LEDVANCE MCU Select DALI-2 Controllers User Guide

July 25, 2024
LEDVANCE

MCU Select DALI-2 Controllers

“`html

Specifications

  • Product Name: MCU SELECT DALI-2 controllers

  • Model Numbers: MCU SELECT DALI-2 EXC TW, MCU SELECT DALI-2
    TW

  • EAN: 4058075837522, 4058075837485, 4058075837508

Product Information

The MCU SELECT DALI-2 controllers are advanced lighting
management devices designed for efficient control of DALI-2
compatible luminaires. With features like setting minimum dimming
levels, memory value storage, and behavior customization after
mains interruption, these controllers offer versatile lighting
solutions for various applications.

Product Usage Instructions

1. Mounting

Ensure to switch off mains and DALI supply during
installation.

  • Flush Box Mounting: Suitable for concrete walls or hollow
    walls.

  • Surface Mounting: Follow dimensions and fixation hole patterns
    provided. Ensure cable/wire preparation is done correctly.

2. Configuration

Behavior after mains interruption can be set using the rotary
switch on the backside of the MCU:

  • *  **A:** Last dimming level and switching state  

    before interruption will be re-established.

    • *B:** Dimming level stored by Double Click (=
      Memory value).

3. Handling

User Operation:

  • * Follow the instructions provided in the user manual for daily  

    operation.

4. Resetting MCU and DALI Drivers

  1. 1. Switch off mains of the MCU and all connected devices, then set  

    rotary switch to position 9.

  2. Switch on mains of the MCU and connected devices.

  3. If light is ON, switch off lights via short push to the rotary
    knob of the MCU.

Frequently Asked Questions (FAQ)

Q: What should I do if the lights do not respond to the

controller?

A: Check the power supply to the controller and ensure proper
wiring connections. Reset the controller following the provided
instructions if needed.

“`

1
LIGHT MANAGEMENT IS VIVARES
Application guide MCU SELECT DALI-2 controllers
Status: June 2024 | LEDVANCE Subject to change without and notes. Errors and omission excepted.

2
Application guide MCU SELECT / SELECT TW

MCU SELECT DALI-2 EXC TW

MCU SELECT DALI-2

MCU SELECT DALI-2 TW

EAN: 4058075837522

EAN: 4058075837485

EAN: 4058075837508

3
Application guide MCU SELECT / SELECT TW

Table of contents

Topic

page

1. General: Features & benefits / Compatible design covers

3

3. Mounting: Flush box mounting / Surface mounting

5

4. Configuration: Behaviour after mains interruption / RESET / Set minimum dimming level

7

5. Handling: User operation

10

6. Application example 1: Meeting room

12

7. Application example 2: Room with motion detectors

14

8. Application example 3: Room with room with partition wall

16

9. Application example 4: Room with room with partition walls and motion detectors

18

10. Questions and Answers

21

11. Troubleshooting

22

12. Technical data

23

4
Application guide MCU SELECT / SELECT TW ­ Features & benefits

Product Features
· Dimming and switching of DALI fixtures via integrated rotary knob · Change of color temperature* in combination with DALI DT8 drivers · Control up to 25 DALI LED drivers per active control unit
Product Benefits
· All in one solution with integrated DALI power supply · Plug and control ready · Compatible with 3rd party design covers of leading European brands · Interconnection of up to 4 MCU’s with automatic synchronization via DALI · Suitable for rooms with separation walls · Possibility of combination with standard motion detectors · Fits into standard flush device boxes with > 40mm depth · Works in active
(= mains powered) or
passive mode (= DALI powered) · Automatic or manual memory of switch on level · Individual setting of lowest dimming level · Configuration of power on state after mains interruption by rotary switch
Application areas
· Conference rooms · Residential / Shop/ Hospitality areas

  • Only MCU SELECT DALI-2 TW and MCU SELECT DALI-2 EXC TW

5
Application guide MCU SELECT / SELECT TW ­ Compatible design covers
Compatible design covers
6mm Adapter *
(subject to change without notice)

  • Supplied with MCU SELECT DALI-2 EXC TW

6
Application guide MCU SELECT / SELECT TW ­ Flush mounting

Suitable flush boxes
For concrete walls / for hollow walls

Wire preparation

Switch off mains and DALI supply during installation !

