E98PDIHJ Mechanical Timer Socket
Product Information
Technical Specifications
- Power supply: 230V
- Own Consumption: Based on model
- Charge LED: Yes
- Incandescent lamps: Supported
- Halogen lamps: Supported
- Halogen + electronic transformer: Supported
- Halogen + ferromagnetic transformer: Supported
- Fluorescent: Supported
- Relay status: NO or NC
- Detection angle: Adjustable
- Detection field: Adjustable
- Brightness Level: Adjustable
- Timing: Adjustable
- Sensitivity: Adjustable
- Protection: Weatherproof
- Working temperature: Based on model
Product Usage Instructions
Installation
-
Ensure the power supply is 230V.
-
Mount the unit in a suitable location with the desired
detection angle and field. -
Connect the appropriate lamps or transformers based on your
setup.
Adjustments
Use the provided controls to adjust the brightness level,
timing, and sensitivity according to your preferences.
Maintenance
Regularly clean the unit and ensure it is free from any
obstructions that may affect detection.
Troubleshooting
If the unit malfunctions, refer to the user manual for
troubleshooting steps or contact customer support.
Frequently Asked Questions (FAQ)
Q: What should I do if the detection range is too short?
A: Try adjusting the detection angle and sensitivity settings to
increase the range.
Q: Can this product be used with LED lamps?
A: This product is designed for use with incandescent, halogen,
and fluorescent lamps. Consult the user manual for compatibility
with LED lamps.
Q: What is the recommended working temperature for this
product?
A: Refer to the product specifications for the recommended
working temperature range.
EN
INSTRUCTION MANUAL
Ref. DM TEC B1B, DM TEC B1N and DM TEC B1P CEILING SURFACE MOUNTING BLUETOOTH
360º MOTION DETECTOR
TECHNICAL SPECIFICATIONS
Power supply Own Consumption
Charge LED
Incandescent lamps Halogen lamps 230V
Halogen + electronic transformer Halogen +
ferromagnetic transformer Fluorescent
Relay status NO or NC Detection angle
Detection field
Adjustments Brightness Level
Timing
Sensitivity
Protection
Working temperature
230V~ ±10% ~50/60Hz <1W
16A cos = 1 400W 3.000W 3.000W
3.000W
2.400W
1.300W (130µF) Select from DINUY Configure APP
Circular, 360º 360º in a maximum of Ø7m with 2,5m height and 18ºC
DINUY Configure App 5 to 2000Lux, or Disabled
1 seg. till 60 minutes 5 values adjustable through
DINUY Configure App IP40, Class II
10ºC .. +45ºC
CHARACTERISTICS
“3 in 1” indoor detector, for ceiling surface mounting with the following
operating modes: – Motion Detector; – Presence Detector; – Twilight Switch.
It has a switching channel with a 16A relay. ZCT (Zero Crossing Technology),
which allows to protect the
contactors of the relay and manage high loads. Highly sensitive PIR sensor,
which detects the slightest movement
within its coverage area. It incorporates a red LED indicator that helps test
the correct motion
detection of the device. It incorporates a blue LED indicator to identify that
the detector is
Bluetooth enabled. Configuration and adjustment through the DINUY CONFIGURE
App.
FUNCTIONING
This multifunction detector can be configured in any of the following
operating modes – Motion Detector: Detects small movements based on the
temperature difference and measures the brightness only when the luminaire is
off. Once the luminaire is switched on, it will not be switched off until
there are no people present. Typical application example: Transit areas,
corridors. – Presence Detector: Detects small movements based on the
temperature difference and measures luminosity constantly. Typical application
example: Work areas and constant presence. Offices. – Twilight Switch:
Lighting control based on the amount of exterior lighting. Typical application
example: Areas affected by exterior lighting.
This detector automatically switches the lighting based on the detection of
the slightest movement of people and the level of natural light.
Possibility of connecting several detectors in parallel, which makes it
possible to expand the area to be covered in a single lighting line.
In Presence Detector mode, while the lighting is on due to the presence of a
person within its coverage area, the sensor will compare the measured natural
light with the setpoint set in the configuration (Brightness Parameter): – If
the natural light is below the set Brightness setting, the timing will reset
when new movement is detected and the lighting will continue on. – If the
natural light is above the Brightness setting, the timer will not reset when
new movement is detected and the lighting will turn off when the time set in
the Timer expires.
DIMENSIONS
45mm 35mm
118,5mm
MOUNTING
A. Choice of location: Since the detector responds to temperature changes,
please avoid the following conditions: – Avoid pointing the detector towards
areas or objects whose surfaces are highly reflective or subject to rapid
changes in temperature. – Avoid mounting the detector near heat sources, such
as convectors, air conditioners, dryers… – Do not direct the detector towards
light sources. – Avoid directing the detector towards objects that move with
the wind, such as curtains or small trees or bushes. Consider the direction of
movement when installing the detector.
