Specifications
- Model Numbers: DTK-RM12NETS, DTK-RM16NETS, DTK-RM24NETS, DTK-RM12EXTS, DTK-RM16EXTS, DTK-RM24EXTS
- Type: Surge Protective Device (SPD)
- Application: Rackmount surge suppression for shielded Ethernet, PoE, and PoE extender circuits
- Installation Location: Indoors on the equipment rack closest to the point of use
Product Usage Instructions
Pre-installation Checks
Before starting the installation process, please ensure the following:
- Test the circuit to verify the correct operation.
- Turn off the power to the equipment to be protected.
Mounting the Device
The device can be mounted in a standard 19″ equipment rack or wall-mounted using a hinged wall mount bracket.
Grounding
Connect to equipment ground using the ground lug provided on the rear of the faceplate.
Installing Surge Module
- Remove the module or blank bezel for new installation.
- Insert the new surge module into the opening aligning it with the integrated card guides.
- The orientation should match the previous module.
- Press the new surge module in place ensuring it is seated completely and the bezel is flush with the rack mount chassis.
Connecting RJ45 Cables
Connect the RJ45 cables as per the instructions provided.
Power Restoration
After all connections have been made and no hazards exist, restore power to the circuit.
Frequently Asked Questions (FAQ):
Q: Can I install this Surge Protective Device myself?
- A: This SPD should be installed by a licensed contractor following National and Local Electrical Codes.
Q: Where should this device be installed?
- A: The device is intended to be installed indoors on the equipment rack closest to the point of use.
INSTALL INSTRUCTIONS
DTK-RM12NETS, DTK-RM16NETS, DTK-RM24NETS DTK-RM12EXTS, DTK-RM16EXTS, DTK- RM24EXTS
- This Surge Protective Device (SPD) is a high-performance device, designed to protect sensitive electronic loads connected to service panels, fire panels, or where the SPD is directly connected to the electronic device.
- Maximum protection will only be achieved if the SPD is properly installed. Please read and follow the installation instructions carefully.
- NOTICE: This SPD should be installed by a licensed contractor by the National and Local Electrical Codes and the following instructions.
APPLICATION
- Rackmount surge suppression for shielded Ethernet, PoE, and PoE extender circuits with field-replaceable surge modules (DTK-NETMS, DTK-EXTMS).
INSTRUCTIONS
- Note: This device is intended to be installed indoors on the equipment rack closest to the point of use.
- Test the circuit before installation to verify correct operation.
- Turn off the power to the equipment to be protected.
- This device can be mounted in a standard 19″ equipment rack, or wall mounted using a hinged wall mount bracket.
- Connect to equipment ground using the ground lug provided on the rear of the faceplate. Use a minimum #10 AWG wire.
- Make sure the ground wire is as short as possible.
- Ground Resistance Rule: Max ground resistance is 25 Ohms, and 5 Ohms or less is optimum.
- This cannot be an assumed value and must be measured to assure proper grounding.
- Plug the RJ45 tipped cable from the field or supply wiring to the “IN” UNPROTECTED RJ45 jack.
- Plug a 3′ RJ45 male to RJ45 male patch cable from the “OUT” PROTECTED RJ45 jack to the equipment to be protected. The 3′ patch cable will give this device time to react.
- After all connections have been made and no hazards exist, restore power to the equipment.
- Note: The grounding detail for field-installed network surge protectors is not applicable when a shielded protector using STP (Shielded Twisted Pair), with properly tipped shielded RJ45 connectors, has been terminated at a properly mounted and grounded shielded rack mount surge protector. The shield is used to dissipate the excess overvoltage.
- For example, DTK-MRJPOES, a shielded single-channel protector, uses DTK-RM12NETS, DTK-RM16NETS or DTK-RM24NETS shielded rack-mount multi-channel protector.
- Surge Module Install/Replacement: There is no need to remove this protector from the rack, the surge modules can be installed/replaced while it is mounted.
- This product is made up of 12, 16, or 24 individual surge modules.
If 1 or more channels self-sacrifice, or go end of life, you can replace that module as follows:
- Power down the individual circuit before servicing this device.
- Insert a 3/8″ wide flat blade screwdriver into the top-notch of the module’s bezel.
- Gently turn the screwdriver to the right to loosen the bezel.
- Insert the screwdriver into the bottom notch and again gently turn the screwdriver to the right until the module is free of the mating connector located at the rear of the rack mount chassis.
- Remove the module or blank bezel for new installation.
- Insert the new surge module into the opening aligning the surge module with the integrated card guides.
- The orientation should match the previous module.
- Press the new surge module in place making sure it is seated completely and the bezel is flush with the rack mount chassis.
- Connect the RJ45 cables as mentioned in #5 and #6 of the INSTRUCTIONS listed above.
- After all connections have been made and no hazards exist, restore power to the circuit.
- Please see the illustrations page for more details.
- Drawn By: B. Aycock 4-27-18 Created By: R. Mitchell 4-30-18