DELTA DT3 Series Temperature Controller Instruction Manual

August 28, 2024
Delta

DELTA DT3 Series Temperature Controller

Specifications

  • Model: DT3 Series Temperature Controller
  • Operating Temperature: Up to 50°C
  • Control Type: Open-type
  • Power Switch: Not Furnished
  • Maximum Ambient Temperature: 50°C

Precautions

Before using the DT3 Series Temperature Controller, please adhere to the following safety precautions:

  • Avoid touching AC terminals while power is supplied to prevent electric shock.
  • Ensure power is disconnected when checking the unit inside.
  • Do not modify or disassemble the controller.

Installation Guidelines

When installing the temperature controller:

  • Use recommended solder-less terminals for proper connection.
  • Avoid dust or foreign objects falling inside the controller.
  • Keep away from high voltage and frequency sources.
  • Ensure proper wiring and positioning to prevent interference and damage.

Maintenance

For maintenance of the controller:

  • Turn off power before cleaning the surface with a dry cloth.
  • Avoid touching internal circuits to prevent damage.
  • Avoid using sharp objects on operation buttons to prevent damage.

FAQs

Q: What should I do if the controller malfunctions?
A: If the controller malfunctions, turn off the power, wait for capacitors to discharge, and then follow the troubleshooting steps provided in the manual. Do not attempt to repair the controller while power is on.

Q: Can I extend the thermocouple wires?
A: Yes, you can extend or connect thermocouple wires usingcompensating wires that match the thermocouple types. Ensure correct polarity and keep the wire length as short as possible.

Q: How should I wire a platinum resistance thermometer (RTD) to the controller?
A: When wiring an RTD to the controller, use wires with resistance, keep wire length short, and route power wires away from load wires to prevent interference and noise.

Precaution

Warning! Please comply with safety precautions in the manual. Failure to do so may cause controller or peripheral products malfunction, or even result in serious harm such as fire, electrical injury or other damages.
DANGER! Caution! Electric Shock! Do not touch the AC terminals while the power is supplied to the controller to prevent electric shock. Make sure power is disconnected while checking the unit inside.
This controller is an open-type temperature controller. Be sure to evaluate any dangerous application in which a serious human injury or serious property damage may occur.
This controller is not furnished with a power switch or fuse, therefore a switch or circuit-breaker should be provided in the application system including this unit. The switch or circuit-breaker should be nearby and easily reached by operator, and must have the mark disconnecting means for this unit.

1. Always use recommended solder-less terminals: When integrated into a temperature control system, the maximum ambient temperature is 50 degree C. Fork terminal with isolation (M3 screw, width is 5.8 mm). Make sure all wires are connected to the correct polarity of terminals.
2. Do not allow dust or foreign objects to fall inside the controller to prevent it from malfunctioning. Never modify or disassemble the controller. Do not connect anything to the “No used” terminals.
3. To prevent interference, keep away from high voltage and high frequency when installing. Do not install and/or use the controller in places subject to: (a) Dust or corrosive gases and liquid; (b) High humidity and high radiation; (c) Vibration and shock;

4. Power must be off when wiring and replacing a temperature sensor. 5. Be sure to use compensating wires that match the thermocouple types when extending or connecting the thermocouple wires. 6. Please use wires with resistance when extending or connecting a platinum resistance thermometer (RTD). 7. Please keep the wire as short as possible when wiring a platinum resistance thermometer (RTD) to the controller and please route
power wires as far as possible from load wires to prevent interference and induced noise. 8. This controller is an open-type unit and must be placed in an enclosure away from high temperature, humidity, dripping water,
corrosive materials, airborne dust, and electric shock or vibration. 9. Make sure power cables and signals from instruments are all installed properly before energizing the controller, otherwise serious
damage may occur. 10. Do not touch the terminals in the controller or try to repair the controller when power is on, in order to prevent electric shock. 11. Wait at least one minute after power is disconnected to allow capacitors to discharge, and please do not touch any internal circuit
within this period. 12

. When maintaining the controller, please turn off the power first and use a dry cloth to clean the surface. Do not open the enclosure or
touch the internal circuit to avoid circuit destruction or malfunction. 13. Do not use any sharp objects to press the operation buttons. It may result in button surface damage or even electrical injury when
accidentally access to internal circuit. 14. Measured current: When measuring current, use an external current transformer (CT). 15. When using this CT device, note that the current transformer must not be under an open circuit. 16. When using this CT device, make sure the powered bus on the secondary side of the current transformer has been locked and
secured to the device to prevent the bus falling during the use, which could damage the device. 17. When using the current transformer with the device, use the transformer that is compliant with the IEC-61010-2-032 standard to
ensure safety. 18. When measuring current, a current transformer must be used with the device. 19. Use copper conductors only.

Product Features
DT3 series is a new temperature controller with a high cost-performance ratio. It greatly decreases development costs and time, and improves the functions of temperature control systems. With a high resolution LCD display, it is easy for operators to monitor the temperatures of any environment or occasion. High resolution LCD panel: High contrast and customized display graphics for user’s easy understanding. High-speed sampling time 100ms: High-speed sampling for external temperature measurement and fast output response for
performance requirements of high-precision control. User-defined function keys and modular extension flexibility. Conform with CE international safety certification

Basic System Structure
DT3 obtains the temperature of the controlled environment from the sensor and sending the measured data to the electronic processor. After computing and under a fixed control cycle, it proportionally sends the heating signal via different output interfaces such as relays, voltage pulse or DC currents. By providing power to the heater and raise temperature, DT3 will then control the temperature variation within a specific range.

Temperature Input

Detect Sensor

Temperature controller
Control Output (Realy) (DC Pulse) (DC Current)

Control Environment Heater

Display, LED & Pushbuttons

Odering Information
DT3 Series Panel Size (W×H)
1st output group selection
Power supply 2nd output group selection

DT3: Delta 3 Series Temperature Controller

20: 4848 1/16 DIN W48 × H48mm 30: 7272 W72 × H72mm

40: 4896 1/8 DIN W48 × H96mm 60: 9696 1/4 DIN W96 × H96mm

R: Relay Output, 250Vac, 5A V: Voltage Pulse Output, 12Vdc -10%~+20% C: DC Current Output, 4 ~ 20mA L: Linear Voltage Ouptut 0 ~ 10Vdc

A: 80 ~ 260Vac D: 24Vac and 24Vdc (DT330 7272 model not support)

0: None R: Relay Outupt, 250Vac, 5A V: Voltage Pulse Output, 12Vdc -10%~+20%

2

EVENT inputs/ CT function (optional) 1 EVENT inputs/ CT function (optional) 2 EVENT inputs/ CT function (optional) 3

C: DC Current Output 4 ~ 20mA L: Linear Voltage Ouptut 0 ~ 10Vdc 0: None, 1: Event Input3, 2: RS-485 Communication 0: None, 1: Event Input2, 2: CT measure input2, 3: Retransmission Output 0: None, 1: Event Input1, 2: CT measure input1, 3: Remote Setpoint input

Specifications

Input Voltage Power Consumption Display Method
Sensor Type

80 ~ 260Vac 50/60Hz; 24Vac 50/60Hz ±10%; 24 Vdc ±10% 8VA max. LCD display. Process value (PV): Yellow color, Set point (SV): Green color Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK (Thermal couple measuring location are not intended to be directly connected to the MAINS supply.) 3-wire Platinum RTD: Pt100, JPt100 Resistance: Cu50, Ni120 Analog input: 0 ~ 5Vdc, 0 ~ 10Vdc, 0 ~ 20mA, 4 ~ 20mA, 0 ~ 50mVdc

Control Mode
Control Output
Alarm Output Type Display Accuracy Sampling Rate Vibration Resistance Shock Resistance Ambient Temperature Storage Temperature Altitude Relative Humidity Panel protection level

PID, PID program control (Ramp/Soak control), FUZZY, Self-tuning, Manual and On/FF Relay output: Max. load 250Vac, 5A resistive load Voltage pulse output: 12Vdc, Max. output current 40mA Current output: DC 4 ~ 20m A output (Load resistance: Max. 500) Analog voltage output: 0 ~ 10Vdc Relay output: Max. load 250Vac, 3A resistive load 0 or 1 digit to the right of the decimal point (selectable) Analog input: 0.1 sec/ per scan; Thermocouple or Platinum RTD: 0.1 sec/per scan 10 to 55Hz, 10m/s2 for 10min, each in X, Y and Z directions Max. 300m/ s2, 3 times in each 3 axes, 6 directions 0°C ~ +50°C -20°C ~ +65°C Max. 2000m 35% ~ 80% RHnon-condensing IP66

Operation

There are three modes of operation: operation, regulation and initial setting. When power is applied, controller gets into the operation

mode. Press the

key to switch to regulation mode. If the

key is pressed for more than 3 seconds, controller will switch to the

initial setting mode. Pressing the

key while in the regulation mode or initial setting mode, forces the controller to return to the

operation mode..

PV/SV: Sets the temperature set point and displays the temperature process value. Use

keys to set the temperature set

point.

Setting method: While in any function mode, press the

key to select the desired function and use

keys to change

settings. Press

key to save the changes.

The flow chart below shows how to switch the settings and internal functions:

Regulation Mode

Press key less than 3 sec Press key

Operation ModeParameter Setting:

Operation Mode

Press key more than 3 sec Initial Setting Mode
Press key

Display

Description

Retransmission and Compensation Adjusting

Use

to set temperature set point, use

to switch between the display parameter

RUN/STOP: Control setting RUN or STOP PATTERN: Start pattern setting (set control mode to PROG mode) STEP: Start step setting (set control mode to PROG mode) SELECT POINT: Decimal point setting (0: integral ; 1: one decimal point)

RUN 0 0 1

3

LOCK: Setting lock mode (LOCK1: all; LOCK2: onlySV and F1/F2 key is allowed)

ALARM1 HIGH: Upper limit alarm 1 (display according to the setting in ALARM mode)

ALARM1 LOW: Lower limit alarm 1 (display according to the setting in ALARM mode)

ALARM2 HIGH: Upper limit alarm 2 (display according to the setting in ALARM mode)

ALARM2 LOW: Lower limit alarm 2 (display according to the setting in ALARM mode)

ALARM3 HIGH: Upper limit alarm 3 (set OUT2 to ALARM mode and it will display according to the setting in ALARM mode)

ALARM3 LOW: Lower limit alarm 3 (set OUT2 to ALARM mode and it will display according to the setting in ALARM mode)

ALARM1 HIGH PEAK: High peak value 1

ALARM1 LOW PEAK: Low peak value 1

ALARM2 HIGH PEAK: High peak value 2

ALARM2 LOW PEAK: Low peak value 2

ALARM3 HIGH PEAK: High peak value 3 (display when OUT2 is set to alarm mode)

ALARM3 LOW PEAK: Low peak value 3 (display when OUT2 is set to alarm mode)

OUT1: Display and adjust output value of 1st output group

OUT2: Display and adjust output value of 2nd output group (display when OUT2 is set to Heating/Cooling Mode)

OUT1 MAX: Upper limit % of 1st output group (perform linear calculation again)

OUT1 MIN.: Lower limit % of 1st output group

OUT2 MAX: Upper limit % of 2nd output group (display when OUT2 is set to Heating/Cooling Mode)

OUT2 MIN: Lower limit % of 2nd output group (display when OUT2 is set to Heating/Cooling Mode)

CT1: Display CT1 current (display when external CT is connected to CT1)

CT2: Display CT2 current (display when external CT is connected to CT2)

Display, LED & Pushbuttons

to return to target temperature setting.

OFF 4.0 4.0 4.0 4.0 4.0 4.0
0.0 0.0 100.0 0.0 100.0 0.0

Initial Setting ModeParameter Settings:

Display

Description

INPUT: Set input type (refer to “Temperature Sensor Type & Temperature Range Chart” for the selection of Thermocouple or Platinum Resistance types.) TEMP. UNIT: Set temperature unit /it wil not be displayed when in analog input mode

TEMP. HIGH: Set up upper temperature limit (the upper limit setting is different for different types of sensor)

TEMP. LOW: Set up lower temperature limit (the lower limit setting is different for different types of sensor)

CONTROL: Select control modes ( 5 different modes: ON-OFF, PID, MANUAL, FUZZY and 2PID)

CONTROL SV provides 4 different options: CONS; PROG; SLOP; and REMO. REMO mode is available when REMOTE function is added. WAIT SV: Set up waiting temperature display when in programmable control WAIT TIME: Set up waiting timedisplay when in programmable control SLOP: Set up start slope display when in programmable control

PATTERN: Select pattern to be edited (display when in programmable control, there are 16 patterns and each pattern includes 16 steps. Setting parameters are OFF, SAVE, 0~F.)

TUNE: Select AT or ST (display when in PID/2PID control mode)

SELECT HEAT/COOL: Select heating, cooling or dual output heating and cooling

ALARM1 SET: Set up Alarm 1 mode (refer to “Alarm Output” for more setting on modes)

ALARM1 OPTION: Set up Alarm 1 options (refer to “Alarm Output” for more setting on modes)

ALARM1 DELAY: Set up Alarm 1 delay (refer to “Alarm Output” for more setting on modes)

ALARM2 SET: Set up Alarm 2 mode (refer to “Alarm Outputs”)

ALARM2 OPTION: Set up Alarm 2 options (refer to “Alarm Outputs” )

ALARM2 DELAY: Set up Alarm 2 delay (refer to “Alarm Outputs” )

Factory Setting PT
850.0
-200.0 PID
CONS
OFF AT H1H2 0 0 0 0 0 0

4

ALARM3 SET: Set up Alarm 3 mode (refer to “Alarm Output”)(display when OUT2 is set to ALARM mode) ALARM3 OPTION: Set up Alarm 3 options (refer to “Alarm Output”) (display when OUT2 is set to ALARM mode) ALARM3 DELAY: Set up Alarm 3 delay (refer to “Alarm Outputs” ) (display when OUT2 is set to ALARM mode) PV Color Change Function: Select the alarm to change PV display color. (refer to “Alarm Outputs”) 2PID change temperature (display on 2PID control mode)
2PID reset temperature (display on 2PID control mode)

REMOTE TYPE: Set up Remote type (display when

is set to REMO mode)

(V0:0~5V; V1:1~5V; V10:0~10V; MA0:0~20mA; MA4:4~20mA)

Select auxiliary function 1

Select auxiliary function 2

COMMUNICATION WRITE: Enable/disable communication write-in COMMUNICATION SELECT: Select ASCII or RTU format COMMUNICATION NO.: Set up communication address BPS: Set up baudrate LENGTH: Set up data length STOP: Set up stop bit PARITY: Set up parity bit
Press

to return to input type setting

0
0
0 OFF 1.0 0.5
MA4
0 0 OFF ASCII 1 9600 7 1
E

Regulation ModeParameter Settings:

Display

Description

AT: Auto-tuning Switchdisplay when setting Ctrl = PID/FUZZY/2PID, TUNE = AT, R-S=RUN

Press

ST: SELF-TUNING Switch (display when setting Ctrl = PID, TUNE = ST)

PID NO.: Select the nth (n=0~5) PID. When set in AUTO, PID is auto-selected. (display when

setting Ctrl=PID)

PID SV NO.: Accordinig to the selection of PID No. (n=0~5), set SV value accordingly. It will allow ~
the system perform auto selection when it’s set to AUTO mode. (Display when Ctrl =

PID/FUZZY/2PID).

P : Proportional Setting (display when setting Ctrl = PID/FUZZY/2PID and TUNE = AT) ~ Set P value according to the selection of PID No. (n=0~5). When P is set to AUTO, the system will

select P value accordingly.

I: Integral Time Setting (display when Crtl=PID/FUZZY/2PID; this parameter is set automatically

~ when TUNE=AT.) Set I value according to the selection of PID No. (n=0~5). When I is set to AUTO, the system will

select I value accordingly.

D: Deviation Time SEtting: (display when Crtl=PID/FUZZY/2PID; this parameter is set

~ automatically when TUNE=AT.) Set D value according to the selection of PID No. (n=0~5). When D is set to AUTO, the system will

select D value accordingly.

I OFFSET: Integral deviation setting, when Integral is not 0. (display when Crtl=PID/FUZZY/2PID;

~ this parameter is set automatically when TUNE=AT.) Set IOF value according to the selection of PID No. (n=0~5). When IOF is set to AUTO, the

system will select IOF value accordingly.

PD OFFSET: PD offset when Integral=0 to eliminate a consistent deviation.

Set up Fuzzy gain value (when Ctrl=FUZZY)

Set up Fuzzy Deadband (when Ctrl=FUZZY)

OUT1 HYSTERESIS: Adjust Output 1 hysteresis (when in ON/OFF control)

OUT2 HYSTERESIS: Adjust Output 2 hysteresis (when in ON/OFF control)

OUT1 HEAT: Heating control cycle for Output 1 ( when Ctrl= PID/FUZZY/MANUAL/2PID)

OUT1 COOL: Cooling control cycle for Output 1 (when Ctrl= PID/FUZZY/MANUAL/2PID)

OUT2 HEAT: Heating control cycle for Output 2 ( when Ctrl= PID/FUZZY/MANUAL/2PID)

OUT2 COOL: Cooling control cycle for Output 2 (when Ctrl= PID/FUZZY/MANUAL/2PID)

COEF: Ratio of Output 1 against Output 2 (when Ctrl= PID/FUZZY/2PID and when in dual output

Factory Setting OFF OFF 0
100
47.6
260
41
0
0 4 0 0 0 Output selection: C; V; S: 5sec. R: 20sec. 1.00

5

control) DEAD: Set up deadband (when Ctrl is not set to MANUAL and when in dual output) PV FILTER: Set up input filter factor of PV PV RANGE: Set up input filter range of PV PV OFFSET: Adjust input compensation of PV PV GAIN: Adjust input gain of PV SV SLOPE: Set up rising slope (when CRTS = SLOP) ANALOG OUT1 MAX.: Adjust upper limit compensation for analog Output 1 (1scale = 1A; 1scale = 1mV) ANALOG OUT1 MIN.: Adjust lower limit compensation for analog Output 1
(1 scale = 1A; 1scale = 1mV) ANALOG OUT2 MAX.: Adjust upper limit compensation for analog Output 2
(1scale = 1A; 1scale = 1mV) ANALOG OUT2 MIN.: Adjust lower limit compensation for analog Output 2
(1scale = 1A; 1scale = 1mV) RETRANSMISSION MAX.: Adjust upper limit compensation for Retransmission (1scale = 1A) (display when a Retransmission Card is connected to DT3) RETRANSMISSION MIN.: Adjust lower limit compensation for Retransmission (1scale = 1A) (display when a Retransmission Card is connected to DT3) REMOTE GAIN: Adjust Remote gain (When CRTS = REMO) REMOTE GAIN: Adjust Remote compensation (When CRTS = REMO)
REMOTE LOW: Remote lower limit (When CRTS=REMO) REMOTE HIGH: Remote higher limit (When CRTS=REMO) EVENT1: Set up EVENT1 function (display when a Event Card is connected to EVENT1) EVENT2: Set up EVENT2 function (display when a Event Card is connected to EVENT2)
EVENT3: Set up EVENT3 function (display when a Event Card is connected to EVENT3)

0 1 1.00 0.0 0.000
0
0
0
0
0
0 0 0 0 100 OFF OFF OFF

PID mode: Any of the 6 PID groups can be selected. When set to AUTO mode, the program will automatically select the PID group that

is the closest to the target temperature.

Select 0~5 group of PID and execute AT function, the system will automatically load P; I; D and IOF parameters into the selected PID

group.