7
Application guide MCU SELECT / SELECT TW ­ Surface mounting

Mounting principle

Dimensions and fixation hole pattern

Side cable entry

Rear cable entry

SURFACE MOUNT FRAME
(4058075843561)
Switch off mains and DALI supply during installation !

Cable / wire preparation

8

Application guide MCU SELECT / SELECT TW ­ Configuration: Behaviour after mains interruption

State of the lighting after mains interruption can be set by the rotary switch on the backside of the MCU

Setting MCU SELECT DALI-2

MCU SELECT DALI-2 TW / MCU SELECT DALI-2 EXC TW

A

Last dimming level and switching state before Last dimming level / last CCT and switching state before mains

mains interruption will be re-established

interruption will be re-established

B*

Dimming level stored by Double Click (=

Memory value)

Dimming level and CCT stored by Double Click (= Memory value)

C

10% brightness

10% brightness, CCT = 4000K

D

20% brightness

20% brightness, CCT = 4000K

E

30% brightness

30% brightness, CCT = 4000K

F

50% brightness

50% brightness, CCT = 4000K

0

80% brightness

80% brightness, CCT = 4000K

1

100% brightness

100% brightness, CCT = 4000K

2

OFF (Light level 0%)

OFF (Light level 0%)

3

No light level command send

(= individual “DALI POWER ON LEVEL” programmed in the DALI drivers applies)

4-8

Reserved (do not use)

Switch off mains and DALI supply before accessing the rotary switch on the backside!

  • In Setting B the double click is disabled. Please store the memory value to be used after mains interruption by setting the rotary switch temporarily to position A.

9
Application guide MCU SELECT / SELECT TW ­ Configuration: RESET

RESET MCU and the connected DALI drivers

Step 1: Step 2:

Switch off mains of the MCU and of all connected devices, then set rotary switch on the backside of the MCU to position 9
Switch on mains of the MCU and of all connected devices

Step 3: If light is ON, Switch Off lights via Short push to the rotary knob of the MCU

Step 4: Keep rotary knob of the MCU pressed for > 10s until light goes to 100%

Step 5: Step 6:

Switch off mains of the MCU and of all connected devices, then set rotary switch back to the original position
Switch on mains of the MCU and of all connected devices

Remark
Note previous position of the switch
A DALI RESET command is sent to all connected drivers and the minimal dimming level is reset to 1%. RESET affects all interconnected powered up MCUs and drivers

Switch off mains and DALI supply before accessing the rotary switch on the backside!

10
Application guide MCU SELECT / SELECT TW ­ Configuration: Set minimum dimming level

Setting the minimal dimming level

Remark

Step 1: Step 2:

Switch off mains of the MCU and of all connected devices, then set rotary switch on the backside of the MCU to position 9
Switch on mains of the MCU and of all connected devices

Note previous position of the switch

Step 3: If light is OFF, Switch On lights via Short push to the rotary knob of the MCU

Step 4: Step 4: Step 5:

Adjust brightness level by clockwise / counterclockwise rotation of the knob until desired minimal brightness level is achieved Keep rotary knob of the MCU pressed for > 10s until lights blink
Switch off mains of the MCU and of all connected devices, then set rotary switch back to the original position

If 1% or low dimming levels cannot be achieved by rotation of the knob, please RESET the MCU and the drivers
Current brightness level is stored as new minimum dimming level. Minimum dimming level setting affects all interconnected and powered up MCUs.

Step 6: Switch on mains of the MCU and of all connected devices

Switch off mains and DALI supply before accessing the rotary switch on the backside!

11
Application guide MCU SELECT / SELECT TW ­ User operation
Switch ON / OFF
· To switch on / off briefly press the rotary knob. · Switching direction toggles with each knob press.

