COLUMBIAVAC KLC9300GB Portable Air Conditioner User Manual

June 10, 2024
COLUMBIAVAC

COLUMBIAVAC KLC9300GB Portable Air Conditioner

Product Information

The KLC9300GB/KLC9300GC is a portable air conditioner that can be controlled via Wi-Fi using iOS and Android devices. The device uses flammable R290 gas, so it should be handled with caution to avoid any fire hazards. Before use, it is important to read the instruction manual carefully. Any repair or maintenance work should only be carried out by authorized personnel.

Safety Warnings

  • The device should stand upright for 24 hours before first use to avoid compressor damage.
  • When working with refrigeration systems, it is necessary to ensure that safety checks are carried out to minimize the risk of fire.
  • Hot work should only be carried out on refrigeration equipment or related components with appropriate safety equipment available.
  • The device should be placed in a well-ventilated area to avoid system tampering or hot work.
  • The ventilation should safely disperse the released refrigerant and preferably release it outside into the atmosphere.

Product Usage Instructions

  1. Before first use, ensure that the device has been standing upright for 24 hours.
  2. Place the device in a well-ventilated area.
  3. Make sure that the air outlet pipe (18) is not bent or folded sharply, and that the air flows freely.
  4. If you want to control the device using a smartphone app, download the app from the website www.eldom.eu and follow the instructions provided.

The disposal of used electrical and electronic equipment (applies to European Union countries and other European countries with separate waste-collection systems).
This symbol on the product or its packaging indicates that it should not be classified as household waste. It should be handed over to an appropriate company dealing with the collection and recycling of electrical and electronic equipment. The correct disposal of the product will prevent potential negative consequences for the environment and human health resulting from hazardous substances present in the product. Electrical devices must be handed over to restrict their re-use and further treatment. If the device contains batteries, remove them, and hand them over to a storage point separately. DO NOT THROW EQUIPMENT INTO THE MUNICIPAL WASTE BIN. Material recycling helps to preserve natural resources. For detailed information on how to recycle this product, please contact your local authority, the recycling company, or the shop where you bought it.

  • Appliance is filed with flammable gas R290.
  • Before using the appliance, read the manual.
  • Before installing the appliance, read the installation manual.
  • Any repairs you need, contact the nearest authorized Service Centre and ctrictly follow manufacturer’s instruction only.

CAUTION: RISK OF FIRE
The figures in this Instructions Manual might slightly differ from those actually displayed on the device. Note the actual figures.

SAFETY INSTRUCTIONS

PRECAUTIONS

  •  Carefully read the Instructions Manual, and familiarize yourself with the warnings on the device before installing and commissioning. The Instructions Manual contains the correct installation and operation principles of the air conditioner. Non-observance of the principles can lead to voiding the warranty.
  • This device can be used by children of at least 8 years of age; by persons with reduced physical and mental abilities; and by persons with no experience or knowledge of the equipment, if supervised or instructed on its safe use so that the risks associated with it are understood. Children should not play with the device. Unattended children should not be allowed to perform the cleaning and maintenance of the device.
  • Unintended use of the air conditioner can lead to voiding the warranty.
  •  The device should not be operated by persons who have no knowledge of the equipment or have not read the Instructions Manual. This particularly applies to children.
  •  The device is intended for use only with R-290 (propane) gas as the refrigerant. R290 is a gaseous coolant which meets EU Environmental Directives.