Select the nth PID (n = 0 ~ 5)

press

to set 0 ~ 5th PID parameters

Set up the 0th PID temperature value

press

~

Set up the 5th PID temperature value

press

Set up the 0th proportional band value

~

Set up the 5th proportional band value

Set up the 0th Ti value

~

Set up the 5th Ti value

Set up the 0th Td value

~

Set up the 5th Td value

Set up the 0th PID integral deviation

~

Set up the 5th PID integral deviation

Press

to set the parameters in

Press

to set the parameters in

“Regulation Mode”

“Regulation Mode”

Programmable Editing: set

to

or

and set

to

.

Select desired editing pattern number 0~F

press

to set the desired editing pattern number 0~F

If the setting is OFF, leave the editing pattern page and go to

to continue with the setting.

Edit the temperature of step No.0 of pattern No. 0

~

press

Edit the temperature of step No.0 of pattern No. 15

Edit the time of step No.0 of pattern No. 0 (time unit: hh, mm)

~

Edit the time of step No.0 of pattern No.15 (time unit:

hh, mm)

~

Set up step 0~15 in order

~

Edit the temperature of step No.15 of pattern No.0

~

Edit the temperature of step No.15 of pattern No.15

Edit the time of step No.15 of pattern No.0

~

Edit the time of step No.15 of pattern No.15

Seelect the actual required steps for executing pattern No.0

~

Seelect the actual required steps for executing

pattern No.15

Set up the additional cycle (0~199) for pattern No. 0 execution

~

Set up the additional cycle (0~199) for pattern No.

15 execution

6

Set up the link pattern of pattern No.0 (0~F;

END; STOP)

Press

to return to the

selection of desire editing pattern and number.

~

Set up the link pattern of pattern No.15 (0~F;

END; STOP)

Press

to return to the

selection of desire editing pattern and number

Initial Start-up Setting

1. When setting up DT3 for the first time, press

key for more than 3 seconds till the screen display

and select according

to your temperature sensor type. Please be aware that a selection of wrong model would cause PV temperature display error. (Refer

to the chart below)

2. When setting up the temperature sensor type by using RS-485, write your value (range 0~19) into register 1004H.

3. When setting up the current input method, remove the temperature controller cover and set JP8 to short. (Refer to the chart below)

Temperature Sensor Type & Temperature Range Chart

Input Temperature Sensor Type
Thermocouple K type

Register Value Temperature Range 0 -200 ~ 1300°C

Input Temperature Sensor Type Register Value Temperature Range

Thermocouple TXK type

10 -200 ~ 800°C

Thermocouple J type

1 -100 ~ 1200°C

Platinum Resistance (JPt100)

11 -20 ~ 400°C

Thermocouple T type

2

-200 ~ 400°C

Platinum Resistance (Pt100)

12 -200 ~ 850°C

Thermocouple E type

3

0 ~ 600°C

Resistance (Ni120)

13 -80 ~ 300°C

Thermocouple N type

4 -200 ~ 1300°C

Resistance (Cu50)

14 -50 ~ 150°C

Thermocouple R type

5

0 ~ 1700°C

Analog Voltage Input (0~5V)

15

-999~9999

Thermocouple S type

6

0 ~ 1700°C

Analog Voltage Input (0~10V)

16

-999~9999

Thermocouple B type

7

100 ~ 1800°C

Analog Voltage Input (0~20m A)

17

-999~9999

Thermocouple L type

8

-200 ~ 850°C

Analog Voltage Input (4~20m A)

18

-999~9999

Thermocouple U type

9

-200 ~ 500°C

Analog Voltage Input (0~50m V)

19

-999~9999

How to Set Up Current Input

Remove the temperature controller cover and set JP8 to short. JP8 jumper locates near the sensor input area on PCB board.

Normal Input (Factory Setting)

Current Input (4 ~ 20mA, 0 ~ 20mA)

Display Unit Setting

Use following parameter to change the PV and SV display unit, select decimal point and switch between /F.

In Operation Mode In Initial Setting Mode

: SP=1 displays decimal place (ex: 25.5 degree); SP=0 displays integral number (ex: 25 degree). : Select temperature display unit /. (=* 9 / 5 + 32)

Set Value and the Upper/Lower Limit of Input Value Setting

Set the Upper Limit of Input Value: This parameter can be set in the Initial Setting Mode

, the upper limit input value must

be set within the range shown in the chart “Temperature Sensor Type & Temperature Range”.

Set the Lower Limit of Input Value: This parameter can be set in Initial Setting Mode

, the lower limit input value must be

set within the range shown in the chart “Temperature Sensor Type & Temperature Range”.

Set the SV: This parameter can be set in Operation Mode, SV value must be set within the range of upper/lower limit input value.

SV can not be set in In “Program Mode” or in “Remote Mode”.

7

Digital Filter and Linear Compensation Setting

In “Regulation Mode”,

and

parameters can be used to ajust the filter status and to avoid interferences on input signal.

: Filter Factors (setting range=0~50; factory setting=8). Digital Filter Calculation equation: PV=(Last displayed PV * n +

Measure Value)/ (n+1). When the parameter value is small, the PV display is close to the Measured Value. When the parameter

value is large, the PV response is slow.

: Filter Range (setting range=0.10~10.00/). If factory setting = 1, it means the controller will begin Digital Filter

Calcaulation when the Measure Value lies within the range of “Last displayed PV + / – 1.00/”. Therefore, it is recommended to

set a larger value when noise interferences is serious.

When PV display value is different than user’s expectation, Linear Compensation function can be set by

and

parameters in”Regulation Mode”.

: Linear Compensation Value (setting range= -99.9 ~ +99.9). Linear Compensation Calculation equation: PV = Measure

Value + Compensation Value.

For example: Measure Value=25.0; Compensation = 1.2. After applying to the Compensation equation PV=26.2.

Linear Compensation Gain (setting range = -0.999~0.999). Linear Compensation Gain Calculation equation: PV =

Measure Value* (1 + Gain/1.000) + Compensation.

For example: Measure Value=25.0; Gain= 0.100. After applying to the Gain calculation equation PV= 25.0 * (1 + 0.100 / 1.000) = 27.5

If temperature deviation is the same in every temperature, settting linear compensation value can solve deviation problem. If temperature

deviation varies upon different temperatures, calculate the linear deviation error and adjusts the temperature by setting Gain and

Compensation value.

Applications of Analog Voltage & Current Input
The input range of analog voltage and current are used as the uppler/lower limit of the controller’s voltage and current setting. When setting up the desire voltage or current, it must lies within the range of upper/lower limit. For example: If the range of analog input voltage is 0~5V, the upper limit setting will be 5000 and lower limit setting will be 0. If the decimal setting is set to 3 decimal place, a input voltage of 2.5V will displays as 2.500. The equation of Display Value = (Upper limit setting of controller­ Lower limit setting of controller)*(Input voltage- Analog lower limit)/(Analog upper limit­ analog lower limit) + Lower limit setting of controller.

Disable the Cold Junction Function

The cold conjunction function of a thermocouple is set to ENABLE, but in some cases, we can set it to DISABLE.

In Initial Setting Mode,

is used to set the first digit (Y) of Yxxx, (when Y=0, Enable; when Y=1, Disable).

Analog Output Compensation

When the output mode is set to analog current output (4~20mA) or linear voltage output (0~10V), user’s desire output value can be

attained by using compensation function. For example, the analog output 1 can be adjusted in

and

parameters in

“Regulation Mode”. The output value can be positive or negative (+/-) and it can be changed by pressing the Up/Down key on the

temperature controller. The scale of each pressing is an increase or decrease of 1uA and 1mV.

For example: To change the current output range from 4~20mA to 3.9~20.5mA, set

to 500 (20.5-20=0.5mA; 0.5mA/1uA= 500).

and set

to -100 (3.9-4=-0.1mA; -0.1mA/1uA=-100).

To control the output manually: Set parameter

to

inInitial Setting Mode.

To set output to 0%: Set parameter

to

or

to

inOperation Mode.

To adjust the lower limit of analog output: Input a desire value and check the meter to adjust the analog input value to desire value

(For example: 4~20 m A, adjusting analog value will be 20 m A). Set parameter desire value in Regulation Mode.

(Output 1) or

(Output 2) to your

To set output to 100%: Set parameter

(Output 1) =

or

(Output 2) =

in Operation Mode.

To adjust the lower limit of analog output: Input a desire value and adjust the analog input value to your desire value (For example:

4~20 m A, adjusting analog value will be 20 m A). Set Regulation Mode.

(Output 1) or

(Output 2) to your desire value in

8

Retransmission and Compensation Adjusting
When the input value changes, the retransmission output will also be changed correspondingly. For example: If retransmission = 4~20mA ; uppler/lower limit = 100.0 ~ 0. Wen the controller reads 0, it outputs 4mA; when the controller reads 100, it outputs 20mA. The value can also be a negative number to generate a negative slope. For negative slope, sets upper/lower limit = 0~100.0. In this case, when the controller reads 0, it outputs 20mA; when the controller reads 100, it outputs 4mA. Refer to the slope diagram below.

Output = Negative Slope

Output = Positive Slope

(Figure 1: Propotional Output Diagram)

To set Retransmission to positive/negative slopes (a Retransmission board must be installed first): In Initial Setting Mode set

the

parameter, the last digit (Y) of xxxY indicates when Y=0 positive slope; when Y=1 negative slope.

To adjust the lower limit of Retransmission:

a Make sure the slope of Retransmission is positive.

b Set lower limit value larger than the display value: InInitial Setting Modeset the value in

larger than the display value

(PV). c Input the analog value to meter, check the meter and adjust the analog input value: In Regulation Mode, enter the new value

into

. For example, if the range is 4~20mA, the new value will be 4mA.

