dormakaba RCI 910NTC Narrow Touchless Switch Installation Guide

August 31, 2024
dormakaba

dormakaba RCI 910NTC Narrow Touchless Switch

Specifications

  • Operating Voltage: +10 ~ +24VDC
  • Operating Current: 100mA max @ 12VDC
  • Operating Temperature: -10°C ~ +50°C
  • Relay Output: 1A @ 30VDC
  • Read Range:
    • 3 ~ 5cm (Capacitance)
    • 5 ~ 10cm (Infrared)
    • 5 ~ 7cm (Combined)
  • Operating Humidity: 10 ~ 90%

Product Usage Instructions

Switch Installation

  1. Separate the switch from the back plate by unlatching at the bottom of the switch.
  2. Wire as per the terminal chart provided.
  3. Set DIP switches 1, 2, and 3 for the desired unlock time (1 to 7 seconds) as per the chart.
  4. Set DIP switches 4 thru 8 as per the definition chart.
  5. Secure the back plate in place using the screws provided.
  6. Reattach the switch by snapping it onto the back plate. Press downward and apply pressure near the bottom until the switch snaps into place.

FAQ

  • Q: What should I do if the switch does not respond?
    A: Check the wiring connections to ensure they are correct and secure. Also, verify that the power input is within the specified range.

  • Q: How do I adjust the unlock time of the switch?
    A: Set DIP switches 1, 2, and 3 to configure the desired unlock time between 1 to 7 seconds. Refer to the chart for specific settings.

INSTALLATION

RCI 910NTC
NARROW TOUCHLESS SWITCH
The RCI 910NTC is a dual technologies (Capacitance & Infrared) contactless button. It has a mechanical override provided as back up in case of power or electronic failure. A good choice for mullion mounted applications.

Features

  • Mullion mounted applications
  • 1 – 7 second activation time or Toggle mode
  • 12-24VDC
  • Base Unit current draw @ 12VDC = 27mA resting, 39mA activated @ 24VDC = 17.5mA resting, 23.2mA activated
  • Secondary mechanical switch on Normally Open Circuit – Max. 100mA
  • Selectable Capacitive or Infrared or both sensor activations
  • Optional wireless transmitter and receiver available as accessories
  • Selectable beeper options: permanently on/off or temporary on/off
  • Sync to ground REX input

Mounting Dimensions

Switch Installation:

  1. Separate the switch from the back plate by unlatching at the bottom of the switch.

  2. Wire as per the terminal chart on page 2.

  3. Set DIP switches 1, 2 and 3 for desired unlock time (1 to 7 seconds) per chart on page 2.
    If Dip switches 1, 2 and 3 are all OFF = Toggle mode.

  4. Set DIP switches 4 thru 8 per the definition chart on page 2.

  5. Secure the back plate in place using screws provided.

  6. Reattach the switch by snapping onto the back plate.

  7. Press downward and apply pressure near the bottom until the switch snaps into place.

Specifications

Operating Voltage: +10 ~ +24VDC Relay Output: 1A @ 30VDC
Operating Current: 100mA max @ 12VDC Read Range: 3 ~ 5cm

(Capacitance) 5 ~ 10cm (Infrared)

5 ~ 7cm (Combined)

Operating Temperature:| -10 ~ 70°C| Operating Humidity:| 10 ~ 90%

Wiring Terminals:

No. Color Label Description
1 Blue MO Manually open the door input, Active low
2 Red VDC Power input (+10V ~ +24VDC)
3 Black GRD Grounding
4 Brown RTE_NO **** Relay output (Dry contact)
5 Orange RTE_COMM
6 Purple RTE_NC

Dip Switch Definition:


1

| ON| ****

Adjust working mode and relay activation time

| **** Latching| Enable: Dip Switches 1-3 OFF Disable: Just 1 of 1-3 Dip Switches ON| Trigger once, the relay maintains open, green LED lights.

Trigger again, the relay output close, green LED goes out, blue LED lights.

---|---|---|---|---|---
OFF
2| ON| **** Timing (1 – 7

seconds)

| D-SW1| ON| OFF| ON| OFF| ON| OFF| ON
OFF| D-SW2| OFF| ON| ON| OFF| OFF| ON| ON
3| ON| D-SW3| OFF| OFF| OFF| ON| ON| ON| ON
OFF| Time| 1| 2| 3| 4| 5| 6| 7
4| ON| Manage Infrared induction| Turn OFF infrared
OFF| Turn ON infrared (Default)
5| ON| Buzzer control| Turn OFF the beep
OFF| Turn ON the beep (
Default)
6| ON| Normal| Normal (Default)
OFF| Anti-interference| Can be turned on when there is interference source in the field (
Only for capacitance)
7| ON| Manage Capacitance| Turn OFF capacitance

OFF| Turn ON capacitance (*Default)
8| N/A| N/A| N/A

NOTE: **Do not turn OFF both Infrared (Dip Switch 4) and Capacitance (Dip Switch 7) induction at the same time, otherwise the 910NTC will become a normal mechanical contact exit button.

FCC Regulatory Statements

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:

  1. This device may not cause harmful interference, and
  2. This device must accept any interference received, including interference that may cause undesired operation.

NOTE: ANY CHANGES OR MODIFICATIONS NOT EXPRESSLY APPROVED BY THE PARTY RESPONSIBLE FOR COMPLIANCE COULD VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT.

© 2024 dormakaba Canada Inc
www.dormakaba.us
Phone: 1.800.265.6630
E-mail: sales_RCI@dormakaba.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

dormakaba User Manuals

Related Manuals