Define manual Switch ON behaviour

· To store a fixed brightness and CCT for Switch ON, adjust brightness and CCT value as desired and store by Double Click.
(Note: Double Click is disabled in turnkey position B)
· Storage is indicated by two times blinking of the lights.
Double Click

· To delete a fixed brightness and CCT* for Switch ON, switch off the light and Double Click the knob.
(Note: Double Click is disabled in turnkey position B)
· Deletion is indicated by lights switching to ON 100%/4000K. Without after deletion, the last values before manual OFF will be used for Switch ON.
Double Click

  • Only MCU SELECT DALI-2 EXC TW and MCU SELECT DALI-2 TW

12
Application guide MCU SELECT / SELECT TW ­ User operation
Dimming
· If light is switched on, light level can be increased by a clockwise rotation of the knob and decreased by a counterclockwise rotation.
· The magnitude of change of the light level is derived from the rotation speed and rotation angle · The minimum dimming level can be restricted as described in the chapter “Configuration” of this guide
Setting the colour temperature (CCT)*
· If light is switched on and DALI DT8 compatible luminaires are connected, the colour temperature can be increased by a clockwise rotation when the knob is pressed and decreased by a counterclockwise rotation of the pressed knob.
· The magnitude of change of the CCT is derived from the rotation speed and rotation angle

  • Only MCU SELECT DALI-2 EXC TW and MCU SELECT DALI-2 TW

13
Application guide MCU SELECT / SELECT TW ­ Application example 1: Meeting room

Description
FUNCTIONALITY · Up to 25 luminaires shall be controlled by a broadcast DALI signal · Dimming and switching of all luminaires shall be possible at both entry doors of the
room
PRINCIPLE SETUP · A MCU SELECT is installed at both entry doors · The MCU at one door is connected to mains and acts as central DALI bus power
supply (= active MCU) · The second MCU is connected to DALI only and is supplied from the DALI bus (=
passive MCU) · All luminaires are connected to mains and the DALI bus
OPTIONS · If tunable white luminaires shall be controlled, please use MCU SELECT DALI-2 EXC TW
or MCU SELECT DALI-2 TW · If number of luminaires is > 25, please connect second MCU also to mains

Installation scheme

230VAC

Active MCU

Passive MCU

14
Application guide MCU SELECT / SELECT TW ­ Application example 1: Meeting room

Installation
Safety · Switch off mains and DALI supply during installation ! · DALI must be treated like mains voltage
Wiring · Max. total DALI wire length: 300m · Recommended DALI wire diameter 1,5mm² · DALI and mains voltage may be routed in the same cable
(e.g. NYM 5×1,5mm²) Hints: – Ensure correct polarity DA+/DA- when connecting the
second MCU – Respect the max. number of luminaires per circuit breaker
as otherwise high inrush currents at mains switch on of the ComLEmDisdsriivoenrisnmg ay trigger the fuse · To avoid that lights are switched on after a temporary mains
interruption please set turnkeys of all MCU to identical position A (=last state) or position 2 (=OFF)
Possible system size · Max. 25 DALI drivers per active DALI MCU · Max. 4 DALI MCU per system · Each Active MCU can power 1 passive MCU via DALI bus

Wiring diagram 1:
Active MCU SELECT

DA+
DA-
L
N

N L DA-DA+

~

~

DT6/DT8 DALI

DA

driver

DA

Up to 25 drivers

~

~

DT6/DT8 DALI

DA

driver

DA

Passive MCU SELECT
N L DA-DA+

15
Application guide MCU SELECT / SELECT TW ­ Application example 2: Room with motion detectors

Description
FUNCTIONALITY · Up to 25 luminaires shall be switched by standard motion detectors · Dimming and switching of all luminaires shall be possible at both entry doors of the room
if persons are present
PRINCIPLE SETUP · A MCU SELECT is installed at both entry doors · The MCU at one door is connected to mains and acts as central DALI bus power supply
(= active MCU) · The second MCU is connected to DALI only and is supplied from the DALI bus (= passive
MCU) All luminaires are connected to the DALI bus · Mains of all luminaires and the active MCU is switched via the load contacts of the detectors

Installation scheme
Active MCU 230VAC

Passive MCU

16
Application guide MCU SELECT / SELECT TW ­ Application example 2: Room with motion detectors

Installation
Safety · Switch off mains and DALI supply during installation ! · DALI must be treated like mains voltage
Wiring · Max. total DALI wire length: 300m · Recommended DALI wire diameter 1,5mm² · DALI and mains voltage may be routed in the same cable
(e.g. NYM 5×1,5mm²) Hints: – Ensure correct polarity DA+/DA- when connecting the
second MCU – Respect the max. number of luminaires per circuit breaker
and max. load at the switched sensor output Commissioning · Fully automatic ON/OFF by motion detection:
Set turnkeys of all MCU to identical position C-F, or 0,1 · Semi automatic (= Manual ON via MCU and automatic OFF
via Motion detector): Set turnkeys of all MCU to position 2
Possible system size · Max. 25 DALI drivers per active DALI MCU · Max. 4 DALI MCU per system · Each Active MCU can power 1 passive MCU via DALI bus

Wiring diagram 2:

Active MCU SELECT

DA+
DA-
L
N

N L DA-DA+

~

~

DT6/DT8 DALI

DA

driver

DA

Motion /Presence sensors with mains voltage contact

Up to 25 drivers

~

~

DT6/DT8 DALI

DA

driver

DA


Passive MCU SELECT
N L DA-DA+

17
Application guide MCU SELECT / SELECT TW ­ Application example 3: Room with room with partition walls

Description
FUNCTIONALITY · Central dimming and switching of all luminaires shall be possible at both entry doors
of the room when separation wall is open · Independent control of each part room shall be possible as soon as soon as the room
is split in two separate rooms by closing the wall
PRINCIPLE SETUP · A MCU SELECT is installed at both entry doors · Both MCU at are connected to mains and act as DALI bus power supply (= active
MCUs) · While the DALI wires of both part rooms are interconnected when the wall is open, the
DALI connection between both parts is interrupted at one pole when the wall is closed · All luminaires are connected to mains and the DALI bus of the DALI MCU of the
corresponding part room.

Installation scheme

230VAC

Active MCU

OPTIONS · If tunable white luminaires shall be controlled, please use MCU SELECT DALI-2 EXC
TW or MCU SELECT DALI-2 TW

230VAC

Active MCU

18
Application guide MCU SELECT / SELECT TW ­ Application example 3: Room with room with partition walls

Installation hints
Safety · Switch off mains and DALI supply during installation ! · DALI must be treated like mains voltage
Wiring · Max. total DALI wire length: 300m · Recommended DALI wire diameter 1,5mm² · DALI and mains voltage may be routed in the same cable
(e.g. NYM 5×1,5mm²) Hints: – Ensure correct polarity DA+/DA- when connecting the
second MCU – Respect the max. number of luminaires per circuit breaker
Commissioning · To avoid that lights are switched on after a temporary mains
interruption please set turnkeys of all MCU to identical position A (=last state) or position 2 (=OFF)
Possible system size · Max. 25 DALI drivers per active DALI MCU · Max. 4 DALI MCU per system · Each Active MCU can power 1 passive MCU via DALI bus

Wiring diagram 3:
Active MCU SELECT
N L DA-DA+
DA+
DA-
L N

~

~

DT6/DT8 DALI

DA

driver

DA

~

~

DA

DA

Separation wall switch (contact open when wall is closed)

driver

DT6/DT8 DALI

driver

DT6/DT8 DALI

Up to 25 drivers

Up to 25 drivers

~

~

DA

DA

~

~

DT6/DT8 DALI

DA

driver

DA

Active MCU SELECT
N L DA-DA+

19

Application guide

MCU

SELECT

/

SELECT

TW

­

Application

example

4:

Room with room motion detectors

with

partition

walls

and

Description
FUNCTIONALITY · If separation wall is closed light is switched on individually in each room part when
motion is detected and can then be dimmed and switch via the MCU of this room part. · If separation wall is open light is switched on centrally for the whole when motion is
detected by one of the sensors. If the room is occupied and the wall is open, a central manual control of all luminaires is possible via both MCU.
PRINCIPLE SETUP · A MCU SELECT is installed at both entry doors · All MCU are connected to mains (= active MCUs)
Luminaires of a room part are connected to the DALI bus of the MCU in this room part · Mains supply of the luminaires and the MCU in a part room are switched via the
motion detector in this part · When separation wall is opened the DALI Bus of the part rooms are interconnected · When separation wall is opened the mains output of the motion detectors are
interconnected

Active Installation scheme
MCU
230VAC

OPTIONS · If tunable white luminaires shall be controlled, please use MCU SELECT DALI-2 EXC
TW or MCU SELECT DALI-2 TW

Active MCU

20

Application guide

MCU

SELECT

/

SELECT

TW

­

Application

example

4:

Room with room with motion detectors

partition

walls

and

Installation hints
Safety · Switch off mains and DALI supply during installation ! · DALI must be treated like mains voltage Wiring · Max. DALI wire length (total for all room parts): 300m · Recommended DALI wire diameter 1,5mm² · DALI and mains voltage may be routed in the same cable
(e.g. NYM 5×1,5mm²) Hints: – Ensure correct polarity DA+/DA- when connecting the
second MCU – Respect the max. number of luminaires per circuit breaker
and max. load at the switched sensor output
Commissioning · Fully automatic ON/OFF by motion detection:
Set turnkeys of all MCU to identical position C-F, or 0,1 · Semi automatic (= Manual ON via MCU and automatic OFF
via Motion detector): Set turnkeys of all MCU to position 2
Possible system size · Max. 25 DALI drivers per room part · Max. 4 room parts with one active DALI MCU each

Wiring diagram 4a :
Motion /Presence sensor with mains voltage contact

Active MCU SELECT

DA+
DA-
L
N

N L DA-DA+

~

~

DT6/DT8 DALI

DA

driver

DA

~

~

DT6/DT8 DALI

DA

driver

Separation wall switch (contacts open when wall is closed)
Up to 25 drivers

DA

~

~

DT6/DT8 DALI

DA

driver

DA

~

~

DA

DA

Motion /Presence sensor with mains voltage contact

Up to 25 drivers

DT6/DT8 DALI

driver

Active MCU SELECT
N L DA-DA+

21

Application guide

MCU

SELECT

/

SELECT

TW

­

Application

example

4:

Room with room with motion detectors

partition

walls and

Wiring diagram 4b: dividable room with motion detectors, separate mains circuits for the part rooms

Motion /Presence sensor with mains voltage contact

Separation wall switch (contacts open when wall is closed)

Motion /Presence sensor with mains voltage contact

Active MCU SELECT

DA1+
DA1-
L1 N
L1´

N L DA-DA+

~

~

DT6/DT8 DALI

DA

driver

DA

Up to 25 drivers
A K1 B

~

~

DT6/DT8 DALI

DA

driver

DA

DT6/DT8 DALI

driver

Up to 25 drivers

DA

DA

~

~

DA

DA

~

~

A K3 B

A K2 B

DT6/DT8 DALI

driver

Active MCU SELECT
N L DA-DA+
DA2+
DA2-
L2 N L2´

22
Application guide MCU SELECT / SELECT TW
Questions and Answers
Q: How can I set an individual level / a individual CCT for automatic switch on when motion is detected? A: Temporarily set the turnkey of all MCU to position A, ensure that separation wall is open and the MCU are interconnected via DALI and are powered up.
The adjust the brightness and the CCT to the desired levels and store this level by a Double click to the rotary knob of the MCU. Finally set the turnkey of all MCU to position B Q: As the of room parts are bigger, they can not be covered by the detection area of a single motion detector, how can I increase the number of detectors? A: If you need multiple detectors in one part room just interconnect the Outputs with switched phase (L’) of the detectors Q: What if the high number of drivers per part room exceeds the load capacity of the switching contact of the motion detector? A: If the max. capacitive load of the detector is not sufficient, please use a power conductor / power relay in-between luminaires and load contact of the motion detector Q: What if the room parts are connected to different phases and circuit breakers and may therefore not be interconnected by the switch contact of the movable wall? A: In this case you need additional power conductors, please see corresponding wiring diagram Q: Can I use also daylight dependent control? A: If the selected motion detectors have an integrated light sensor, it is possible to set a brightness threshold directly at the sensors. That avoids an unnecessary switch on if
sufficient daylight is available. A closed loop / daylight harvesting control is not possible. Q: Can I use DALI sensors instead of the standard motion detectors? A: No, the DALI MCU does not support other DALI control devices such as DALI Sensors or DALI Push button couplers.
Q: Can I connect a DALI MCU to another DALI control system or a BMS solution? A: No, the DALI MCU is a standalone control solution
Q: Is it possible to control more than 25 drivers with one MCU ? A: Yes. If you need to control more luminaires, please use an external DALI power supply. The DALI MCU should not be connected to mains but supplied out of DALI (=passive
DALI MCU). Consider 10mA as DALI current consumption of the DALI MCU and 2mA for each driver.

23
Application guide MCU SELECT / SELECT TW
Questions and Answers
Q: Can I mix/interconnect MCU SELECT and MCU TOUCH in the same installation? A: In principle that is possible, as there may be some limitations concerning the synchronization of MCU of different type, this combination is not officially recommended

24
Application guide MCU SELECT / SELECT TW
Troubleshooting
Q: What can I do if some luminaires have a different dimming behavior than the rest ? A: Most probably not all DALI drivers have ex-factory settings. Please perform a RESET as described at the beginning of this application guide
Q: I have installed two MCU, why do the lights behave differently depending which MCU I use? A: To ensure a complete synchronization, the MCU must be interconnected and powered when configuration settings such as storing a Switch On level or a Min level are done
Q: The MCU is not working, and lights stay always at 100%, what is the possible root cause? A: Most probably the DALI bus voltage is missing, and the luminaires are at System failure level. Please check DALI voltage with a multimeter (typically: ~16V DC).
Possible root cause: The MCU has no mains supply or the DA+/DA- wires of interconnected are mixed up at one MCU or the number of drivers / passive MCU is too high

25
Application guide MCU SELECT / SELECT TW

Technical data
Input voltage range (AC) Power consumption Allowed wire diameter Protection class Protection type Ambient temperature range Humidity range Max. total DALI wire length Max. DALI output current* DALI input current** Dimming range CCT setting range Dimensions (l x w x h) Net weight Lifetime

MCU SELECT DALI-2

MCU SELECT DALI-2 EXC TW

MCU SELECT DALI-2 TW

100-240V (50/60Hz) 0.65-2.7W 0.5-1.5mm² II IP 20 -20…+50°C 10-95%
100m@0.5mm² / 200m@1.0mm² / 300m@1.5mm² 65mA 10mA 1-100% —
80x80x53mm 162g
50.000h

100-240V (50/60Hz)

100-240V (50/60Hz)

0.65-2.7W

0.65-2.7W

0.5-1.5mm²

0.5-1.5mm²

II

II

IP 20

IP 20

-20…+50°C

-20…+50°C

10-95%

10-95%

100m@0.5mm² / 200m@1.0mm² / 300m@1.5mm² 100m@0.5mm² / 200m@1.0mm² / 300m@1.5mm²

65mA

65mA

10mA

10mA

1-100%

1-100%

2700-6500K

2700-6500K

81x81x54mm

80x80x53mm

133g

162g

50.000h

50.000h

*Mains supplied MCU (=active MCU) / **DALI supplied MCU (= passive MCU)

THANK YOU