SCHLAGE 801 Series Local and Remote Monitoring Station Installation Guide
- September 5, 2024
- Schlage
Table of Contents
SCHLAGE 801 Series Local and Remote Monitoring Station
Dimension
Specifications
Audible
- Input Req: 10-28VDC/3-14mA
- Rated: 70dB@ 2ft @28VDC
Hook-Up Leads:
- (4) 24 AWG – 6″ long
- BLK (C) – Common
- RED (U) – Unsecured
- RED (S) – Secure
- RED (A) – Alarm
LED Indicators:
- Input Req: 10-28VDC/3-14mA ea.
- Secure – Green
- Unsecured – Red
- Alarm – Yellow
- Touch Entry Leads:
- 2 Conductor, 22 AWG., 1ft White and Black
IMPORTANT NOTE
Unit must be equipped with MBS option for LEDs to work.
Description
Provides local signal to assure users that a delayed egress system is
functional (code requirement). Includes audible and visual indication of lock
status and delay activation. Mounts in standard single gang electrical box.
Description of Operation
The 801 is wired to a magnetic lock delayed egress system as shown on wiring diagram (page 2).
The following is an operation sequence from normal (secure) condition – through an unauthorized egress attempt – to system reset:
Condition:
- Door closed and secure
- Unauthorized egress attempt
- After 15 (or 30) second delay
- System reset
- Legal release
801 Status
- Alarm Silent – Green LED on
- Alarm Sounds – Green & Red LED on
- Alarm Sounding – Yellow & Red LED on
- Alarm Silent – Green LED on
- Alarm Silent – Red LED on
M490DEP
NOTES:
Fire alarm connection:
For direct connection, fire alarm terminals connect to N.C. Dry Output
Contacts (open on alarm). Conductor count to mag changes to four (4). If power
supply output is controlled by fire alarm, place jumper between fire alarm
terminals.
Customer Service
©Allegion 2017
Printed in U.S.A.
24480857 Rev. 08/17-c