DITEK D200-277 SPD Surge Protector Instruction Manual

September 5, 2024
DITEK

DITEK D200-277 SPD Surge Protector

Specifications

  • Model: D200-277/4803Y
  • Manufacturer: DITEK Corporation
  • Voltage: 277/480 VAC
  • Phase: 3 phase Wye
  • Application: Type 1 Surge Protective Device (SPD)
  • Maximum Amperes: 100,000 rms symmetrical Amperes
  • Recommended Circuit Breaker Size: 30 Amps

FAQs

  • Q: How do I know if the SPD is functioning correctly?
    • A: The SPD includes an audible alarm that signals when protection is compromised. Regularly check for this alarm and ensure it is connected to a power source.
  • Q: Can the conduit length be adjusted during installation?
    • A: Yes, the conduit length can be cut shorter if necessary. Refer to the instructions for details on adjusting the conduit length.

IMPORTANT SAFETY INSTRUCTION

NOTICE: This SPD should be installed by a licensed contractor according to all applicable National and Local Electrical Codes and the following instructions.
APPLICATION

Type 1 SPD for hardwired installation on a 277/480 VAC 3-phase Wye electrical service.

INSTRUCTIONS:

Caution: Measure all voltages to verify applied voltage does not exceed the voltage rating of the unit. Reference the Expected System Voltages chart below. Improper installation voids the warranty.
NOTE: Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical Amperes. Recommended circuit breaker size is 30 Amps. This SPD contains no serviceable parts.

  1. Turn off the power at the main breaker or service disconnect before beginning installation.
  2. Remove the front cover from the electrical panel.
  3. Determine the ideal mounting position of the SPD by orienting the unit as close as possible to the position of the circuit breaker selected for the SPD connection.
  4. Remove a 3/4” knockout in the electrical panel or drill a 3/4” NPT hole in the electrical panel.
  5. See the Illustrations Page on the back side of this document for instructions on assembling the included liquid-tight conduit and connector. The conduit length can be cut down shorter if desired.
  6. Remove “Locknut A” from the conduit connector.
  7. Feed all wires, conduit, and 3/4” NPT connector through the knockout hole in the panel, and finally tighten “Locknut A” on the conduit connector.
  8. Connect the Ground wire (Green) to the Ground bus inside of the panel.
  9. Connect the Neutral wire (White) to the Neutral bus inside of the panel.
  10. Connect the (3) Phase wires (Black) to the load side of the 3-pole circuit breaker.
  11. Securely mount the enclosure with appropriate anchors by using the mounting feet located at each corner.
  12. After all connections have been made and no hazards exist, replace the panel cover and restore power.

Audible Alarm Operation:

  • This SPD includes an audible alarm that will sound when the unit has self-sacrificed and is no longer providing protection.
  • To silence the audible alarm, power to the SPD needs to be disconnected via the circuit breaker or disconnect.

Dry Contact Connection: This is a Form C Dry Contact Circuit, 0.9A, 240VAC maximum input. Normally Open (NO)=Black Wire, Common (COM)= Red Wire, Normally Closed (NC)=White Wire.
Note: Remote Alarm Wires To Be Connected To Class 1 Circuits Only.

INSTALLATION STEPS

  • STEP 1
  • STEP 2
  • STEP 3
  • STEP 4

MORE INFO

  • DRAWN BY: BRIAN AYCOCK 12/13/23
  • APPROVED BY: MIKE MOLINARI 12/13/23
  • DITEK TECHNICAL SUPPORT 1-888-472-6100
  • www.diteksurgeprotection.com.
  • DOC # INT-100139-001
  • PART NO. 191561
  • REV. 5
  • DITEK Corporation
  • ONE DITEK CENTER
  • 1720 Starkey Road
  • Largo, FL 33771