Information on equipment using R290 gaseous refrigerant

  •  Read all warnings carefully.
  •  Do not pour the refrigerant into the atmosphere.
  •  R-290 (propane) is flammable and heavier than air.
  •  It first accumulates at the lower levels, but can be distributed by air movement (e.g., by fans).
  •  If propane is present, or its presence is even just suspected, it is forbidden to allow unqualified personnel to try to find the cause.
  •  The R-290 (propane) used in the device is odour less.
  •  No odour does not mean that no gas is escaping.
  •  In the event of leak detection, evacuate all persons from the room, ventilate the room, and contact the local fire service in order to report the propane leak.
  •  Do not allow anyone into the room until a qualified service technician arrives and affirms that entering the room is safe.
  •  Do not use tools other than those recommended by the manufacturer during defrosting and cleaning.
  •  The device should be placed in the area free of fixed ignition sources (e.g., an open fire, or operating gas or electric equipment).
  •  The device‘s components are specially designed for the use of propane, and have no ignition or sparking properties. Replace the components only with identical spare parts.
  • Do not allow the housing to be punctured. Do not burn the device.
  •  The unit must be installed, operated, and stored in a room bigger than 11 m2.
  •  If the unit is installed, operated, or stored in a room without ventilation, measures should be implemented preventing the accumulation of leaking coolant, the causing of a fire, or an explosion hazard due to the ignition of the coolant caused by an electric heater, stove, or other ignition sources.
  •  Store the device in a way which avoids mechanical damage.
  •  Persons operating or modifying the cooling circuit must hold the appropriate authorizations from an accredited organization to guarantee the professional handling of the refrigerant, which must be confirmed by reputable industry organizations.
  •  All repairs should be performed according to the manufacturer’s recommendations. Maintenance and repairs requiring the employment of experts in other fields should be carried out under the supervision of a person authorized to use flammable refrigerants.
  • This device is intended for home use only, as described in this Instructions Manual. Do not use the device for purposes other than those specified in this Instructions Manual.
  • Installing the air conditioner does not require special knowledge, and may be performed by the user in accordance with the guidelines and figures contained in the Instructions Manual. Improper installation can result in water leakage, or electrocution, or irreparable damage to the unit. Eldom Sp. z o. o. shall not be liable for any potential losses due to the improper use of the device.
  •  The unit must be installed in accordance with the national regulations for electrical systems. Before connecting the device to the mains, check that the mains current parameters (voltage) correspond to the parameters indicated on the device. The device’s outlet plug should be completely plugged into the power socket. Do not use extension cords or multi-outlet adapters to connect the device’s power cord. Remove the outlet plug from the socket if the device is not to be used for an extended period. If the unit has not been used for a long time, check that the air inlets and outlets are unobstructed before starting the device.
  •  Connect the device only to an earthed power socket.
  • Keep the device at least 50 cm away from flammable material and substances (e.g., alcohol, etc) or pressurized containers (e.g., aerosols).
  • The power cord and plug are intended for the final disconnection of the device from the power supply, which is why they must be easily accessible at all times.
  • Switch off the air conditioner and disconnect it from the power supply during a storm.
  •  Do not insert hands or objects into the air outlets.
  • Do not put any objects on the device.
  •  Do not step or sit on the device.
  • Do not insert fingers or other objects into the air outlet.
  • Do not touch the air inlet or the aluminium fins of the unit.
  •  Before cleaning, repair, maintenance, or inspection, switch the air conditioner off and disconnect it from the power supply.
  •  Clean the device with a dry, soft, cloth. If the unit’s housing is heavily soiled, you may use a cloth soaked in a household cleaning agent. Do not wipe or clean the air conditioner with chemical solvents such as petrol and alcohol.
  • Do not immerse or expose this unit to precipitation, moisture, or other liquids.
  • Do not operate with wet hands. Avoid water spillages on the unit.
  • Do not immerse or expose this unit to precipitation, moisture, or other liquids.
  •  Do not leave the device unattended when it is running. Do not tilt or overturn the device.
  •  Place and operate the unit away from splashes of water or oil.
  •  If during the device’s operation, the user detects any irregularities, such as a strange odour or sound, smoke, steam, fire, over heating of housing or outlet plug, fuse failure, or interruptions to the operation of other devices, immediately switch the device off, disconnect from the power supply, and contact an authorized service centre.
  •  Do not use if the power cord is damaged, or if the unit has been dropped or otherwise damaged. The repair of the device should be entrusted to an authorized service centre; see information on the warranty card and on the website www.eldom.eu.
  •  All modifications, and the use of spare parts or device elements other than the original ones, are prohibited, and can pose a hazard to the safety of use.
  • Under the risk of voiding the warranty, the user may not perform any repairs, modifications, or disassembly, of the device’s housing.
  •  There are no user-serviceable parts inside the unit.
  • All modifications, and the use of spare parts or device elements other than the original ones, are prohibited, and can pose a hazard to the safety of use.
  • Persons operating or modifying the cooling circuit must hold the appropriate authorizations from an accredited organization to guarantee the professional handling of the refrigerant, which must be confirmed by reputable industry organizations.
  • All repairs should be performed according to the manufacturer’s recommendations. Maintenance and repairs requiring the employment of experts in other fields should be carried out under the supervision of a person authorized to use flammable refrigerants. If there is any lack of understanding of any information, or help is needed, contact the dealer’s service centre
  • BEFORE THE FIRST USE OF THE DEVICE, MAKE SURE THAT IT HAS BEEN PLACED IN THE VERTICAL POSITION FOR 24 HOURS; OTHERWISE, THE DEHUMIDIFIER COMPRESSOR CAN BE DAMAGED.

