COMELIT Vedo Control Panels Communication Expansion Module Instruction Manual

July 26, 2024
Comelit

Vedo
VEDOGSM
TECHNICAL MANUAL

Vedo Control Panels Communication Expansion Module

COMELIT Vedo Control Panels Communication Expansion Module - QR
Cordhttps://pro.comelitgroup.com/manuals/22788

GSM communication card for Vedo Control Panels

The GSM communication expansion module Art.
VEDOGSM allows telephone calls, SMS, MMS and emails to be sent on the data network, plus the sending of digital protocols and date and time synchronisation. Combined with the voice message board Art. VEDOVOICE, it allows remote management of the control panel by a voice dialler.

Main features

  • GSM850, EGSM900, DCS1800, PCS 1900
  • GSM/GPRS channel support
  • Main or reserve telephone dialler
  • Indication of alarms, malfunctions, sabotage and events via SMS
  • Customisable SMS alerts
  • Control panel status interrogation via SMS
  • Checking residual credit of the prepaid SIM
  • Transmission of Voice Messages via GSM
  • Event transmission in Contact-ID and SIA (Level 1) format via GSM and over TCP-IP (SIA-DC-09 protocol support)
  • Event transmission by email with images
  • Event transmission by MMS
  • Date and time updating

Protocol number

All products have an identification label for traceability. Two examples are shown below:

Compatibility

This manual refers to the VEDOGSM model with protocol number ≥991201 or equal to 98xxxx, which can only be used with Comelit VEDO control panels, firmware version ≥2.13.0 For previous models, please refer to the specific manual available at the website pro.comelitgroup.com
The VEDOGSM module with firmware version ≤004 may only be used with Comelit VEDO control panels featuring firmware version ≤2.12.5 (Protocol number example 004PWWYYXXXXXXXX)

Technical specifications

Manufacturer /supplier Comelit Group S.p.A.
Dimensions (WxHxD) 72x48x29 mm (without antenna)
Weight 23 g without antenna

41 g with antenna
Consumption (min./max.)| 10 mA in Idle
60 mA in communication
Average power consumption in 1 h: 20 mAh 1 alarm every 5 minutes and communication with duration of 1 minute
Operating temperature and Operating humidity| -10 °C / + 55 °C with warm dry air
-10 °C / + 40 °C with max. + 93% RH (not condensed)
Certified safety grade| 2 according to EN50131-1
Observing any indications for configuration and installation
Environmental class| II in compliance with EN 50131-1
Types of alarm transmission for which the device is suitable| SP4 in compliance with EN 50131-1
Interface type| Control panel expansion
Operating mode saving and forwarding event / event transmission (passthrough)| Event transmission (pass-through)
Generation and/or transmission times of alarm messages| voice messages: 10 sec
email: 10 sec without image, 90 sec with image
MMS: 45 sec
Times for generating a reply signal (when used)| CONTACT ID: times according to standard SIA DC-05-1999.09
SIA: times according to standard SIA-DC-03-1990.01
SIA-DC-09: times according to standard ANSI/SIADC-09-2007
Times for detecting and presenting faults| No GSM and GPRS
coverage: 120 sec
SIM fault: 20 sec
Antenna disconnected: 45 sec
Method for signalling faults to alarm system| Alert send failure: regular or on event
Level of output signals and/or sensitivity of input signals| Minimum level DTMF tones at input: 36mVeff – 28.8dbV 100mVpp
Level DTMF tones at output: low freq 9 dBm / high freq 11 dBm
Safety signals level supplied| Digital protocols protected for info and replacement Telephone protocols
(Contact ID and SIA): no information protection
IP protocols: information protection and protection from replacement
Sharing of transmission connections| GSM: GSM850, EGSM900, DCS1800, PCS 1900
Class 4 (2W) for GSM850 / EGSM900
Class 1 (1W) for DCS1800 /PCS1900
Voltage operating range| 10 ~ 15 V
| Specifications in compliance with EN 50136-2
| Cut off the power supply (both power supply unit and battery) before
fitting/removing modules! Risk of permanently damaging the expansion
module and the control panel board.

Description

  1. COMELIT Vedo Control Panels Communication Expansion Module - Description Antenna connector
  2. SIM housing
  3. LED enabling/disabling jumper
  4. Module connector position

● Holes for securing the module to the control panel board

LED AND JUMPER

DL1| Green LED: module serial communication. Lights up briefly when the module communicates with the control panel.
---|---
DL2| Green LED: module serial communication. Lights up briefly when the module communicates with the control panel.
DL3| Red LED off: The module is not in operation.
Red LED rapid flashing (64 ms On/ 800 ms Off):
The module is not connected to the network.
Red LED slow flashing (64 ms On/ 2000 ms Off):
The module is connected to the network.
DL4| Red LED: GSM communication. Flashes when a transfer via the GSM or GPRS network is in progress, e.g. during receipt of an SMS or during registration with the network at the time of initialisation.
Jumper| If disconnected, the LEDs turn off

Installation

  1. Make sure the board on which you intend to fit the module is not connected to the power supply!
  2. Insert the plastic spacers in the relevant holes.
  3. Then, taking care to plug the module connector into the control panel connector designated MOD5 correctly, apply sufficient pressure to engage the spacers in the GSM expansion card and plug the connector in almost completely.COMELIT Vedo Control Panels Communication Expansion Module - GSM
  4. Once the module has been fitted correctly, connect the antenna that you intend to use by tightening the connector on the cable to the goldcoloured connector on the GSM module.

The antenna must be correctly connected and its connector must be fully tightened.
Before using the module, it must be enabled with the Safe Manager software. If the module is enabled but not connected, a fault will be generated. Antenna presence can be detected only using the antenna supplied. In all other cases antenna presence detection must be excluded from the GSM dialler options.

ANTENNA POSITIONING WITH BOXSTANDARD HOUSING
Place the antenna at least 20 cm away from the GSM module.
Do not place the antenna on metal surfaces! The antenna can be fitted externally; for this reason there are 2 cutouts to allow easy feedthrough of the antenna cable.![COMELIT Vedo Control Panels Communication Expansion Module

Do not place the antenna on metal surfaces!

COMELIT Vedo Control Panels Communication Expansion Module - antenna
on

FITTING THE SIM CARD

  1. First check that all power is OFF.
    √ The SIM card must be enabled, and if it is a payas-you-go type, it must have sufficient credit on it to be able to make phone calls, send messages or transmit digital protocols via TCP-IP. It is not essential to unlock it, because the control panel is capable of managing the PIN to unlock the SIM card.

  2. Gently force the top of the SIM connector towards the centre of the control panel board (downwards if the control panel is already mounted on the wall).

  3. Once you have overcome the resistance, turn it over on its hinges.

  4. Insert the SIM card in the mobile part in such a way that you can see the gold-coloured contacts of the SIM and that the bevelled corner is on the left.

  5. Repeat the sequence in reverse to release the SIM card from its seat.

The product complies with standards EN 50131-1EN 50136-1, EN 50136-2, EN 61000-6-3.
The device is immune to the disturbances governed by standard EN 50130-4.
Emission standards with which the device complies: EN 61000-6-3, EN 50130-4, EN 301489-1, EN 301489-3, EN 301489-17.

Warning

  • This Comelit product has been designed and manufactured for use in the creation of security and automation systems in residential, commercial, industrial and public buildings.

  • All activities connected to the installation of Comelit products must be carried out by qualified technical personnel, with careful observation of the indications provided in the manuals supplied with those products.
    The product must be installed to the highest standards.

  • Disconnect the power supply before carrying out any operations on the wiring.

  • Use wires with a cross-section suited to the distances involved, observing the instructions provided in the system manual.

  • We advise against running the system wires through the same duct as power cables (230V or higher).

  • To ensure Comelit products are used safely: carefully observe the indications provided in the manuals / instruction sheets; make sure the system created using Comelit products has not been tampered with / damaged.

  • Comelit products do not require maintenance aside from routine cleaning, which should be carried out in accordance with the indications provided in the manuals / instruction sheets. Any repairs must be carried out: for the products themselves,  xclusively by Comelit Group S.p.A.; for the systems, by qualified technical personnel. Do not use alcohol or aggressive products for cleaning purposes.

  • Comelit Group S.p.A. accepts no liability for any purpose other than the intended use, or failure to observe the indications and warnings contained in this manual / instruction sheet. Comelit Group S.p.A. reserves the right to change the information provided in this manual / instruction sheet at any time and without prior notice.

  • The manufacturer, Comelit Group S.p.A., hereby declares that this equipment conforms to the applicable directives. The full EU conformity declaration is available on the product web page.

  • In accordance with art. 26 of Italian Legislative Decree dated 14th March 2014, no. 49 “Implementation of directive 2012/19/EU on Waste Electrical and Electronic Equipment (WEEE)”. the “crossed-out wheelie bin” symbol indicates that at the end of its useful life, this product must be separated from other waste before collection for disposal. The user should therefore take the exhausted appliance to suitable local collection centres for waste electrical and electronic products. As an alternative to handling this process yourself, you can take the appliance to your local equipment dealer when purchasing a new equivalent product. Electronics dealership businesses covering an area of 400 m² are also obliged to accept waste electronic products smaller than 25 cm for disposal, without any obligation to purchase. Suitable separated waste collection for the subsequent reuse of the appliance sent for recycling, processing and environmentally conscious disposal helps to avoid potential negative effects on the environment and human health, and encourages the reuse and recycling of the materials used in the construction of the appliance.

www.comelitgroup.com
Via Don Arrigoni, 5 – 24020 Rovetta (BG) – Italy

6ª edizione 01/2024