DITEK D50-2401 Phase Industrial Surge Protective Device Installation Guide

August 23, 2024
DITEK

DITEK D50-2401 Phase Industrial Surge Protective Device

Specifications :

  • Model: D50-2401, D50-240HW
  • Manufacturer: DITEK Corporation
  • Voltage: 240 VAC single phase
  • Type: Type 1 SPD
  • Maximum Amperes: 100,000 rms symmetrical Amperes
  • Recommended Circuit Breaker Size: 20 Amps

Product Usage Instructions

Installation:

  1. Turn off the power at the main breaker or service disconnect before beginning installation.
  2. Remove the front cover from the electrical panel.
  3. Determine the ideal mounting position of the SPD by orienting the unit as close as possible to the desired position.

Caution :
Measure all voltages to verify applied voltage does not exceed the voltage rating of the unit. Improper installation voids the warranty

Important Note :
This SPD should be installed by a licensed contractor in accordance with all applicable National and Local Electrical Codes.

FAQ :

  • Q: What should I do if the applied voltage exceeds the unit’s voltage rating?
    A: If the applied voltage exceeds the unit’s voltage rating, do not proceed with the installation. Contact a licensed contractor for further assistance.

  • Q: Can the SPD be installed on any circuit?
    A: The SPD is suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical Amperes. The recommended circuit breaker size is 20 Amps.

INSTALL INSTRUCTIONS

D50-2401, D50-240HW
DITEK Corporation
ONE DITEK CENTER 1720 Starkey Road Largo, FL 33771

  • NOTICE : This SPD should be installed by a licensed contractor in accordance with all applicable National and Local Electrical Codes and the following instructions.
  • APPLICATION
  • Type 1 SPD for hardwired installation on a 240 VAC single phase electrical service.

INSTRUCTIONS :

Caution : Measure all voltages to verify applied voltage does not exceed the voltage rating of the unit. Reference the Expected System Voltages chart below. Improper installation voids the warranty.
NOTE : Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical Amperes. Recommended circuit breaker size is 20 Amps. This SPD contains no serviceable parts.

  1. Turn off the power at the main breaker or service disconnect before beginning installation.
  2. Remove front cover from the electrical panel.
  3.  Determine the ideal mounting position of the SPD by orienting the unit as close as possible to the position of the circuit breaker selected for the SPD connection.
  4. Remove a 3/4” knockout in the electrical panel or drill a 3/4” NPT hole in the electrical panel.
  5. Feed all wires through the knockout hole in the panel and tighten the included 3/4” locknut to the SPD fitting.
  6. Connect the Ground wire (Green) to the Ground bus inside of the panel.
  7. Connect the Neutral wire (White) to the Neutral bus inside of the panel.
  8. Connect the Phase wire (Black) to the load side of the single pole circuit breaker.
  9. If desired, secure the enclosure with appropriate anchors by using the mounting feet on the SPD enclosure.
  10. After all connections have been made and no hazards exist, replace panel cover and restore power.

DRAWN BY: BRIAN AYCOCK 12/13/23 APPROVED BY: MIKE MOLINARI 12/13/23
DITEK TECHNICAL SUPPORT 1-888-472-6100
www.diteksurgeprotection.com

DOC # INT-100134-001 PART NO. 191566 REV. 5