DITEK D50 Series Surge Protection Installation Guide

August 23, 2024
DITEK

DITEK D50 Series Surge Protection

Specifications

  • Model: D50-120/2401
  • Manufacturer: DITEK Corporation
  • Input Voltage: 120/240 VAC split phase
  • Type: Type 1 Surge Protective Device (SPD)
  • Maximum Amperes: 100,000 rms symmetrical Amperes
  • Recommended Circuit Breaker Size: 20 Amps
  • Serviceable Parts: None

Product Usage Instructions

  1. Pre-Installation:

    • Ensure installation is carried out by a licensed contractor
      following all National and Local Electrical Codes.

    • Verify that the applied voltage does not exceed the unit’s
      voltage rating by referencing the Expected System Voltages chart.

    • Turn off power at the main breaker or service disconnect before starting installation.

  2. Installation Steps:

    • Remove the front cover from the electrical panel.
    • Determine the ideal mounting position of the SPD by aligning it as close as possible to the desired location.
    • Follow the manufacturer’s guidelines for mounting the SPD securely in place.
    • Connect the SPD to the electrical service as per the wiring diagram provided. Double-check all connections and ensure they are secure.
  3. Post-Installation:

    • Restore power at the main breaker or service disconnect.
    • Check for proper functionality by testing the SPD according to the manufacturer’s recommendations.
    • Keep the area around the SPD clear for easy access in case maintenance is required.

Frequently Asked Questions (FAQ)
Q: What should I do if the applied voltage exceeds the unit’s rating?
A: If the voltage exceeds the unit’s rating, do not proceed with installation. Contact a qualified electrician to address the issue.

DITEK Corporation
ONE DITEK CENTER 1720 Starkey Road Largo, FL 33771

INSTALL INSTRUCTIONS

D50-120/2401

NOTICE: This SPD should be installed by a licensed contractor in accordance with all applicable National and Local Electrical Codes and the following instructions.

APPLICATION

Type 1 SPD for hardwired installation on a 120/240 VAC split phase electrical service.

INSTRUCTIONS
Caution: Measure all voltages to verify applied voltage does not exceed the voltage rating of the unit. Reference the Expected System Voltages chart below. Improper installation voids the warranty.
NOTE: Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical Amperes. The recommended circuit breaker size is 20 Amps. This SPD contains no serviceable parts.

  1. Turn off the power at the main breaker or service disconnect before beginning installation.
  2. Remove front cover from the electrical panel.
  3. Determine the ideal mounting position of the SPD by orienting the unit as close as possible to the position of the circuit breaker selected for the SPD connection.
  4. Remove a 3/4” knockout in the electrical panel or drill a 3/4” NPT hole in the electrical panel.
  5. Feed all wires through the knockout hole in the panel and tighten the included 3/4” locknut to the SPD fitting.
  6. Connect the Ground wire (Green) to the Ground bus inside of the panel.
  7. Connect the Neutral wire (White) to the Neutral bus inside of the panel.
  8. Connect the (2) Phase wires (Black) to the load side of the 2-pole circuit breaker.
  9. If desired, secure the enclosure with appropriate anchors by using the mounting feet on the SPD enclosure.
  10.  After all connections have been made and no hazards exist, replace panel cover and restore power.

DRAWN BY: BRIAN AYCOCK 12/13/23 APPROVED BY: MIKE MOLINARI 12/13/23
DITEK TECHNICAL SUPPORT 1-888-472-6100 www.diteksurgeprotection.com
DOC # INT-100121-001 PART NO. 191545 REV. 7