To adjust the upper limit Retransmission:

a Make sure the slope of Retransmission is positive.

b Set upper limit value smaller than the display value: InInitial Setting Modeset the value in

smaller than the display

value (PV). d Input the analog value to meter,check the meter and adjust the analog input value: In Regulation Mode, enter the new value

into

. For example, if the range is 4~20mA, the new value will be 4mA.

Check the Firmware Version and Output Type
When the temperature controller is ON, the PV and SV display will shows firmware version, output type and accessory functions in first 3 seconds. PV (first 3 digits) indicates the firmware version. Ex: 110 indicates firmware version V1.10. PV (4th digit) indicates the function of accessory 1.
C: RS485 Communication E: EVENT3 Input SV (frist 2 digits) indicates the output type of OUT1 and OUT2.
N: No function V: Voltage pulse output R: Relay output C: Current output L: Linear voltage output S: SSR output SV (3rd digit) indicates the function of accessory 2. N: No function C: CT measure E: EVENT1 input R: REMOTE input SV (4th digit) indicates the function of accessory 3. N: No function C: CT measure E: EVENT2 input R: RETRANSMISSION output

Selection for Heating/Cooling/Alarm/Dual Loop Output Control

DT3 series offers 1 set of Output Control (OUT1) that is built-in internally and 2 sets of Alarm Output(ALARM1 ALARM2). User can also

purchase a 2nd set of Output Control (OUT2) or a 3rd set of Alarm Output (ALARM3). Using 1 set of Output Control :

InInitial Setting Mode, sets

to Heating (H1) or Cooling(C1) mode.

Using 2nd set of Output Control:

When the 2nd set of output control (OUT2) is used as a 3rd set of arlarm (ALARM3), set Cooling + Alarm 3(C1A2) in Initial Setting Mode.

to Heating + Alarm 3(H1A2) or

OUT2 output types in relay, voltage pulse, analog current, linear voltage and SSR output can all be used for ALARM ON-OFF. For

9

example, OUT2 is set to analog current output. It outputs 4mA when alarm is OFF and outputs 20mA when alarm is ON.

When the 2nd set of output control (OUT2) is used as dual output control, set

to heating (H1H2); cooling (C1C2);

Heating/Cooling(H1C2) or Cooling/Heating (C1H2) control mode inInitial Setting Mode.

The Dead Band parameter

is automatically enabled when the temperature controller is in dual output control. As shown

in the diagram follow. The purpose of Dead Band function is to reduce the energy wastage of frequent heating/cooling actions. For

example, if SV = 100 degree and

= 2.0, there will be no output when the temperature is between 99~101°C..

Output of

when in ON-OFF control mode (Ctrl=ON-OFF control):

Adjust heating hysteresis

Adjust cooling hysteresis

Heating

Cooling Set Point

Output of

when in PID control mode (Ctrl=PID):

Heating
Set Point

Cooling

Heating
Set Point

Cooling

When the controller is in PID control and dual loop output mode,

sets the P value of the 2nd set of PID. The 1st set of PID

is generated when TUNE= AT, but user can also manually sets the PID value. The P value of th 2nd set of PID = the P value of 1st

set of PID x

. The I and D value of the 2nd set of PID remains the same as the 1st set of PID.

SV Control Mode Setting

There are 4 methods for setting SV of the temperature setting; they are Fixed, Slope, Program and Remote.

Fixed SV Mode: controls the temperature to directly rise to a fixed setting value

Set parameter

to

in Initial Setting Mode

Set the target temperature: set SV value by a parameter in Operation Mode

Slope SV Mode: Control temperature rises at a slope (unit: /min.) to a fixed value.

E.G., if parameter

set to 1, set a slope of 0.5 and set SV to 200.0; this means the temperature rises 0.5 every minute

from room temperature up to 200.0.

If parameter

set to 0, set a slope of 5 and set SV to 200; this means the temperature rises 5 every minute from room

temperature up to 200.

Set parameter

to

in Initial Setting Mode

Set rising slope (unit: /min. or /s): set rising slope by parameter

in Regulation Mode

Set target temperature: set SV value by a parameter in Operation Mode

Set unit for rising slope (unit: /min. or /s): for parameter

in Initial Setting Mode, set the corresponding Y

position value to xxYx (Y can be 0 or 1; Y= 0: /min.; Y=1: /s).

Program SV mode: This means the temperature setting value is not a fixed value but a setting curve defined by the user according to his-her requirements. By way of PID control, the temperature input rises along with the defined temperature curve. As to how to input the temperature setting curve, the machine provides 16 patterns with 16 steps each, together with a linking parameter, a loop parameter, and a number of executions. Each step has 2 parameters (temperature setting value and time). If the initial step has a time parameter set to 0, temperature will rise from room temperature at the initial slope up to the target temperature. After setting these parameters, each temperature controller will have its own set of initial pattern and initial step for

10

creating its own temperature setting curve. Some of the terms are explained as follows: a Initial pattern: set the program to start running at a sequential number of patterns b Initial Step: set the program to start running at a sequential number of steps c Initial Slope: If the time setting of the initial step of the initial pattern is set to 0, an initial slope shall be set to allow the temperature to rise from room temperature to the setting value. d Step: includes 2 parameter settings: a setting point X and an executing time T, representing the setting value (SV) to rise to X after time T. If the setting point X is identical to the previous setting, this process is called a Soak, otherwise a Ramp, therefore this control procedure is also called a Ramp Soak control. The first running procedure is preset as a Soak control, to set the temperature control to setting point X in advance and maintain the temperature at X, at a duration of T. e Link Parameter: the number of the subsequent pattern to be linked after executing this pattern. If set to END, the program mode will end but maintain the last setting value; if set to STOP, all the program controls will end with the output switched off. f Number of loops: Number of extra loops to be carried out for the pattern. If set to 1, the pattern will be carried out 2 times. g Executing step: Number of steps executed for each pattern. h Wait time, wait temperature: After reaching the program temperature value, a wait time and wait temperature can be set; if the current temperature is not within the range of (temperature setting value ± wait temperature), the set wait time will start to count down until the currently measured temperature reaches the range of (temperature setting value ± wait temperature) of each step before proceeding to the subsequent step. An alarm will be issued if the range of (temperature setting value ± wait temperature) is not reached when the count down reaches 0. i Execution: If the setting control is in running mode, the program will start running from the initial pattern and initial step, and carry out commands one by one. When the setting control is in end mode, the program will stop running and give out an output disable. When setting control is in stop control and temperature is controlled at the setting value before the stop, by re-selecting the start status, the program will start running from the initial pattern and initial step. When setting control is in pause control and temperature is controlled at the setting value before the stop, by re-selecting the start status, the program will start running from the step where the program was paused and carry out the remaining part.

Set parameter

to

In Initial Setting Mode

Set initial pattern: Set parameter

to initial pattern in Operation Mode.

Set initial step: Set parameter

to initial step inOperation Mode

Select edit pattern: Set parameter

in Initial Setting Mode to set the pre-edit pattern, assume selection is `x’.

Press

key to select the patterns including “SPx’0”, “tMx’0”, “SPx’1”, “tMx’1″…

“SPx’F”, “tMx’F”, “PSYx’ “, “CYCx’ “, “LiNx’ “, wherex’ is the selected pattern, which can be 0, 1, …, E, F. “SPx’0” “SPx’1″…”SPx’F” are temperature settings of this step; ” tMx’0″ ” tMx’1″ … ” tMx’F” are time

settings of this step; “PSYx’ ” is the maximum effective procedure; “CYCx’ ” is the number of loops for executing

the loop, “LiN`x'” is the number of the subsequent patterns to be linked after executing this pattern.

Set initial slope: Set initial slope by parameter

in Initial Setting Mode(unit: 0.1/min. or 0.1/s)

Set wait temperature: Set wait temperature by parameter

in Initial Setting Mode.

Set wait time: Unit min., set wait time by parameter

in Initial Setting Mode.

Set unit of program edit time: Set value corresponding to Y position of parameter

in Initial Setting Mode, e.g.,

xxYx (Y is 0 or 1; 0/min., 1/s)

Set SV display method on program mode: Set value corresponding to Y position of parameter Mode, e.g., Yxxx (Y is 0 or 1; 0normal, 1dynamic)

in Initial Setting

11

Set power off saving on program mode: Set value corresponding to Y position of parameter Mode, e.g., xxxY (Y is 0 or 1; 0normal., 1power off saving)

in Initial Setting

Note: When any settings or changes of the program parameters are made, please save the settings/changes to the controller by opting for parameter SAVE. Otherwise, the settings/changes will be reset upon power-off.
How to SAVE:

Select

in the menu, then press the

keys and select

to complete saving. The

key is displayed only when any settings/changes are made.

Using RS485 communicatiion writing value 1 to address 1129H, the parameters will be saved.

Remote Mode: Input of setting value can be dynamic, an analog value (voltage or current) can be converted into a dynamic input

value. Two methods can be used for the conversion: positive slope or negative slope, they are depicted as follows: a Positive slope Remote setting: Display of Remote analog input is in positive proportion with setting input, e.g.: Remote input

type is selected as 1~5 V analog voltage, Remote higher limit of input is set as 5000, Remote lower limit of input is 1000,

decimal display is set as 0; when Remote input is 5V, the screen shows 5000; when Remote input is 2V, the screen show

2000; this is the dynamic setting of the screen display. (Dynamic setting value =(Remote higher limit of input ­ Remote lower

limit of input)*(Remote input value – lower limit of Remote input)/( higher limit of Remote input – lower limit of Remote input)+

Remote lower limit of input) b Negative Slope Remote setting: Display of Remote analog input is in negative proportion with setting input, e.g.: Remote

input type is selected as 1~5 V analog voltage, Remote higher limit of input is set as 5000, Remote lower limit of input is 1000, decimal display is set as 0; when Remote input is 5V, the screen shows 1000; when Remote input is 2V, the screen show 4000; this is the dynamic setting of the screen display. (Dynamic setting value =(Remote higher limit of input ­ Remote lower

limit of input)*(Remote input value – lower limit of Remote input)/( higher limit of Remote input – lower limit of Remote input) ­

Remote lower limit of input)

Set parameter

to

in Initial Setting Mode

Note: This option is only available when a Remote board is inserted. If the Remote type is of analog current, the JP in the

Remote board must be shorted (using a short cap). If the Remote type is of analog voltage, ensure the JP is open. Remote type setting: Set type of the Remote input (including analog current 0~20 m A,4~20m A; analog voltage 0~5V, 1~5V,

Control Mode Setting
There are 4 control modes; ON-OFF, PID, FUZZY and MANUAL. ON-OFF Mode: For heating output, the output is off when input is greater than the setting value; output is on when input is smaller
than (setting value ­ adjustment sensitivity setting value). For cooling output, the output is on when the input is greater than (setting value + adjustment sensitivity setting value); output is off when input is smaller than the setting value. If one of 2 outputs is set for heating and the other for cooling, a non-action zone can be set as follows.