SAFETY WARNINGS FOR SERVICING
Observe all these warnings when performing the following works while servicing the dehumidifier with R290.

  1. Area inspections
    Before performing any works on circuits containing flammable refrigerants, it is necessary to perform safety inspections of the area to make sure that the risk of ignition is minimized. When repairing the cooling system, the following precautions must be implemented before working on the system.

  2. Working procedure
    Tasks should be carried out under the controlled procedure so that the risk of the presence of flammable gas or vapours is minimized when work is being carried out.

  3. General workplace
    All maintenance personnel and others working in the place should be instructed in the nature of the work. Avoid working indoors. The area around the workplace must be isolated. Make sure that conditions in the area have been secured by control flammable materials.

  4. Refrigerant-presence inspection
    Before and during performing work, check the area with a suitable refrigerant detector to ensure that the technician is aware of potentially flammable atmospheres. Make sure that the leak-detection equipment used is suitable for use with flammable refrigerants, i.e., does not cause sparking, is properly sealed, and is intrinsically safe.

  5. Fire-extinguishing accessibility
    If any hot operations are to be carried out on the cooling equipment or any associated parts, suitable fire-extinguishing equipment should be available. Dry powder or CO2 fire extinguisher should be placed adjacent to the charging area.

  6. No ignition sources
    No persons performing work on cooling systems, which consists of uncovering pipes containing flammable refrigerant may use any ignition sources in a manner creating a risk of fire or explosion. All possible sources of ignition, including cigarette smoking, should be kept at a suitable distance from the place of installation, repair, removal, and disposal, during which the flammable refrigerant can be released into the environment. Before starting work, examine the area around the equipment to ensure that there is no fire or ignition hazard. Place “No smoking” signs.

  7. Ventilated area
    Make sure that the area is outside or properly ventilated before performing any repair or maintenance works on the system or hot operations. A certain degree of ventilation should be maintained during the work-performing period. Ventilation should safely disperse the released refrigerant, and preferably release it outside into the atmosphere.

  8. Cooling equipment inspections
    In the event of the replacement of electrical components, they should be appropriate for the purpose, and compliant with the relevant specifications. The manufacturer’s guidelines for maintenance and servicing must be observed at all times. If any doubts, contact the technical department of the manufacturer. The following inspections should be performed concerning the systems using flammable refrigerants:

    •  The size of the load is compliant with the room size in which components containing refrigerant are installed;
    •  Ventilation units and outlets are working properly, and are not clogged up;
    • When using an intermediate cooling circuit, check for the refrigerant;
    •  The marking of the device is still visible and legible. Markings and signs which are illegible must be corrected;
    •  Cooling pipes or components should be installed in a place where there is a low likelihood of their coming into contact with any substance which can cause corrosion of components containing refrigerant, unless these components are made of materials inherently resistant to corrosion, or adequately protected against corrosion.
  9. Electrical-equipment inspections
    Repairs and maintenance of the electric components include preliminary safety inspections and component-control procedures. In the instance of a fault which could risk safety, do not connect the power supply to the circuit until it has been satisfactorily rectified. If the fault cannot be rectified immediately, but further action is necessary, an appropriate temporary solution must be implemented. This should be reported to the device owner so that all parties are informed. Preliminary safety inspections include:

    •  condenser discharge: should be done in a safe way to avoid the possibility of sparking;
    •  no covering of live electrical components or wiring when charging, recovering, or cleaning the system;
    • earthing continuity
  10. Repairs to sealed components
    During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation. Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure that the apparatus is mounted securely. Ensure that seals or sealing materials have not degraded to the point that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specifications.

  11. Repair to intrinsically safe components
    Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.

  12. Cabling
    Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.

  13. Detection of flammable refrigerants
    Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.

  14. Removal and evacuation
    When breaking into the refrigerant circuit to make repairs – or for any other purpose –conventional procedures shall be used. However, for flammable refrigerants it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to:

    •  remove refrigerant;
    •  purge the circuit with inert gas;
    •  evacuate;
    •  purge with inert gas;
    •  open the circuit by cutting or brazing.
      The refrigerant charge shall be recovered into the correct recovery cylinders. For appliances containing flammable refrigerants the system shall be purged with oxygen-free nitrogen to render the appliance safe for flammable refrigerants. This process may need to be repeated several times. Compressed air or oxygen shall not be used for purging refrigerant systems. For appliances containing flammable refrigerants, refrigerants purging shall be achieved by breaking the vacuum in the system with oxygen-free nitrogen and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final oxygen-free nitrogen charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take place. Ensure that the outlet for the vacuum pump is not close to any potential ignition sources and that ventilation is available.
  15. Leak detection methods
    The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing process.