Lateral movement: Greater sensitivity
Movement towards the center: Lower sensitivity
B. Access terminals and anchors: To access only to separate the cover.
C. Mounting:
COVERAGE
It is recommended to mount the detector at a height of 2.5m, thus achieving a
detection area of 7m in diameter.
2,5m
Ø 3m Ø 7m
Area of max. sensitivity
INSTALLATION AND WIRING
ATTENTION: Dangerous voltage!.
· Installation of electric equipment must be carried out by qualified
professionals.
· Before you start making any connections, disconnect the power supply to
avoid any risk.
· When some kinds of lamps blow, they can produce a very high current which
could damage the detector.
NOTE Once the detector is connected to the power supply, it is necessary to
wait 30 seconds for it to stabilize. During this time, the device activates
its output and does not respond to movement.
Follow one of the following diagrams to make the connection:
– Simple installation of a single detector:
L
230V~ 50/60Hz
N
Load
N L LL
– Installation of two detectors in parallel with a single charge:
230V~ 50/60Hz
L N
Load
N L LL
N L LL
SETTINGS
ALL OPERATION SETTINGS OF THIS DETECTOR ARE EXCLUSIVELY CONFIGURED THROUGH THE
DINUY CONFIGURE APP (see below).
To consult about the installation of the App, menus, application of the
configuration, or the resolution of problems related to the configuration,
please consult the instructions for use of the DINUY CONFIGURE App.
The basic operating values of this detector are ‘Timing’, Brightness´ and
Sensitivity’ can be adjusted using the DINUY CONFIGURE App.
– Timing Setting (TIME) Factory setting: 1 minute. Sets the time the charge
will be on after detecting movement. The ignition time can be adjusted between
1sec. and 60min. After the first detection, the time will be reset and, each
time a new movement is detected, the timing will begin again. – Brightness
Adjustment (LUX) Factory setting: Disabled. Its function is to set the maximum
luminosity value, above which the detector will not activate the load despite
detecting movement. Furthermore, in mode Presence Detector if the set
brightness level is exceeded while the lighting is activated (presence of
people), the load will be automatically deactivated. The user can set this
value depending on their requirements, between 5 and 2.000 Lux and disabled.
If this parameter is set to a very low value, close to 5 Lux, the detector
will only work in the dark, at night (in case there is not enough natural
light). If this parameter is set to the value Disabled, the detector will work
in any light level, regardless of natural light, both day and night. –
Sensitivity Adjustment Factory setting: Very High. This parameter allows you
to limit the detection range and adapt the operation to, for example, unstable
environments. You can choose between 5 adjustment options: · Very High · High
· Medium · Low · Very low
FUNCTION TEST The purpose of this test is to check and adjust the coverage
area of
the detector when it is first connected.
NOTE Once the detector is connected to the power supply, it is necessary to
wait 30 seconds for it to stabilize. From that moment, the operation test can
be carried out. The red LED visually indicates when motion is detected and
works
both when the load is on and off. This red LED will light up whenever motion
is detected. Walk from outside the coverage area inward until the lights turn
on. The blue LED indicates that the Bluetooth is activated and ready to
receive the programming from the smartphone. Once the detector is powered at
230V~ the Bluetooth will be activated for a while. After this time the
Bluetooth will be automatically deactivated. This time can be selected from 10
minutes to 4 hours. The factory setting is 2 hours. Once you have verified
that the operation is correct, save the detector settings with the desired
values
COVER SHUTTER
A cover shutter is included in the same detector box, which allows you to
exclude areas from the detection area, as well as reduce the coverage area
according to needs.
In the event that the default detection area of the detector is too large, or
it is detected in areas that are not desired, this area can be easily reduced
simply by using the shutter covers.
PROBLEM RESOLUTION
When the detector stops working normally, review the possible faults and the
suggested solutions in the following table that will help you solve the
problem:
Problem The lamps do not turn on
The lamps don’t go out
Lamps turn on and off cyclically
Possible cause No voltage reaching the detector Bad connection
Suggested Solution Properly power the detector
Check the connections and follow the instructions diagram
Poorly adjusted LUX Check Brightness Adjustment setting
Defective charge Very high ambient temperature The set shutdown time is too
long
The detector trips unexpectedly Bad connection
Replace the load
Wait for the ambient temperature to reduce and test the detector Reduce
disconnection time and check that the lamps turn off after the time has
elapsed
Stay out of the coverage area to avoid false activations
Make sure the charging and power are connected well
The load (fluorescence, contactor…) is generating harmonics that continuously trigger the detector with each switching
Move the detector away from the load or place an RC harmonic suppression filter (AC DM-002) between L’ and N
Unwanted activations
Lamps work in reverse, turning on when they should be off, and off when they
should be on
Heat sources, drafts, reflective surfaces or objects that move due to wind
The Output Polarity is set in reverse
Avoid directing the detector towards heat sources, such as air conditioners, fans, radiators. Make sure there are no objects that move with the wind. Reduce the Sensitivity of the detector with the APP Dinuy Configure. Make sure you change the Output Polarity in the ADVANCED MENU
Read User Manual Online (PDF format)