PID Mode: When set for heating or cooling, the program performs PID operation via input temperature and setting temperature, with the operation result output for the temperature control. A PID parameter and control period must be set for this function; these parameters can also be generated automatically via auto-tuning (AT). a A total of six sets of PID parameters are available, one of which can be selected for carrying out PID, and the program may automatically select a set of PID that is most close to the input value. In order to achieve this, each set of PID parameters has a reference input setting value which allows the user to set for manual setting or for auto- tuning (AT). E.G., for the six sets of PID parameters as shown below, SV is reference input setting. Let us select the 4th set as the PID running parameter: i.e., P=40, I=220, D=55, IOF=30%. If we select AT to find the set closest to the setting value with a setting input of 230, the program will automatically find the second set as the running parameter for PID operation.

Set PID parameters and the control period: in which PID parameters can be adjusted manually according to system characteristics or created automatically by AT, the pre-set integral value is set as I parameter 0, allowing for promptly

achieving the setting value; unit is % output; proportional error compensation is: when I parameter is set to =0, for the

adjustment of reduced time to reach the temperature. The Control Period is the period of PID operation, if the control period is

10s, it means a PID operation is carried out every 10s. The result is then output to control the temperature. If the system

heats up quickly, the control period shall not be set too long. For relay output, the lifespan of the relay shall be considered; a

short period will shorten the lifespan of relay. c Coef and DeadBand are added in the PID parameter for double output (one for heating and one for cooling). Coef refers to

the ratio between the first and second portions of output (P parameter of second group =Coef*P, Coef= 0.01~99.99);

DeadBand is the overlapping temperature of the P output of the first group and the second group.

Set parameter

t in Initial Setting Mode

To set for heating or cooling control: Select desired output control by parameter

in Initial Setting Mode. If no

board is inserted in Output2, selection items are: H1, C1 (H for heating, C for cooling, 1 for output 1). If a board is inserted in

Output 2, selection items are: H1H2, C1H2… H1A2(H for heating, C for cooling, 1 for output 1, 2 for output 2, A for Alarm 3 )

Select number of PID sets as running parameter and set PID parameter: Select 0~5,

, by parameter

in

Regulation Mode, then press

key to set the selected PID parameter including “SVx'”, “Px'”, “Ix'”, “dx'”, and “ioF`x'”,

13

where x’ is the pre-selected set as the PID running parameter, which can be 0~5. “SVx'” is the reference temperature

setting value; “Px'”, “Ix'”, “dx'”, “ioFx'” correspond to P, I, D, and IOF. Set the control period: in parameter Regulation Mode, PV displays “ox’-y'”, x’ is 1(output 1) or 2 (output 2),y’ is H(Heating)

or C (Cooling) Set double output Coef: Set Coef value by parameter

in Regulation Mode

Set DeadBand of double output: Set DeadBand zone by parameter

in Regulation Mode

Set control to running mode: Set parameter

in Operation Mode to

.

Set AT: Set parameter

to

in Regulation Mode. The selected number of PID will be adjusted

automatically. After that, a pre-set parameter of integrated PID value will be created automatically and the display will

automatically alter into

.

Note: When performing AT, the entire system must complete setting; i.e. the input Sensor must be wired and correctly set, and the

output must be connected to a heater or cooler pipe.

MANUAL Mode: Manual control function, may force output of a fixed value; normally operated by combining switchover of PID

control. a Switch from PID control to manual control: Control output will maintain the original control output before switching over to

manual control. E.g., if the control output before the PID calculation is 20%, then the control output after switching to manual

control is 20%. You may force a fixed output value after a switchover, for example: controlling the output to be 40%. b Switch from manual control to PID control: if manual control before switching-over to PID control is 40%, the program will

take 40% as the initial value for calculating the PID value and output the new control.

Note: If power of machine is switched off in manual control mood, the output % will be maintained when the power is switched on again.

Set parameter

to

in Initial Setting Mode

Set control period: in parameter Regulation Mode, PV displays “ox’-y'”, x’ is 1 (output 1) or 2 (output 2),y’ is H (Heating)

or C (Cooling) Set output %: in parameter Operation Mode, PV screen displays “oUtx'”,x’ is 1 (output 1) or 2 (output 2)

FUZZY Mode: This comprises 2 parts: PID parameters and Fuzzy exclusive parameters. Since Fuzzy control is calculated based

on P.I.D values of PID control, the user must first set P.I.D parameters or perform auto tuning (AT) to produce these parameters. In

addition, Fuzzy control includes the following 2 exclusive parameters. a Fuzzy Gain Setting: altering this value will directly affect the calculation of Fuzzy gain. Increasing this value will directly

enhance the Fuzzy control; decreasing this value will weaken the Fuzzy control. It is recommended that this value shall be

decreased for systems with slow reaction to heating/cooling. This value may be increased for systems with quick reaction to

heating/ cooling. b Set Fuzzy DeadBand: The effective bandwidth of Fuzzy control, when PV value enters into the range of SV-FZDB

<PV<SV+FZDB, Fuzzy control will stop calculation. I.e., when the PV is within this temperature range, its Fuzzy control is fixed.

Set parameter

to

in Initial Setting Mode

Set Fuzzy Gain: Set value of Fuzzy Gain by parameter

in Regulation Mode.

Set Fuzzy DeadBand: Set value of Fuzzy DeadBand by

parameter in Regulation Mode.

Setting of multiple PID sets

When PID control is selected, the system provides 6 sets (PID 0~5) PID parameter sets (P, I, D and IOF parameter) to be selected by the user. In general conditions, one set of PID (P0) is adequate. For different setting values (SV), when the same PID value is not adequate to control the precision, the user may set up multiple sets of PID parameters for the system to automatically switch-over to an applicable PID set. Set only one PID set:

Set parameter

to 0 (PID 0, the first set) inRegulation Mode, set parameter

to ON; at this time, the System starts to

Auto Fine-tune the PID value. During the calculation, AT LED lights up in the display panel. When the PV value generates 2 curves of temperature oscillation based on the SV value, the AT process is completed and the AT LED in the panel goes out. The calculated PID

parameters are displayed in

,

,

,

Automatic switching-over Multiple PID sets:

and

, of which their content can be revised by the user.

Set parameter

to 0 (PID 0, the first set) inRegulation Mode, set the required SV value (e.g. 100 degree), set parameter

as ON; on completion of auto fine-tuning, the system fills in parameters

=100,

,

,

and

automatically, their content can be revised by the user.

Set parameter

to 1 (PID 1, the second set), set the required SV value (e.g. 150 degree), set parameter

as ON; on

completion of auto fine-tuning, the system fills in parameters

=150,

,

,

and

automatically.

14

Set parameter

to AUTO, System will verify on its own whether the current SV value is closer to parameter

or

,

and load the corresponding PID set automatically. E.g., if SV=110, system will load

parameters. If SV=140, system will load

parameters.

If more SV groups are required, PID2~PID5 can be set up with the same sequence as described above.

Tune Function

This machine provides 2 tuning methods (Auto_Tuning and Self_Tuning) for automatic generation of PID parameters (only applicable

when control mode is set to PID control).

Auto_Tuning: by full output of heating or cooling, temperature is allowed to oscillate up and down. Attain parameters of the

magnitude and period, calculate P, I, D, IOF parameters; in addition, save the temperature setting value for performing AT, for the

use of PID control. After Auto_Tuning, PID control will be carried out automatically.

Set parameter

to

in Initial Setting Mode

AT setting: Set parameter

to

in Regulation Mode

Self_Tuning: By full output of heating or cooling, max. slope of temperature alteration and system delay can be attained from the

Temperature-Time Curve, and P, I, D, IOF parameters can be calculated. Self tuning can be carried out in RUN mode and in STOP

mode. In the RUN mode, PID parameters are allowed to be updated when the machine is running; in the STOP mode, PID

parameters for the SV value can be attained.

Set parameter

to

inInitial Setting Mode

ST Setting: set parameter

to

in Regulation Mode

Limits controlling the output range

Maximum and minimum output can be limited; if the original maximum control output is 100% and the minimum control output is 0%, you

may set the maximum control output to 80% and the minimum control output to 20%.

Setting the upper limit of control output: Set values for parameters

(output 1),

(output 2) inOperation Mode.

Setting the lower limit of control output: Set values for parameters

(output 1),

(output 2) inOperation Mode.

CT Function

This controller provides maximum 2 CTs (CT1 and CT2) for measuring current values of output 1 and output 2; when the corresponding

output is ON, use CT to measure the corresponding current. An alarm will be activated (ON) when the current exceeds the setting range

of alarm. (A hardware PCB is required.) Insert CT1, CT2 PCBs to Option1, Option2 Set the corresponding alarm to CT Alarm: Please refer to “Alarm Output Setting”. Set the upper limit of CT alarm output (unit: 0.1A): Please refer to “Alarm Output Setting”. Set the lower limit of CT alarm output (unit: 0.1A): Please refer to “Alarm Output Setting”.

