DITEK D50-120/240HL Industrial Surge Protective Device Installation Guide

August 22, 2024
DITEK

DITEK D50-120/240HL Industrial Surge Protective Device

Product Specifications

  • Model: D50-120/240HL
  • Manufacturer: DITEK Corporation
  • Voltage Compatibility: 120/240 VAC 3 phase High Leg Delta
  • Type: Type 1 Surge Protective Device (SPD)
  • Maximum Amperes: 100,000 rms symmetrical Amperes
  • Recommended Circuit Breaker Size: 20 Amps
  • Serviceability: Contains no serviceable parts

Product Usage Instructions

  1. Turn off the power at the main breaker or service disconnect before beginning installation.
  2. Remove the front cover from the electrical panel.
  3. Determine the ideal mounting position of the SPD by orienting the unit as close as possible to the position indicated.
  4. Measure all voltages to ensure they do not exceed the voltage rating of the unit based on the Expected System Voltages chart.
  5. Install the SPD in accordance with all applicable National and Local Electrical Codes.

FAQ

  • Q: Can this surge protective device be installed on a single-phase system?
    • A: No, this device is designed for use on a 3-phase High Leg Delta electrical service.
  • Q: What should I do if the applied voltage exceeds the unit’s rating?
    • A: If the voltage exceeds the unit’s rating, do not proceed with the installation and seek professional assistance.

INFORMATION

NOTICE

  • This SPD should be installed by a licensed contractor in accordance with all applicable National and Local Electrical Codes and the following instructions.

APPLICATION

  • Type 1 SPD for hardwired installation on a 120/240 VAC 3 phase High Leg Delta electrical service.

INSTALLATION INSTRUCTIONS

Caution: Measure all voltages to verify applied voltage does not exceed the voltage rating of the unit. Reference the Expected System Voltages chart below. Improper installation voids the warranty.
NOTE: Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical Amperes. Recommended circuit breaker size is 20 Amps. This SPD contains no serviceable parts.

  1. Turn off the power at the main breaker or service disconnect before beginning installation.
  2. Remove front cover from the electrical panel.
  3. Determine the ideal mounting position of the SPD by orienting the unit as close as possible to the position of the circuit breaker selected for the SPD connection.
  4. Remove a 3/4” knockout in the electrical panel or drill a 3/4” NPT hole in the electrical panel.
  5. Feed all wires through the knockout hole in the panel and tighten the included 3/4” locknut to the SPD fitting.
  6. Connect the Ground wire (Green) to the Ground bus inside of the panel.
  7. Connect the Neutral wire (White) to the Neutral bus inside of the panel.
  8. Connect the (1) High Leg Phase wire (Red) to the load side of the 1-pole High Leg circuit breaker.
  9. Connect the (2) Phase wires (Black) to the load side of the 2-pole circuit breaker.
  10. If desired, secure the enclosure with appropriate anchors by using the mounting feet on the SPD enclosure.
  11. After all connections have been made and no hazards exist, replace panel cover and restore power.

BREAKER PANEL

EXPECTED SYSTEM VOLTAGES

Contact

DITEK Corporation

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals