DITEK D200-277 SPD Surge Protector Instruction Manual
- September 5, 2024
- DITEK
Table of Contents
DITEK D200-277 SPD Surge Protector
Specifications
- Model: D200-277/4803Y
- Manufacturer: DITEK Corporation
- Voltage: 277/480 VAC
- Phase: 3 phase Wye
- Application: Type 1 Surge Protective Device (SPD)
- Maximum Amperes: 100,000 rms symmetrical Amperes
- Recommended Circuit Breaker Size: 30 Amps
FAQs
- Q: How do I know if the SPD is functioning correctly?
- A: The SPD includes an audible alarm that signals when protection is compromised. Regularly check for this alarm and ensure it is connected to a power source.
- Q: Can the conduit length be adjusted during installation?
- A: Yes, the conduit length can be cut shorter if necessary. Refer to the instructions for details on adjusting the conduit length.
IMPORTANT SAFETY INSTRUCTION
NOTICE: This SPD should be installed by a licensed contractor according
to all applicable National and Local Electrical Codes and the following
instructions.
APPLICATION
Type 1 SPD for hardwired installation on a 277/480 VAC 3-phase Wye electrical service.
INSTRUCTIONS:
Caution: Measure all voltages to verify applied voltage does not exceed
the voltage rating of the unit. Reference the Expected System Voltages chart
below. Improper installation voids the warranty.
NOTE: Suitable for use on a circuit capable of delivering not more than
100,000 rms symmetrical Amperes. Recommended circuit breaker size is 30 Amps.
This SPD contains no serviceable parts.
- Turn off the power at the main breaker or service disconnect before beginning installation.
- Remove the front cover from the electrical panel.
- Determine the ideal mounting position of the SPD by orienting the unit as close as possible to the position of the circuit breaker selected for the SPD connection.
- Remove a 3/4” knockout in the electrical panel or drill a 3/4” NPT hole in the electrical panel.
- See the Illustrations Page on the back side of this document for instructions on assembling the included liquid-tight conduit and connector. The conduit length can be cut down shorter if desired.
- Remove “Locknut A” from the conduit connector.
- Feed all wires, conduit, and 3/4” NPT connector through the knockout hole in the panel, and finally tighten “Locknut A” on the conduit connector.
- Connect the Ground wire (Green) to the Ground bus inside of the panel.
- Connect the Neutral wire (White) to the Neutral bus inside of the panel.
- Connect the (3) Phase wires (Black) to the load side of the 3-pole circuit breaker.
- Securely mount the enclosure with appropriate anchors by using the mounting feet located at each corner.
- After all connections have been made and no hazards exist, replace the panel cover and restore power.
Audible Alarm Operation:
- This SPD includes an audible alarm that will sound when the unit has self-sacrificed and is no longer providing protection.
- To silence the audible alarm, power to the SPD needs to be disconnected via the circuit breaker or disconnect.
Dry Contact Connection: This is a Form C Dry Contact Circuit, 0.9A,
240VAC maximum input. Normally Open (NO)=Black Wire, Common (COM)= Red Wire,
Normally Closed (NC)=White Wire.
Note: Remote Alarm Wires To Be Connected To Class 1 Circuits Only.
INSTALLATION STEPS
- STEP 1
- STEP 2
- STEP 3
- STEP 4
MORE INFO
- DRAWN BY: BRIAN AYCOCK 12/13/23
- APPROVED BY: MIKE MOLINARI 12/13/23
- DITEK TECHNICAL SUPPORT 1-888-472-6100
- www.diteksurgeprotection.com.
- DOC # INT-100139-001
- PART NO. 191561
- REV. 5