Read current values of CT1, CT2: Read current values by parameters

,

in Operation Mode.

Select CT measurment range

CT1 100A settingSet a value corresponding to Y position by parameter 0 or 1; 0: 30A; 1: 100A)
CT2 100A settingSet a value corresponding to Y position by parameter 0 or 1; 0: 30A; 1: 100A)

in Initial Setting Mode, such as xxYx (Y can be in Initial Setting Mode, such as xYxx (Y can be

Short the jumper on CT board. The CT board input voltage maximun 200mV, current maximum 50mA.

Jumper

CT board

15

Normal inputdefault setting 30A

Short (100A)

EVENT Function
This controller provides a maximum of 3 EVENTs (EV1~EV3) for respectively setting EV functions as shown in the following Table <1>. For example, if EV1 is used for Run/Stop selection, when the controller is set to RUN status, if terminals in the Option1 slot are open, the controller is in RUN status; if terminals in the Option1 slot are shorted, the controller switches to STOP status.

Function setting Function

OFF

R-S

SV2

MANU

Disable

Run/Stop SV 1/ SV 2

Auto/ Manual

Table <1> EVT function setting

P-Hd Run/ Hold

Run/Stop: This function switches the controller between RUN and STOP status. SV 1/SV 2: This function selects SV 1 or SV 2 as the active setpoint. Auto/Manual: This function selects PID and Manual control. Run/Hold: This function switches controller between run and hold status when in program control.

Insert EV1, EV2 PCB to Option1 or Option2, or insert hardware with a built-in EV3 function

Set EV functions as listed in Table <1> EVT Function Setting by parameters

,

,

inRegulation Mode.

Note: Selection of “Evt`x'” items must match with the inserted PCB; if only Option1 is inserted, then only “Evt1” will be displayed.

Limits of temperature ranges

Different input sensors have different application ranges (e.g.: J type factory setting is -100 ~ 1200), adjust parameters

(upper

limit) /

(lower limit) in Initial Setting Mode.

If lower limit is altered to 0 and upper limit is altered to 200, the limit function will be enabled in the following conditions: When setting the SV value, the limits may set for 0~200

In ON-OFF, PID, FUZZY and Self-Tuning control conditions, the control output will be forced to shut off if the PV value exceeds the

upper/lower limit. (Alarm output is still normal)

User Setting of F1, F2 function keys

In the Operation Mode, (PV/SV display mode), pressing a function key more than 3 seconds will prompt you to the setting of the following

functions; press

keys to make a selection.

Function

Description

MENU

When in a screen other than the PV/SV display mode, pressing F1/F2 key continuously may save the setting, to quickly switch the menu screen
(When the screen shows KEY SAVE, the menu screen is saved)

AT

Selecting this function, F1 / F2 button can be used for quick ON / OFF operation of AT function

R-S

Selecting this function, F1 / F2 button can be used to switch between RUN/STOP status.

PROG Selecting this function, F1 / F2 button can be used to switch between RUN/HOLD status.

ATMT

Selecting this function, F1 / F2 button can be used to switch between PID and MANUAL control mode

ALRS

Selecting this function, F1 / F2 button can be used to reset Alarm Hold status.

SV2

Selecting this function, F1 / F2 button can be used to switch between SV1/SV2.

For disabling F1/F2 function, please select MENU without saving any menu screen.

16

Edit a self-defined Menu Screen

Hidden MENU setting: Lock all buttons by adjusting parameter

to

in Operation Mode. At the same time press

and

keys for 3 seconds to display

, and enter Password-1. The screen will show menu number

table for details. Select “Hide” to hide the Menu.

, see the following

Menu Layer setting: Lock all buttons by adjusting parameter

to

in Operation Mode. At the same time press

and

keys for 3 seconds to display

, and enter Password-2. The screen will show menu number

table for details. Selectable items are NOR= display layers; ADJ= adjust layers; SET= set layers.

, see the following

Menu layer reset: Lock all buttons by adjusting parameter

to

in Operation Mode. At the same time press

and

keys for 3 seconds to display

, and enter Password-3. The screen displays

(Level reset) parameters, select

to reset all menu layers to default setting.

RUN layer

Menu No.

Corresponding menu

M101

M102

M103

M104

.

2. Enter the current password in

screen. If the password is correct, you will be prompted to Set-New-Password

screen

. If the password is incorrect, the screen will return to PV/SV display mode.

3. Enter the new password two times in the

screen. The screen will return to PV/SV display mode with the keys

unlocked. If the two entries of password are not the same, the screen will go back to the state of step 2. Cannot remember the password:

Restore factory settings to release the locking.

Alarm Outputs

Two alarm outputs are provided in the machine, a maximum of 3 alarm outputs can be expanded. A total of 19 Independent alarm settings

can be made as listed in the table. Additional settings are provided, such as alarm delay, alarm standby, alarm output hold, alarm reverse

output, and alarm peak record, as described as follows:

a Alarm Delay Setting: Sets alarm delay time. When the movement conforms to the alarm setting mode, controller will delay the

generation of an alarm signal; an alarm will only be activated when the alarm conditions remains confirmed within the delayed period

of time.

b Alarm Standby Setting: An alarm detection will only be activated when the measured value falls within the ±5 range of the specified

input value, so as to prevent an alarm activation on the start-up if the condition conforms to the alarm setting.

c Alarm Output Hold Setting: The alarm message will be held when the alarm activates, unless the control switches off the alarm.

d Alarm Reverse Output Setting: An alarm output can be set for NC( Normal close) or NO(Normal Open).

e Alarm Peak Record Setting: For recording the peak value of the alarm signal.

Set Value

Alarm Type

Alarm Output Operation

0

Alarm function disabled

Deviation upper- and lower-limit:

ON

1 This alarm output operates when PV value is higher than the setting value SV+(AL-H) OFF

or lower than the setting value SV-(AL-L).

SV-(AL-L) SV

SV+(AL-H)

ON

Deviation upper-limit:

2

This alarm output operates when PV value is higher than the setting value SV+(AL-H). OFF

SV

SV+(AL-H)

ON

Deviation lower-limit:

3

This alarm output operates when PV value is lower than the setting value SV-(AL-L).

OFF

SV-(AL-L) SV

Absolute value upper- and lower-limit: 4 This alarm output operates when PV value is higher than the setting value AL-H or
lower than the setting value AL-L.
5 Absolute value upper-limit: This alarm output operates when PV value is higher than the setting value AL-H.
Absolute value lower-limit: 6
This alarm output operates when PV value is lower than the setting value AL-L.

ON OFF
ON OFF

AL-L

ON OFF

AL-L

AL-H AL-H

18

Hysteresis upper-limit alarm output:

ON

7

This alarm output operates if PV value is higher than the setting value SV+(AL-H). This alarm output is OFF when PV value is lower than the setting value SV+(AL-L).

OFF

SV SV+(AL-L) SV+(AL-H)

Hysteresis lower-limit alarm output:

ON

8

This alarm output operates if PV value is lower than the setting value SV-(AL-H). This alarm output is OFF when PV value is higher than the setting value SV-(AL-L).

OFF

SV-(AL-H) SV-(AL-L) SV

9

Disconnection Alarm: This alarm output operates if the sensor connection is incorrect or has been disconnected.

10 None

11

CT1 Alarm: CT1 is ON if the value of CT1 is lower than the value of AL-L or higher than AL-H.

12

CT2 Alarm: CT2 is ON if the value of CT2 is lower than the value of AL-L or higher than AL-H.

13

When SOAK status (temperature hold) happens to PID program control, alarm output is ON.

14 When RAMP UP status happens to PID program control, alarm output is ON.

15 When RAMP DOWN status happens to PID program control, alarm output is ON.

16 When RUN status happens to PID program control, alarm output is ON.

17 When HOLD status happens to PID program control, alarm output is ON.

18 When STOP status happens to PID program control, alarm output is ON.

19 When END status happens to PID program control, alarm output is ON.

ON
OFF AL-L

AL-H

To set Alarm Mode: Use the parameters

,

,

in Initial Setting Mode to select the alarm mode. There are

in total of 19 different modes (as listed in the table above).

To set Deviation Upper Limit of Alarm: Use the parameters

,

,

in Operation Modeto set the deviation

upper limit.

To set Deviation Lower Limit of Alarm: Use the parameters

,

,

in Operation Mode to set the deviation

lower limit.

To set Alarm Delay Time(Unit: seconds): Use the parameters

,

,

in Initial Setting Mode to set the alarm

delay time.

To set Reverse Alarm: Use the parameters

,

,

inInitial Setting Mode to set the digit Y of value xxYx

(When Y=0: reverse, Y=1: forward)

To set Alarm 3: Alarm 3 function is available when an output board is connected to Output 2. Use the parameter

inInitial

Setting Mode, press the key or to select for the following control output items: H1H2, C1H2… H1A2(H defines heating, C

defines cooling, 1 indicates Output1, 2 indicates Output2 , A indicates Alarm3).

Select x1A2( set x to H or C) to operates Alarm3. To set Standby Alarm: Use the parameters

,

,

Setting Mode to set the digit Y of value xxxY (When Y=0: normal opeartion, Y=1: standby).

in Initial

To set Hold Alarm: Use the parameters

,

,

inInitial Setting Mode to set the digit Y of value xYxx ( When

Y=0: normal operation, Y=1: Hold). To set Peak Alarm Signal: Use the parameters

,

,

inInitial Setting Mode to set the digit Y of value Yxxx

(when Y=0: normal operation, Y=1: peak signal). Note: Refer to the table

Bit3

Bit2

Bit1

Bit0

Peak Alarm Hold Alarm Reverse Alarm Standby Alarm

PV Color Change Function: This controller provides PV color change function. The PV display color will be changed if the selected

alarm energized. Use the parameter

(PV color) in Initial Setting Mode to select the alarm, selectable items are

,

,

,

and

.