  16. Charging procedures
    In addition to conventional charging procedures, the following requirements shall be followed.

    • Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.
    •  Cylinders shall be kept in an appropriate position according to the instructions.
    • Ensure that the refrigerating system is earthed prior to charging the system with refrigerant.
    • Label the system when charging is complete (if not already).
    • Extreme care shall be taken not to overfill the refrigerating system.
    • Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The system shall be leak-tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.
  17. Decommissioning
    Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of recovered refrigerant. It is essential that electrical power is available before the task is commenced.

    • Become familiar with the equipment and its operation.
    •  Isolate system electrically.
    • Before attempting the procedure, ensure that:
    •  mechanical handling equipment is available, if required, for handling refrigerant cylinders;
    • all personal protective equipment is available and being used correctly;
    • the recovery process is supervised at all times by a competent person;
    • recovery equipment and cylinders conform to the appropriate standards.
    • Pump down refrigerant system, if possible.
    • If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
    •  Make sure that cylinder is situated on the scales before recovery takes place.
    •  Start the recovery machine and operate in accordance with instructions.
    • Do not overfill cylinders (no more than 80 % volume liquid charge).
    • Do not exceed the maximum working pressure of the cylinder, even temporarily.
    • When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off.
    •  Recovered refrigerant shall not be charged into another refrigerating system unless it has been cleaned and checked.
  18.   Labelling
    Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. For appliances containing flammable refrigerants, ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.

  19. RECOVERY
    When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely.

When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure-relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of all appropriate refrigerants including, when applicable, flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely.

SPECIAL RECOMMENDATIONS:

  •  Ambient temperature range for the device is 5°C -35°C.
  •  Install the portable air dryer on a flat location with a large space, without obstacles. Leave a 30cm minimum space between the unit and the wall.
  • The device must be installed in accordance with national installation regulations.
  • The plug shall be always accessible after its installation.
  • Always place the appliance in a vertical position, in order to maintain the compressor in good working condition.
  • Do not tilt the device in any direction as spilled water can damage the device.
  •  Do not use the appliance near gas or other inflammable liquids.
  •  Do not block the air outlet and inlet ventilation. Do not place heavy objects on the device.
  • Do not use spray (insecticides, painting) or any other inflammable products near the appliance as the plastic case may be deformed. The unit may sustain electrical damage.

POWER SOURCES

  •  The plug has to be well fixed and should not be damaged.
  • Do not plug in the appliance with an adaptor.
  •  Plug into the wall socket before switching on the appliance then press on the ON/OFF button.

OPERATING INSTRUCTION

PORTABLE AIR CONDITIONER KLC9300GB / KLC9300GC

GENERAL DESCRIPTION Front:

  1. Control panel

  2. Blinds

  3.  Infrared receiver

  4. Front housing

  5. Wheels
    Rear:

  6.  Space for remote control

  7. Filter I

  8.  Handles

  9.  Place for winding the cable

  10. Water drainage – continuous

  11. Filter II

  12.  Power cord

  13.  Water drainage – manual

  14. Outlet hole

  15.  Rear housing
    Additional accessories:

  16.  Remote control (power supply: 2×1.5V AAA)

  17.  Connector

  18.  Outlet tube

  19. Mounting panel

  20.  Drain hose

Control panel (1) / remote control (16)

  • A. switching the device on/off

  • B. selection of the mode of operation of the device (Cool, Fan, Dry, Heat)

  • C. operation mode indicators
    (Cool, Fan, Dry, Heat)

  • D. display (panel)

  • E. buttons for setting the temperature and time

  • F. indicators of fan operation mode
    (High, Mid, Low)

  • G. selection of fan speed

  • H. selection of TIMER function – automatic switching on or off of the device

  • I. Wi-Fi indicator

  • J. display (remote control)

  • K. activation of shutter oscillation
    (remote control only)

  • L. button to change the displayed degrees C/F (remote control only)

INTENDED USE

The KLC9300G air conditioner is designed to improve thermal comfort in living spaces. The air can be cooled or dehumidified with it. It will also work as a standard fan. The device can be controlled from a smartphone by means of the installed application (download from www.eldom.eu).

