EE660 – Low Air Velocity Sensor with RS485 Interface
PLEASE NOTE
Find this document and further product information on our website at www.epluse.com/ee660.
Electrical Connection
WARNING
Incorrect installation, wiring or power supply may cause overheating and
therefore personal injuries or damage to property.
For correct cabling of the device, always observe the presented wiring diagram
for the product version used.
The manufacturer cannot be held responsible for personal injuries or damage to
property as a result of incorrect handling, installation, wiring, power supply
and maintenance of the device.
Hardware
The bus termination shall be realized with 120 Ω resistor using the switch on
the electronics board.
NOTICE
Improper handling of the device may result in its damage.
- The power supply must be strong enough to ensure supply voltage within the specified range (see technical data) at any time and at all devices in the bus. This is particularly relevant when using long and thin cables as those can cause high voltage drop. Please note that a single EE660 requires peak current of 150 mA.
Wiring
Digital interface
Address Setting
Address Switch
Address setting via PCS10 Product Configuration Software
All DIP switches at position 0 → address has to be set via PCS10.
Modbus (slave device): factory setting 65 (permitted values: 1…247).
BACnet (master device): factory setting 65 (permitted values: 0…127).
Example: Address is set via configuration software = factory setting.
Address setting via DIP switch
Modbus (slave device): Setting the DIP switches to any other address than
0, overrules the Modbus address set via PCS10 (permitted values: 1…247).
BACnet (master device): Setting the DIP switches to any other address
than 0, overrules the BACnet address set via configuration software.
BACnet Note: permitted values are 0…127. The 8th bit of the DIP switches
is ignored.
(ID 127 = 0111 111). To set address 0 via DIP switches, the 8th bit shall be
set to 1
(ID 0 = 1000 0000). Example: Address set to 11 (= 0000 1011 binary).\
BACnet Setup
Please refer to PICS (Product Implementation Conformance Statement),
available on www.epluse.com/ee660.
Modbus Setup
FLOAT32
Parameter | Unit 1) | Register number 2) [DEC] | Register address [HEX] 3) |
---|---|---|---|
Temperature | °C | 1003 | 3EA |
Temperature | °F | 1005 | 3EC |
Air velocity | m/s | 1041 | 410 |
Air velocity | ft/min | 1043 | 412 |
INT16
Parameter| Unit 1)| Scale 4)| Register number 2) [DEC]|
Register address 3) [HEX]
---|---|---|---|---
Read register: function code 0x03 / 0x04
Temperature| °C| 100| 4002| FA1
Temperature| °F| 50| 4003| FA2
Air velocity| m/s| 100| 4021| FB4
Air velocity| ft/min| 1| 4022| FB5
- The choice of measurement units (metric or non-metric) must be done according to the ordering guide, refer to EE660 datasheet.
- Switching from metric to non-metric or vice versa by using the PCS10 is not possible.
- Register number (decimal) starts from 1. 3) Register address (hexadecimal) starts from 0.
- Examples: For scale 100, the reading of 2550 means a value of 25.5. For scale 50, the reading of 2550 means a value of 51.
Communication settings (INT16)
Parameter| Register number 1) [Dec]| Register address 2) [Hex]|
Size 3)
---|---|---|---
Write register: function code 0x06
Modbus address 4)5)| 1| 00| 1
Modbus protocol settings 4)| 2| 01| 1
Device information (INT16)
Parameter| Register number 1) [Dec]| Register address 2) [Hex]|
Size 3)
---|---|---|---
Read register: function code 0x03 / 0x04
Serial number (as ASCII)| 1| 00| 8
Firmware version| 9| 08| 1
Sensor name (as ASCII)| 10| 09| 8
- Register number starts from 1.
- Protocol address starts from 0.
- Number of registers.
- For Modbus address and protocol settings refer to Application Note Modbus AN0103 (available at www.epluse.com/ee660).
- If the ID is set via DIP-Switch the response will be NAK.
EE660 – Low Air Velocity Sensor with Analogue Output
Wiring
Voltage output 0-10 V
Jumper Settings
For performing the EE660 settings via the PCS10 Product Configuration Software
(free download from www.epluse.com/pcs10) the
jumper for the measuring range must be set to HI.
Selection of response time t LO 90
|
---|---
Jumper t 90 SLOW 4 s (factory setting)| no jumper FAST 1 s
Selection of the measuring range
| |
---|---|---
Jumper HI
0…2 m/s
(0…400 ft/min)
(factory setting)| Jumper MED
0…1.5 m/s
(0…300 ft/min)| Jumper MED
0…1.5 m/s
(0…300 ft/min)
E+E Elektronik Ges.m.b.H.
Langwiesen 7
4209 Engerwitzdorf | Austria
T +43 7235 605-0
F +43 7235 605-8
info@epluse.com
www.epluse.com QG_EE660 | Version v1.2 | 06-2024