19

RS-485 Communication

1. Supporting transmission speed: 2,400, 4,800, 9,600, 19,200, 38,400bps

2. Non-supported formats: 7, N, 1 or 8, O, 2 or 8, E, 2

3. Communication protocol: Modbus (ASCII or RTU)

4. Function code: 03H to read the contents of register (Max. 8 words). 06H to write 1 (one) word into register. 02H to read the bits

data (Max.16 bits). 05H to write 1 (one) bit into register.

5. Address and Content of Data Register:

Address

Content

Definition

Measuring unit is 0.1, updated one time in 0.1 second

The following reading value display indicates error occurs:

8002H : Initial process (Temperature value is not got yet)

1000H

Present value (PV)

8003H : Temperature sensor is not connected

8004H : Temperature sensor input error

8006H : Cannot get temperature value, ADC input error

8007H : Memory read/write error

1001H

Set point (SV)

Unit is 0.1, oC or oF

1002H

Upper-limit of temperature range The data content should not be higher than the temperature range

1003H

Lower-limit of temperature range The data content should not be lower than the temperature range

1004H

Input temperature sensor type

Please refer to the contents of the “Temperature Sensor Type and Temperature Range” for detail

1005H

Control method

0: PID, 1: ON/OFF, 2: manual tuning, 3: FUZZY

1006H

Heating/Cooling control selection

0: Heating/ Heating, 1: Cooling/ Heating, 2: Heating/Cooling, 3: Cooling/ Cooling, 4: Heating/ Alarm, 5: Cooling/ Alarm

1007H

1st group of Heating/Cooling control cycle

1~990, unit is 0.1 second. When the output setting = realy, the minimum control cycle is 5 second

1008H

2nd group of Heating/Cooling control cycle

1~990, unit is 0.1 second. When the output setting = realy, the minimum control cycle is 5 second 1~990

1009H

PB Proportional band

0.1 ~ 999.9

100AH

Ti Integral time

0~9,999

100BH

Td Derivative time

0~9,999

100CH

Integration default

0 ~ 100%, unit is 0.1%

100DH

Proportional control offset error value, when Ti=0

0 ~ 100%, unit is 0.1%

100EH

The setting of COEF when Dual Loop output control are used

0.01 ~99.99, unit is 0.01

100FH

The setting of Dead Band when Dual Loop output control are used

-99.9 ~ 999.9

1010H

Hysteresis setting value of the 1st output group

-99.9~999.9

1011H

Hysteresis setting value of the 2nd output group

-99.9~999.9

1012H

Read Output 1 value

Unit: 0.1%

1013H

Read Output 2 value

Unit: 0.1%

1014H

Write Output 1 value

Unit: 0.1%, only valid in manual control mode

1015H

Write Output 2 value

Unit: 0.1%, only valid in manual control mode

1016H

Temperature regulation value

-99.9 ~ +99.9. Unit is 0.1

1017H

Analog decimal setting

0 ~ 3

101CH

PID parameter selection

0~5/AUTO

101DH

SV value corresponded to PID value

Only valid within available range, unit: 0.1 scale

1020H

Alarm 1 type

Please refer to the contents of the “Alarm Outputs” for detail

1021H

Alarm 2 type

Please refer to the contents of the “Alarm Outputs” for detail

1022H

Alarm 3 type

Please refer to the contents of the “Alarm Outputs” for detail

1024H

Upper-limit alarm 1

Please refer to the contents of the “Alarm Outputs” for detail

1025H

Lower-limit alarm 1

Please refer to the contents of the “Alarm Outputs” for detail

1026H

Upper-limit alarm 2

Please refer to the contents of the “Alarm Outputs” for detail

20

1027H 1028H 1029H 102AH 102BH 102CH 102FH 1030H 1032H
1033H 1034H 1035H 1036H 1039H 103AH 103BH 103CH 101FH
1200H~13FFH
1400H~140FH

Lower-limit alarm 2 Upper-limit alarm 3 Lower-limit alarm 3 Read LED Status
Read Pushbutton Status Setting lock status Software version Start pattern number Remaining time of the executed step (second) Remaining time of the executed step (minute) No. of currently executed step No. of currently executed pattern Read dynamic value in programmable control Communication write Temperature unit display selection AT setting
Control RUN/STOP setting
Start step number Pattern 0~15 temperature set point setting (Even number) Pattern 0~15 execution time setting (Odd number) Actual number of step setting inside the corresponding pattern

Please refer to the contents of the “Alarm Outputs” for detail Please refer to the contents of the “Alarm Outputs” for detail Please refer to the contents of the “Alarm Outputs” for detail b0: ALM3, b1: ALM2, b2: , b3: , b4: ALM1, b5: OUT2, b6:OUT1, b7: AT b1: F2, b2: Up, b3: Loop, b5: F1, b6: Down, b7: Set, 0: press down key
V1.00 indicates 0x100 0 ~ 15 Only read
Only read
Only read Only read Only read
0: Disable (default), 1: Enable 0: , 1: / linear input (default) 0: OFF (default), 1: ON 0: STOP, 1: RUN (default), 2:END (program mode), 3: HOLD (program mode) 0 ~ 15
-999 ~ 9999 Time: 0 ~ 9001 minute per scale
0 ~ 15 = N, indicate that this pattern is executed from step 0 to step N

Cycle number for repeating the 1410H~141FH execution of the correspond 0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times
pattern

1420H~142FH

Link pattern number setting of the correspond pattern

0 ~ 15, 16 indicates the program end and keep in present step. 17 indicates the program end and execution end. 0~15 indicates the next execution pattern number after executing the current pattern

Address 1100H 1101H
1102H 1103H 1104H
1105H 1106H 1107H 1108H 1109H 110AH 110BH 110CH 110DH 110EH 110FH 1110H 1111H
1112H

Content Adjust Temperature Gain
Temperature Filter Range
Temperature Filter Factor Reverse Output Slope of Temperature Increase
Remote Input Type Selection AT Control Remote Input Reverse Setting Alarm 1 Function Selection Alarm 2 Function Selection Alarm 3 Function Selection Alarm 1 Output Delay Time Alarm 2 Output Delay Time Alarm 3 Output Delay Time Upper Limit of Control Output 1 Lower Limit of Control Output 1 Upper Limit of Control Output 2 Lower Limit of Control Output 2 Programmable Waiting Temeprature

Definition
Range of temperature filter: 10~1000, unit: 0.01 , default: 100(1.0) Setting range: 0~50, default: 8 Bit1: output 2, Bit0: output 1 Unit: 0.1/min or 0.1/sec (refer to CommunicationAddress 1124H) 0: 0~20m A , 1: 4~20m A, 2: 0~5V, 3: 1~5V, 4: 0~10V 0: AT(Auto-tune), 1: ST(Self-tune) 0: forward, 1: reverse Bit3: Peak Record, Bit2: Hold Enable, Bit1: Output Reverse, Bit0: Standby Enable Bit3: Peak Record, Bit2: Hold Enable, Bit1: Output Reverse, Bit0: Standby Enable Bit3: Peak Record, Bit2: Hold Enable, Bit1: Output Reverse, Bit0: Standby Enable Unit: second. Setting range: 0~100sec Unit: second. Setting range: 0~100sec Unit: second. Setting range: 0~100sec Range: lower limit of control output ~100%, unit is 0.1% Range: 0~upper limit of control output, unit is 0.1% Range: lower limit of control output~100%, unit is 0.1% Range: 0~upper limit of control output, unit is 0.1%
Setting range: 0~1000(100.0)

21

1113H 1114H 1115H 1116H
1117H
1118H
1119H
111AH
111BH
111CH
111DH
111EH 1120H 1121H 1122H 1123H 1124H 1125H 1126H 1127H 1128H 1129H 1182H 1183H

Programmable Waiting Time
Programmable Slope Increase
Testing Mode Adjust Upper Limit of Analog Linear Output 1 Adjust Lower Limit of Analog Linear Output 1 Adjust Upper Limit of Analog Linear Output 2 Adjust Lower Limit of Analog Linear Output 2 Adjust Retransmission Upper Limit Adjust Retransmission Lower Limit
Event 1 Selection
Event 2 Selection
Event 3 Selection
SV Control Mode Selection Adjust Remote Compensation Adjust Remote Gain Positive/Negative Selection for Remote Switch Slope Time Unit Cold Junction Compensation Reserve the Programmable Running Status when Power OFF Fuzzy Gain Fuzzy Dead Band Save Programmable Settings into Memory CT1 Read Value CT2 Read Value

Unit: min. Setting range: 0~900 Unit: 0.1/min or 0.1/sec— (refer to Communication Address 1124H) Setting range: 0~1000
Adjust current: 1scale=1A, Adjust voltage: 1scale=1mV
Adjust current: 1scale=1A, Adjust voltage: 1scale=1mV
Adjust current: 1scale=1A, Adjust voltage: 1scale=1mV
Adjust current: 1scale=1A, Adjust voltage: 1scale=1mV
Adjust current: 1scale=1A
Adjust current: 1scale=1A 0: OFF, 1: Run/Stop, 2: Change SV value, 3: PID/Manual control, 4: Switch to Programmable Hold mode 0: OFF, 1: Run/Stop, 2: Change SV value, 3: PID/Manual control, 4: Switch to Programmable Hold mode 0: OFF, 1: Run/Stop, 2: Change SV value, 3: PID/Manual control, 4: Switch to Programmable Hold mode 0: Constant, 1: Slope increase, 2: Programmable input, 3: Remote Input Setting range: -999~999 Setting range: -999~999
0: Positive, 1: Negative
0: min, 1: sec 0: ON, 1: OFF 0: None, 1: Running status is saved and will continue by the previous status when power ON. Setting range: 1~10 Setting range: 0.0~PB
0:None, 1: Saves the programmable settings into memory
Unit: 0.1A Unit: 0.1A