TIPS
In order to reach the target temperature as soon as possible during the cooling process, the doors and windows in the air-conditioned room should be closed, and the use of heat emitting devices should be kept to a minimum. Do not expose yourself to cold air for long periods of time, as this is harmful to your health.

INSTALLATION

Choosing the place for installationKLC9300GB Portable Air Conditioner
02 The device must be placed vertically on a flat surface, in a dry and spacious place. Leave at least 50 cm of free space round the unit. The unit must be installed in accordance with the national regulations for electrical installations. Before connecting to the mains, make sure that the mains-current (voltage) parameters correspond to those specified on the device. The mains plug of the device should be fully plugged into the mains socket. Do not use extension cords or splitters to connect the mains cable of the device. If the device will not be used for an extended period of time, unplug the power cord from the wall outlet. If the unit has not been used for a long time, check that the air inlets and outlets are not blocked before restarting the unit.

Installation of the outlet pipe
Attach the connector (17) to one end of the outlet pipe and attach the other end of the pipe to the outlet (14) The connector (17) can be mounted on the mounting panel (19) and then placed in the window KLC9300GB Portable Air
Conditioner 04The length of the panel (19) is adjustable.

Incorrect installation
The outlet pipe (18) should not be excessively bent Improper installation can result in the improper operation of the device. There must be no sharp bends in the outlet pipe (18). The air leaving the unit must flow freely.

NOTE
The length of the outlet pipe is designed in accordance with the air conditioner’s specifications. Do not replace the outlet pipe with other hoses, or extend it, as this can cause malfunction of the unit. The maximum length of the straightened outlet pipe is 1500 mm. Use the shortest pipe length possible. It is most recommended to install the outlet pipe horizontally.

THE OPERATION OF THE APPLIANCE

All changes in the settings are confirmed with a sound signal.
The air flow from the air conditioner should not be directed directly at people. The cold air flow can be controlled by means of the louvres (2) – “K” button on the remote control. Changing temperature units from degrees C to degrees F is possible using the “L” button on the remote control.
CAUTION: The air conditioner has a compressor protection feature which, depending on a number of factors, allows it to be switched on with a short time delay (3 minutes).

Remote control (16)
The remote control is powered by two 1.5V AAA batteries. To replace the batteries, unscrew the screw located on the back of the remote control. Gently lever up and remove the batteries. Insert the new batteries and gently press down until the catch snaps into place. Pay attention to the polarity. Do not combine batteries of different types or new batteries with used batteries
CAUTION: Do not dispose of spent batteries with household waste. Dispose of spent batteries at designated battery collection points or return them to the seller. Never throw batteries into fire.

Cooling
Turn on the device by pressing the „A” button. Press the „B” key until the „C-Cool” indicator lights up. Use button „E” to set the temperature in the range from 16°C to 30°C. The fan speed is set using button „G”. The current room temperature is shown on the display „D”. The air-conditioner will turn off when the room temperature drops below the set temperature. When using cooling mode, the exhaust air pipe must be connected to the unit.
To turn off, press the “B” button (change mode) or the “A” button (turn off the device).

Heating
Turn on the appliance with the “A” button. Press the “B” button until the “C- Heat” indicator is illuminated. Use the “C” and “E” buttons to set the temperature. Fan speeds are set with the “G” button. The display “D” shows the current room temperature. The air conditioner will turn on when the room temperature drops below the set temperature. When using heating mode, the exhaust air pipe must be connected to the unit. To turn off, press the “B” button (change mode) or the “A” button (turn off the device).

Dehumidification
Turn on the device by pressing the „A” button. Press the „B” key until the „ C- Dry” indicator lights up. The dehumidifier runs continuously – the humidity level cannot be set. In the dehumidifying mode, the airflow speed and temperature are adjusted automatically by the air conditioner processor for the most efficient operation.
CAUTION: When using the dehumidifying function, you must connect the drain hose to the top water outlet! (see WATER DRAINAGE METHODS).

  • When using the dehumidifying function, you must remove the hot air exhaust duct from the appliance.

To turn off, press the “B” button (change mode) or the “A” button (turn off the device).

Fan
In this mode, only the unit’s fan operates. Switch on the appliance using button „A”. Press the „B” button until the „C-Fun” indicator is illuminated. The fan speed is set using button „G”. To turn off, press the “B” button (change mode) or the “A” button (turn off the device).

Start delay
The device must be switched off but connected to the power supply. Press button „H” – digits will start flashing on the display „D”. Use button „E” to select a time from 1 to 24 hours. After selecting the time, wait for the digits on the display to stop flashing. Select the required operating mode of the device (information above).
CAUTION: When the delayed start function is set, the appliance will start working in the last used mode (cooling, heating, dehumidifying or fan).

Timer
Turn on the device by pressing the „A” button. Select the required operating mode of the device (information above). Press button „H” – digits will start flashing on the display „D”. Use button „E” to select a time from 1 to 24 hours. After selecting the time, wait for the digits on the display to stop flashing. To disable the function, press the „A” button and use the „E” button to set the numbers „00” on the display. Changing the operating mode is possible when the „TIMER” function is active.

WATER DISCHARGE
The unit is equipped with an evaporation system. Liquefied water is used to cool the condenser, which increases the cooling efficiency and reduces energy consumption. If the water level in the system reaches the maximum level, the letters (FT) will appear on the display „D” and the compressor will stop running.

Manual removal of water Switch off the device and move it to a place where water can be drained from it. Remove the plug from the hole „13” and carefully drain the water.
Insert the plug into the hole „13”. Turn the device on again.

Constant water drainage Turn the appliance off. Remove the plug from the hole „10”. Mount the rubber tube (20) and place its other end in a container, e.g. a bucket.
CAUTION: The dish or the drainage system must be located below the outlet (10).

  • Do not switch on the appliance with an open water outlet to avoid the risk of flooding the floor with the condensate.

MAINTENANCE

Note: Turn off the unit and unplug it before any maintenance or repair begins to avoid electric shock.

Cleaning
Unplug the unit before any cleaning. Clean the housing with a soft moisture cloth. Do not use chemical solvent (such as benzene, alcohol, gasoline). The surface may be damaged or even the whole case may be deformed. Do not sprinkle water on the unit.

Air filter Clean the air filter every 2 weeks. If the air filter is blocked with dust, the efficiency will reduce. Open the air filter cover upwards, and then take out the air filter. Wash the air filter by immersing it gently into warm (about 40oC) water with a neutral detergent, rinse it and dry it thoroughly in a shaded place.

End of season
Please drain the water. Keep the unit running in Fan mode for two hours until the inside of the unit is dry. Turn off the unit and unplug it. Clean the air filter and after dry it thoroughly, reinstall it. Remove the exhaust pipes and keep them carefully. Wrap the unit with the plastic bag and keep it in a dry place.
CAUTION: Keep the appliance in a dry room. Secure all accessories against damage.

SIMPLIFIED EU DECLARATION OF CONFORMITY

Hereby, Eldom Sp. z o.o., ul. Pawła Chromika 5a, 40-238 Katowice declares that the radio equipment type PORTABLE AIR CONDITIONER KLC9300GB / KLC9300GC is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following internet address: https://www.eldom.eu/wsparcie/deklaracje/

 TROUBLE SHOOTING

Never attempt to repair or open the appliance on your own. Any repair by an unqualified person will void the product warranty and may cause injury or damage. If any of the problems listed in the table below occurs or the troubleshooting procedure fails, contact a professional technical support centre.

PROBLEM CAUSE SOLUTION
**** Air conditioner does not work
  •  No power
  • The “FL” indicator light comes on
  •  The room temperature is too low.
  • ****  The room temperature is below the cooling temperature setting.

|

  •   Plug the appliance to the mains and turn it on
  • Drain the condensate.
  •  The air conditioner should be operated between 7°C and 35°C
  •  Change the temperature setting.

Poor cooling performance|

  •  The air inlet/outlet is obstructed

|

  •   Remove the obstruction

**** Loud noise|

  • The air conditioner does not stand on

|

  •  Move the air conditioner to a level floor, which may reduce the noise.

Compressor does not work|

  •   The automatic overheating
  • protection feature is on.

|

  •  Wait    3    minutes    for    thecompressor to cool down and then restart the appliance

**** E1 error code on the display|

  • **** Circuit temperature sensor error

|

  •   Turn off the appliance, wait for it to cool down, turn it on again; if the error persists, contact the service

E2 error code on the display| External   temperature  sensor error|

  •   Wait until the temperature is in the room temperature range; if the error persists, contact the service

 TECHNICAL DATA

The full technical specification can be found on the rating plate located on the device.

  • Power cord length: 1.80 m
  • Noise: 65 dB
  • Energy efficiency rating:
  • Cooling: A
  • Heating: A+
  • APPENDIX

Air conditioner schematic diagramKLC9300GB Portable Air Conditioner
09

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals