electrical connection can be made according to the wiring diagram on page
20-21.
NB: As the two legs of the motor unit protrude into the wall frame, and one
leg is in contact with the switching contact, cables must be laid in the wall
frame as shown in Figures K/K1 (100-240 V AC connection) and L (12 V DC
connection), so that no cables block the path of the leg.
ELECTRICAL CONNECTION 100-240VAC
NB! Wiring of 100-240 V AC must be performed by a qualified electrician.
NB! The integrated all-pole switch S only functions at 100-240 V AC wiring
Calima auto:
100-240 V AC 50 / 60Hz
Factory-set for continuous basic ventilation, automatic forcing at elevated
humidity levels and under the influence of changes in light.
Option of accelerated air flow rate with 15 minutes’ run-on using manual
switch T.
Calima switch-operated, with run-on time:
(Can be combined with backdraught shutter)
100-240 V AC 50/60 Hz
Must be selected via Pax App.
Start/stop via manual switch T.
(start = max. RPM, stop = 15 minutes run-on time)
Calima humidity-controlled:
(Can be combined with backdraught shutter)
100-240 V AC 50/60 Hz
Must be selected via Pax App.
Basic setting, automatic start/stop at changes in humidity level.
Possibility to start / stop via manual switch T.
(start = max. RPM, stop = 15 minutes run-on time)
NOTE: With T switch activated, the fan always returns to max. speed after
contact via app.
Any changes are only activated when the T input is switched off and the run-on
time has elapsed.
Bluetooth LE: -12dBm EIRP (63µW), nominal 2450MHz.
Radio Equipment Directive (RED)
Pax hereby assure that this type of Bluetooth radio equipment complies with
RED Directive 2014/53 / EU.
The full text of the EU Declaration of Conformity can be found at the
following URL: www.pax.se
Calima heat distributor:
100-240 V AC 50/60Hz
Must be selected via Pax App.
Basic settings, starts at 25 ° C, stops at 22 ° C.
Calima switch-operated on / off
(Can be combined with backdraft shutter)
100-240 V AC 50 / 60Hz
Must be selected via Pax App.
Start / stop via manual switch L.
Connection of 100-240 V AC and 12 V DC must not be done simultaneously (Figure M)
No 100-240 V cables may be laid over the electronics component (Figure N)
ELECTRICAL CONNECTION 12 V DC
NB. Pax recommends that electrical connection of 12 V DC be performed by a qualified electrician.
NB. Maximum variation for 12 V DC voltage of 10 – 13.6 V DC
Calima auto:
12 V DC (switch C always on)
Factory-set for continuous basic ventilation, automatic forcing at elevated
humidity levels and under the influence of changes in light.
Calima switch-operated on/off:
(Can be combined with backdraught shutter) 12 V DC
Must be selected via Pax App.
Start/stop via manual switch C.
Calima humidity-controlled:
(Can be combined with backdraught shutter)
12 V DC (switch C always on)
Must be selected via Pax App.
Basic setting, automatic start/stop at changes in humidity level.
Calima heat distributor:
12 V DC (switch C always on)
Must be selected via Pax App.
Basic setting, starts at 25 °C, stops at 22 °C.
NB. For 12VDC always use switches intended for direct current, C.
Mounting the cover on the wall frame
The fan is double insulated and must not be earthed. When the electrical
connection has been completed, place the cover back over the wall frame by
fitting the hook in the wall frame in the hole in the cover (Figure O).
Next, close the cover over the wall frame (Figure P). Ensure the catch the
screwdriver is pointing to (Figure Q) engages properly.
Make sure that the cover is firmly seated in the hook on the wall frame and
latch by gently pulling the cover.
Finally, put the motor unit in place (Figure R). Be careful when putting the
motor unit in place. The legs and the impeller can be damaged if the unit is
forced in at an angle. A distinct ‘click’ sound confirms that the unit is in
place. Check that the impeller rotates freely before switching on (Figure S).
Pax Calima® Automatic functions and settings via app
Basic setting:
Pax Calima is programmed to cope with the vast majority of installations.
The fan works continuously with a basic flow of approximately 30 m³/h. When
the light changes, when a light is switched on or when shadows change when
someone moves in the room, the flow increases to approximately 60 m³/h.
If the humidity rises rapidly, for example when the shower is on, the fan goes
up to maximum flow at approximately 95 m³/h.
When the humidity has been removed, the fan reverts to the basic flow of
approximately 30 m³/h.
If other settings or functions are desired, download the Pax app from the App
Store or Google Play.
Requirements for functionality via app
Versions of the operating system is updated continuously, for information go
to App Store or Google Play.
Fault indication:
Red LED on the fan indicates power failure when the calendar function has been
activated.
Reset by syncing the app with the fan.
Activate the app:
You have to have a code to activate the app. The code is unique to each fan.
Enter the code or scan it using your phone. Your unique code is on the right
leg of the motor unit (Figure T).
Learn more about all the possibilities with our app at www.paxsweden.com
Strong solvents must not be used on the fan.
The fan must not be dipped in or sprayed with water.
For the fan to continue to function and maintain its capacity, it must be
cleaned at least twice a year, more often if necessary.
-
Before cleaning, switch off the power to the fan.
For a 100-240 V connection, use the all-pole switch in Figure U by switching it off (0). For a 12 V connection, turn off the power at the appropriate external switch.
-
Detach the motor unit by grasping it as shown in (Figure V). Pry off the motor unit by leveraging against the cover with your knuckles. Ensure that you have the motor unit in a secure grip so you do not drop it when it is detached.
-
Clean the opening, the duct and the motor unit with a damp cloth (if necessary, use a mild detergent).
-
The impeller is cleaned directly on the motor (NB the impeller cannot be detached).
-
If the fan has an external backdraught shutter, the shutter blades should be cleaned gently. The backdraught shutter must be located in the duct between the fan and the outer wall.
-
Replace the motor unit in the frame member
Recycling
Discarded fans should be submitted as electronic waste to a recycling centre.
Safe Water Installation
This product conforms to industry regulations for Safe Water Installation.
The supplier guarantees that the product will function correctly if industry
regulations and the product’s instructions are complied with.
All holes for screws must be made as shown in Figures X and Y.
For wooden wet room walls (Figure X), drill only through the coating and
waterproofing.
NB: Never drill through any plywood.
Fill the entire hole with age-resistant sealing compound. Use plumbing screws.
Screw through the plywood or into the studwork.
For concrete wet room walls (Figure Y), drill the appropriate hole depth for
the plug.
Fill the hole with age-resistant sealing compound.
Push the plug into the hole.
Fill the entire plug with age-resistant sealing compound.
Use plumbing screws and screw the product in place.
Warranty conditions
The Pax Calima has a five-year warranty for defects in manufacturing and materials. The warranty is subject to the following conditions:
- The fan must have been installed by a qualified electrician.
- The fan must have been assembled and installed in accordance with the advice and instructions in this user and installation guide.
- The fan must be cleaned regularly in accordance with the advice and instructions in this user and installation guide.
- The fan must be installed and used indoors.
- The fan must not be used in exposed environments (for example in industrial or other environments where there is a risk of the fan being exposed to solvents, a high dust density, gases, etc.).
Pin Code for app
To access the application:
PIN-code for your fan can you find on the right leg of the motor unit.
Write in the PIN- code into the square above to save it.
Copyright © Volution Sweden AB
009-500002-H_220207
We accept no liability for printing errors and reserve the right to make
changes to materials and designs.
References
- Handdukstorkar och badrumsfläktar i unik design Pax.se
- Paxnorge.no
- PAX - Paremman sisäilman puolesta Paxsuomi.se
- Startpage Paxsweden.com
- Forside Paxventilation.dk