1. Communication Transmission Format: Command Code: 03: read words, 06: write 1 word ASCII Mode

Read Command

Read Command Response

Write Command

STX

‘: ‘ ‘: ‘

STX

‘: ‘ ‘: ‘

STX

‘: ‘ ‘: ‘

ADR 1

0′0′

ADR 1

0′0′

ADR 1

0′0′

ADR 0

1′1′

ADR 0

1′1′

ADR 0

1′1′

CMD 1

0′0′

CMD 1

0′0′

CMD 1

0′0′

CMD 0

3′2′

CMD 0

3′2′

CMD 0

6′5′

1′0′ Number of data 0′0′

1′0′

Starting data

`0′

`8′

`4′

(count by byte)

`2′

Starting data

`0′

`8′

address

0′1′ Start address 0′1′

address

0′1′

0′0′

data

1′7′

1′0′

`0′

0′ 1000H/081xHF’

`0′

0′F’

Number of data 0′0′

(word/Bit)

0′0′

4′1′

3′F’

Data content

`0′

E’0′

2′9′ Address data `0′

8′0′

LRC 1

E’D’

1001H

`0′

LRC1

F’E’

LRC 0

A’C’

`0′

LRC 0

D’3′

END 1

CR CR

LRC 1

0′E’

END 1

CR CR

END 0

LF LF

LRC 0

3′3′

END 0

LF LF

Write Command Response

STX

‘: ‘ ‘: ‘

ADR 1

0′0′

ADR 0

1′1′

CMD 1

0′0′

CMD 0

6′5′

1′0′

Starting data

`0′

`8′

address

0′1′

1′0′

0′F’

3′F’ Data content
E’0′

8′0′

LRC1

F’E’

LRC 0

D’3′

END 1

CR CR

END 0

LF LF

22

LRC checksum:

END 1 END 0

CR CR LF LF

LRC check is the added sum from “Address” to “Data content”. For example, 01H

  • 03H + 10+ 00H + 00H + 02H = 16H, then take the

complementary of 2, EAH.

RTU Mode

Read Command

Read Command Response

Write Command

Write Command Response

ADR

01H 01H

ADR

01H 01H

CMD

03H 02H

CMD

03H 02H

Starting data address

10H 08H Number of data 00H 10H (count by byte) 04H 02H

Number of data 00H 00H Start address 01H 17H

(word/Bit)

02H 09H

data

F4H 01H

1000H/081xH

CRC 1 CRC 0

C0H BBH

Address

03H

CBH A9H data1001H 20H

CRC 1

BBH 77H

CRC 0

15H 88H

ADR CMD Starting data address
Data content
CRC 1 CRC 0

01H 01H 06H 05H 10H 08H 01H 10H 03H FFH 20H 00H
DDH 8FH E2H 9FH

ADR CMD Starting data address
Data content
CRC 1 CRC 0

01H 01H 06H 05H 10H 08H 01H 10H 03H FFH 20H 00H
DDH 8FH E2H 9FH

CRC (Cyclical Redundancy Check) is obtained by the following steps.

1. Load in a 16-bit register FFFFH as the CRC register.

2. Do an exclusive OR operation of the first byte of the data and low byte of CRC register, and place the operation result back to the CRC register.

3. Right shift the bits in the CRC register and fill the high bits with “0”. Check the removed lowest bit.

4. If the removed lowest bit is “0”, repeat step 3. Otherwise, do an exclusive OR operation of the CRC register and the value A001H and place the operation result back to the CRC register.

5. Repeat step 3 and 4 until the 8 bits (1 byte) are all right shifted.

6. Repeat step 2 and 5 and calcualte all the bits to obtain CRC check.

Please be aware of the high/low byte transmission order in the CRC register.

Panel Cutout

Pattern

Panel Cutout ( W * H )

Model

Panel Cutout ( W * H )

4848 (DT320)

45mm * 45mm

7272 (DT330)

68mm * 68mm

4896 (DT340)

44.5mm * 91.5mm

9696 (DT360)

91mm * 91mm

When installing the temperature controller, a certain surrounding space should be maintained (as shown below) to ensure proper

cooling and easy removal of mounting accessories.

At least 60 mm space for upper and lower sides and 40 mm space for left and right sides.

23

Mounting and Bracket Installation
DT320 series: Step 1: Insert the controller through the panel cutout. Step 2: Slide M30.5 nut into the opening in the top of the mounting bracket and insert the M30.530mm mounting screw in the mounting
bracket. Insert the mounting bracket into the mounting groove at the right and left of the controller and push the mounting bracket forward until the bracket stops at panel wall. Step 3: Tighten screws on bracket to secure the controller in place. (The screw torque should be 0.4 to 0.5N.m )
DT330 series: Step 1: Insert the controller through the panel cutout. Step 2: Slide M3
0.5 nut into the opening in the top of the mounting bracket and insert the M30.530mm mounting screw in the
mounting bracket. Insert the mounting bracket into the mounting groove at the top and bottom of the controller and push the mounting bracket forward until the bracket stops at panel wall. Step 3: Tighten screws on bracket to secure the controller in place. (The screw torque should be 0.4 to 0.5N.m )
DT340 series: Step 1: Insert the controller through the panel cutout. Step 2: Slide M30.5 nut into the opening in the top of the mounting bracket and insert the M30.5*30mm mounting screw in the
mounting bracket. Insert the mounting bracket into the mounting groove at the top and bottom of the controller and push the mounting bracket forward until the bracket stops at panel wall. Step 3: Tighten screws on bracket to secure the controller in place. (The screw torque should be 0.4 to 0.5N.m )
24

DT360 series:
Step 1: Insert the controller through the panel cutout. Step 2: Slide M30.5 nut into the opening in the top of the mounting bracket and insert the M30.5*30mm mounting screw in the
mounting bracket. Insert the mounting bracket into the mounting groove at the top and bottom of the controller and push the mounting bracket forward until the bracket stops at panel wall. Step 3: Tighten screws on bracket to secure the controller in place. (The screw torque should be 0.4 to 0.5N.m )

Wiring Diagrams and Precautions

Tighten the screw to the torque between 0.4 and 0.5N.m. To avoid signal interference, it is suggested that the power cable and the signal cable to be set separately. Please use solid wires between 14AWG/2C and 22AWG/2C. Maximum 300V and rated temperature to 105°C for input power pins.

The warning symbol

on the case indicated the ports for power input pins 1 and 2. If the power supply is connected to other

ports, the controller will be burned, and personnel injury or fire may occur.

Please use relay output models within the rated load. Otherwise, the cable and crimp terminal may build up heat due to overload.

When the temperature exceeds 50°C, contact burning may occasionally occur.

Please use the crimp terminal of maximum 5.8 mm.

25

Wiring diagram and extention description
DT320

relay
analog current
relay
analog current

pulse voltage
linear voltage
pulse voltage
linear voltage

The middle 13~18 pins are provided after the extension board is installed. DT320A-0000: Built-in no RS485 exptension board, 13~16 pins can freely select the extension card. DT320A-0200: Built-in RS485 extension board, 13~16 pins can freely select the extension card, 17~18 pins have built-in
RS485 function. DT320A: You can install extension boards for 13~18 pins, or you can only install 3~4 pins for OUT2 output extension card.
OUT2 can be changed to be used by Alarm3, so the maximum is “2 output + 2 alarm” or “1 output + 3 alarm”. Extension board model: 1) DT3-20ESTD : without RS485, without EV3 2) DT3-20ECOM : with RS485, without EV3 3) DT3-20EEV3 : without RS485, with EV3

26

DT330
relay pulse voltage analog current linear voltage
TC
RTD
analog input

relay
analog current

pulse voltage
linear voltage

The 10~18 pins are provided after the extension board is installed.
DT330A-0000: Built-in no RS485 exptension board and has the OUT2 extension card already, OUT2 can be changed to be used by Alarm2, so the maximum is “2 output + 1 alarm” or “1 output + 2 alarm”. 12~15 pins can freely select the extension card.
DT330A-0200: Built-in RS485 extension board and has the OUT2 extension card already, OUT2 can be changed to be used by Alarm2, so the maximum is “2 output

  • 1 alarm” or “1 output + 2 alarm”. 12~15 pins can’t extension, 10~11 pins have built-in RS485 function.
    DT320A: Built-in no RS485 exptension board and has the OUT2 extension card already, OUT2 can be changed to be used by Alarm2, so the maximum is “2 output
  • 1 alarm” or “1 output + 2 alarm”, 10~15 pins can’t extension.

27

DT340/DT360
relay pulse voltage analog current linear voltage
TC
RTD analog input

relay
analog current

pulse voltage
linear voltage

The 13~24 pins are provided after the extension board is installed.
DT340/DT360A-0000: Built-in no RS485 exptension board, we can select OUT2 exetension card, OUT2 can be changed to be used by Alarm3, so the maximum is “2 output + 2 alarm” or “1 output + 3 alarm”. 18~21 pins can freely select the extension card DT340/DT360A-0200: Built-in RS485 extension board, we can select OUT2 exetension card, OUT2 can be changed to be used by Alarm3, so the maximum is “2 output + 2 alarm” or “1 output + 3 alarm”. 18~21 pins can freely select the extension card, 13~14 pins have built-in RS485 function. DT340/DT360A: You can install extension boards for 13~24 pins, OUT2 can be changed to be used by Alarm3, so the maximum is “2 output + 2 alarm” or “1 output + 3 alarm”. Extension board model:

  1. DT3-40ESTD : without RS485, without EV3
  2. DT3-40ECOM : with RS485, without EV3
  3. DT3-40EEV3 : without RS485, with EV3

28

DC model wiring diagram

DT320

DT340 / DT360

AC model wiring diagram

29

30

31

32

Prodcut Service
If you need more temperature controller information and technical support, please contact following website:
http://www.deltaww.com/ to download and contact region service window.
Delta Electronics, Inc. 18 Xinglong Road, Taoyuan District, Taoyuan City 33068, Taiwan, R.O.C.
33

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals