DITEK D100-120 Industrial Surge Protective Device Instruction Manual

September 20, 2024
DITEK

DITEK D100-120 Industrial Surge Protective Device

INSTALL INSTRUCTIONS

NOTICE: This SPD should be installed by a licensed contractor per all applicable National and Local Electrical Codes and the following instructions.

APPLICATION
Type 1 SPD for hardwired installation on a 120/208 VAC 3-phase Wye electrical service.

INSTRUCTIONS

Caution: Measure all voltages to verify applied voltage does not exceed the voltage rating of the unit. Reference the Expected System Voltages chart below. Improper installation voids the warranty.
NOTE: Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical Amperes. The recommended circuit breaker size is 30 Amps. This SPD contains no serviceable parts.

  1. Turn off the power at the main breaker or service disconnect before beginning installation.
  2. Remove the front cover from the electrical panel.
  3. Determine the ideal mounting position of the SPD by orienting the unit as close as possible to the position of the circuit breaker selected for the SPD connection.
  4. Remove a 1/2” knockout in the electrical panel or drill a 1/2” NPT hole in the electrical panel.
  5. See the Illustrations Page on the back side of this document for instructions on assembling the included liquid-tight conduit and connector. The conduit length can be cut down shorter if desired.
  6. Remove “Locknut A” from the conduit connector.
  7. Feed all wires, conduit and 1/2” NPT connector through the knockout hole in the panel, and finally tighten “Locknut A” on the conduit connector.
  8. Connect the Ground wire (Green) to the Ground bus of the panel.
  9. Connect the Neutral wire (White) to the Neutral bus of the panel.
  10. Connect the (3) Phase wires (Black) to the load side of the 3-pole circuit breaker.
  11. Securely mount the enclosure with appropriate anchors by using the mounting feet located at each corner.
  12. After all connections have been made and no hazards exist, replace the panel cover and restore power.DITEK-D100-120-Industrial-Surge-Protective-Device-FIG-1 DITEK-D100-120-Industrial-Surge-Protective-Device-FIG-2 DITEK-D100-120-Industrial-Surge-Protective-Device-FIG-3